PART 3 — FIRE PROTECTION, OCCUPANT SAFETY AND ACCESSIBILITYUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
3.1.10.2.Rating of Firewalls
(1) A firewall that separates a building or buildings with floor areas containing a Group E or a Group F, Division 1 or 2
major occupancy shall be constructed as a fire separation of noncombustible construction having a fire-resistance rating
not less than 4 h, except that where the upper portion of a firewall separates floor areas containing other than Group E or
Group F, Division 1 or 2 major occupancies, the fire-resistance rating of the upper portion of the firewall is permitted to
be not less than 2 h.
(2) A firewall that separates a building or buildings with floor areas containing major occupancies other than Group E
or Group F, Division 1 or 2 shall be constructed as a fire separation of noncombustible construction having a fire-
resistance rating not less than 2 h.
(3) Except as permitted by Sentence (4), the required fire-resistance rating of a firewall, except for closures, shall be
provided by masonry or concrete.
(4) A firewall permitted to have a fire-resistance rating not more than 2 h need not be constructed of masonry or
concrete provided
(a) the assembly providing the fire-resistance rating is protected against damage that would compromise the integrity of
the assembly,
(b) the design conforms to Article 4.1.5.17.,
(c) the level of performance of the firewall is not less than of masonry or concrete in the areas of
(i) performance during fire conditions,
(ii) mechanical damage during the normal use of the building, and
(iii) resistance to damage from moisture,
(d) the firewall separates buildings or buildings with floor areas that do not contain
(i) a Group B, Division 1 major occupancy, or
(ii) a Group B, Division 2 major occupancy, and
(e) the firewall does not separate a building regulated by the provisions of Subsection 3.2.6. or a building within the
scope of Article 3.2.2.51. or 3.2.2.60. from another building unless the buildings on both sides of the firewall are
sprinklered.
(See Note A-3.1.10.2.(4))
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.