PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.1.10.3.Continuity of Firewalls
(1) A firewall shall extend from the ground continuously through, or adjacent to, all storeys of a building or buildings so
separated, except that a firewall located above a basement storage garage conforming to Article 3.2.1.2. is permitted to
commence at the floor assembly immediately above the storage garage. (See also Sentence 3.1.10.1.(3))
(2) A firewall is permitted to terminate on the underside of a reinforced concrete roof slab provided
(a) the roof slab on both sides of the firewall has a fire-resistance rating not less than
(i) 1 h if the firewall is required to have a fire-resistance rating not less than 2 h, or
(ii) 2 h if the firewall is required to have a fire-resistance rating not less than 4 h, and
(b) there are no concealed spaces within the roof slab in that portion immediately above the firewall.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.