OBC VOLUME 2 · SUPPLEMENTARY STANDARD SB-3Updated for the 2024 Ontario Building Code

SB-3 — Fire and Sound Resistance Tables

Supplementary Standard SB-3 ("Fire and Sound Resistance Tables") forms part of Volume 2 of the 2024 Ontario Building Code. The full text is reproduced below with a linked table of contents.

2024MMAH Supplementary Standard SB-3

SB-3 Fire and Sound Resistance Tables (This Standard is based in large measure on the Fire and Sound Resistance Tables of the National Building Code of Canada 2020) The following Tables may be used to select building assemblies for compliance with Articles 5.8.1.3., Sentence 9.10.3.1.(1), Articles 9.10.5.1., 9.11.1.3., 9.11.1.4. and Sentence 9.29.5.9.(5) of Division B of the 2024 Building Code. Tables 1 and 2 have been developed from information gathered from tests. While a large number of the assemblies listed were tested, the fire-resistance and acoustical ratings for others were assigned on the basis of extrapolation of information from tests of similar assemblies. Where there was enough confidence relative to the fire performance of an assembly, the fire-resistance ratings were assigned relative to the commonly used minimum ratings of 30 min, 45 min and 1 h, including a designation of "< 30 min" for assemblies that are known not to meet the minimum 30-minute rating. Where there was not enough comparative information on an assembly to assign to it a rating with confidence, its value in the Tables has been left blank (hyphen), indicating that its rating remains to be assessed through another means These Tables are provided only for the convenience of Code users and do not limit the number of assemblies permitted to those in the Tables. The notes to Tables 1 and 2 are mandatory parts of the Tables and must be used by designers in complying with the design requirements of a particular assembly. Assemblies not listed or not given a rating in these Tables are equally acceptable provided their fire and sound resistance can be demonstrated to meet the above-noted requirements either on the basis of tests referred to in Article 9.10.3.1. and Subsection 9.11.1. or by using the data in MMAH Supplementary Standard SB-2, “Fire-Performance Ratings”. It should be noted, however, that Tables 1 and 2 of this Supplementary Standard are not based on the same assumptions as those used in MMAH Supplementary Standard SB- 2. Assemblies in Tables 1 and 2 are described through their generic descriptions and variants and the important details given in the notes to the Tables. Assumptions for MMAH Supplementary Standard SB-2 include different construction details that must be followed rigorously for the calculated ratings to be expected. These are two different methods of choosing assemblies that meet required fire ratings. Table 2 presents fire-resistance and acoustical ratings for floor, ceiling and roof assemblies. The fire-resistance ratings are appropriate for all assemblies conforming to the construction specifications given in Table 2, including applicable Table notes. Acoustical ratings for assemblies decrease with decreasing depth and decreasing separation of the structural members; the values listed for sound transmission class and impact insulation class are suitable for the minimum depth of structural members identified in the description, including applicable Table notes, and for structural member spacing of 305 mm o.c., unless other values are explicitly listed for the assembly. Adjustments to the acoustical ratings to allow for the benefit of deeper or more widely spaced structural members are given in Table Notes (9) and (10). For wall, floor and ceiling assemblies, framing spacing previously specified as 16 and 24 inch on centre has been converted to 406 and 610 mm respectively to represent actual framing spacing used in the field to accommodate modular sheathing panel dimensions. These metric dimensions are deemed to comply with test results based on reported framing spacing of 400 mm or 600 mm on centre.

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Section 1 Fire and Sound Resistance of Walls Table 1 Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing • 38 mm x 89 mm wood studs spaced 406 mm or 610 mm o.c. W1 • with or without absorptive material • 1 layer of gypsum board on each side W1 with W1a • 89 mm thick absorptive material(6) 1h 1h 36 • 15.9 mm Type X gypsum board(7) W1 with 45 min 45 min W1b • 89 mm thick absorptive material(6) 34 [1 h](8) [1 h](8) • 12.7 mm Type X gypsum board(7) W1 with 30 min W1c • 89 mm thick absorptive material(6) 30 min 32 [45 min](8) • 12.7 mm regular gypsum board(7)(9) W1 with W1d • no absorptive material 1h 1h 32 • Wood Studs • 15.9 mm Type X gypsum board(7) W1 with • Single Row W1e • no absorptive material 45 min 45 min 32 • 12.7 mm Type X gypsum board(7) • Loadbearing or Non-Loadbearing • 38 mm x 89 mm wood studs spaced 406 mm or 610 mm o.c. W2 • with or without absorptive material • 2 layers of gypsum board on each side W2 with W2a • 89 mm thick absorptive material(6) 1.5 h 2h 38 • 15.9 mm Type X gypsum board(7) W2 with W2b • 89 mm thick absorptive material(6) 1h 1.5 h 38 • 12.7 mm Type X gypsum board(7) W2 with W2c • 89 mm thick absorptive material(6) 45 min 1h 36 • 12.7 mm regular gypsum board(7) W2 with W2d • no absorptive material 1.5 h 2h 36 • 15.9 mm Type X gypsum board(7) Column 1 2 3 4 5 6 Page 2 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing Loadbearing (STC) W2 with W2e • no absorptive material 1h 1.5 h 35 • 12.7 mm Type X gypsum board(7) W2 with W2f • no absorptive material 45 min 1h 34 • 12.7 mm regular gypsum board(7) • 38 mm x 89 mm wood studs spaced 406 mm or 610 mm o.c. • 89 mm thick absorptive material(6) W3 • resilient metal channels on one side spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on each side W3 with W3a • studs spaced 406 mm o.c. 45 min 1h 45 • 15.9 mm Type X gypsum board(7) W3 with • studs spaced 610 mm o.c. 45 min 1h 48 W3b • 15.9 mm Type X gypsum board(7) • Wood Studs W3 with • Single Row W3c • studs spaced 406 mm or 610 mm o.c. 45 min 45 min 43 • 12.7 mm Type X gypsum board(7) • Loadbearing or • 38 mm x 89 mm wood studs spaced 406 mm or Non-Loadbearing 610 mm o.c. • 89 mm thick absorptive material(6) • resilient metal channels on one side spaced W4 406 mm or 610 mm o.c. • 2 layers of gypsum board on resilient metal channel side • 1 layer of gypsum board on other side W4 with 1h W4a • studs spaced 406 mm o.c. 1h 51 [1.5 h](8) • 15.9 mm Type X gypsum board(7) W4 with 1h W4b • studs spaced 610 mm o.c. 1h 54 [1.5 h](8) • 15.9 mm Type X gypsum board(7) W4 with 45 min W4c • studs spaced 406 mm o.c. 1h 49 [1 h](8) • 12.7 mm Type X gypsum board(7) W4 with 45 min W4d • studs spaced 610 mm o.c. 1h 53 [1 h](8) • 12.7 mm Type X gypsum board(7) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing • 38 mm x 89 mm wood studs spaced 406 mm or 610 mm o.c. • 89 mm thick absorptive material(6) • resilient metal channels on one side spaced W5 406 mm or 610 mm o.c. • 1 layer of gypsum board on resilient metal channel side • 2 layers of gypsum board on other side W5 with W5a • studs spaced 406 mm o.c. 45 min 1h 51 • 15.9 mm Type X gypsum board(7) W5 with W5b • studs spaced 610 mm o.c. 45 min 1h 54 • 15.9 mm Type X gypsum board(7) W5 with W5c • studs spaced 406 mm o.c. 45 min 1h 49 • 12.7 mm Type X gypsum board(7) W5 with W5d • studs spaced 610 mm o.c. 45 min 1h 53 • Wood Studs • 12.7 mm Type X gypsum board(7) • 38 mm x 89 mm wood studs spaced 406 mm or • Single Row 610 mm o.c. • Loadbearing or W6 • with or without absorptive material Non-Loadbearing • resilient metal channels on one side • 2 layers of gypsum board on each side W6 with • studs spaced 406 mm or 610 mm o.c. W6a • 89 mm thick absorptive material(6) 1.5 h 2h 55 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board(7) W6 with • studs spaced 406 mm or 610 mm o.c. with blocking at mid-height(10) W6b • 89 mm thick rock or slag fibre insulation(11) 2h 2h – • resilient metal channels spaced 406 mm or 610 mm o.c. • 15.9 mm Type X gypsum board(7) W6 with • studs spaced 406 mm o.c. with blocking at mid- height(10) W6c 2h 2h – • 89 mm thick dry-blown cellulose fibre insulation(12) • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board(7) Column 1 2 3 4 5 6 Page 4 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing W6 with • studs spaced 406 mm or 610 mm o.c. W6d • 89 mm thick absorptive material(6) 1.5 h 2h 58 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board(7) W6 with • studs spaced 406 mm o.c. W6e • 89 mm thick absorptive material(6) 1h 1.5 h 53 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board(7) W6 with • studs spaced 406 mm o.c. W6f • 89 mm thick absorptive material(6) 1h 1.5 h 55 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board(7) W6 with • Wood Studs • studs spaced 610 mm o.c. W6g • 89 mm thick absorptive material(6) 1h 1.5 h 55 • Single Row • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board(7) • Loadbearing or Non-Loadbearing W6 with • studs spaced 610 mm o.c. W6h • 89 mm thick absorptive material(6) 1h 1.5 h 58 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board(7) W6 with • studs spaced 406 mm or 610 mm o.c. • no absorptive material W6i • resilient metal channels spaced 406 mm or 1.5 h 2h 47 610 mm o.c. • 15.9 mm Type X gypsum board(7) W6 with • studs spaced 406 mm or 610 mm o.c. • no absorptive material W6j 1h 1.5 h 46 • resilient metal channels spaced 406 mm or 610 mm o.c. • 12.7 mm Type X gypsum board(7) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing • two rows 38 mm x 89 mm wood studs each spaced 406 mm or 610 mm o.c. staggered on common 38 mm x 140 mm plate W7 • 89 mm thick absorptive material on one side or 65 mm thick on each side(6) • 1 layer of gypsum board on each side W7 with W7a 1h 1h 47 • 15.9 mm Type X gypsum board(7) • W7 with 45 min 45 min W7b 45 • 12.7 mm Type X gypsum board(7) [1 h](8) [1 h](8) W7 with 30 min W7c 30 min 42 • 12.7 mm regular gypsum board(7)(9) [45 min](8) • two rows 38 mm x 89 mm wood studs each spaced 406 mm or 610 mm o.c. staggered on common 38 mm x 140 mm plate W8 • 89 mm thick absorptive material on one side or • Wood Studs 65 mm thick on each side(6) • 2 layers of gypsum board on one side • Two Rows • 1 layer of gypsum board on other side Staggered on W8 with 38 mm x 140 mm W8a 1h 1.5 h 52 • 15.9 mm Type X gypsum board(7) plate W8 with W8b 45 min 1h 50 • Loadbearing or • 12.7 mm Type X gypsum board(7) Non-Loadbearing • two rows 38 mm x 89 mm wood studs each spaced 406 mm or 610 mm o.c. staggered on common W9 38 mm x 140 mm plate • with or without absorptive material • 2 layers of gypsum board on each side W9 with • 89 mm thick absorptive material on one side or W9a 1.5 h 2h 56 65 mm thick on each side(6) • 15.9 mm Type X gypsum board(7) W9 with • 89 mm thick absorptive material on one side or W9b 1h 1.5 h 55 65 mm thick on each side(6) • 12.7 mm Type X gypsum board(7) W9 with • 89 mm thick absorptive material on one side or W9c 45 min 1h 53 65 mm thick on each side(6) • 12.7 mm regular gypsum board(7) Column 1 2 3 4 5 6 Page 6 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing W9 with W9d • no absorptive material 1.5 h 2h 48 • 15.9 mm Type X gypsum board(7) • two rows 38 mm x 89 mm wood studs each spaced 406 mm or 610 mm o.c. staggered on common 38 mm x 140 mm plate • with or without absorptive material W10 • resilient metal channels on one side spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on each side W10 with • 89 mm thick absorptive material on one side or W10a 1.5 h 2h 62 65 mm thick on each side(6) • 15.9 mm Type X gypsum board(7) W10 with • Wood Studs • 89 mm thick absorptive material on one side or W10b 1h 1.5 h 60 65 mm thick on each side(6) • Two Rows • 12.7 mm Type X gypsum board(7) Staggered on 38 mm x 140 mm W10 with plate W10c • no absorptive material 1.5 h 2h 50 • 15.9 mm Type X gypsum board(7) • Loadbearing or W10 with Non-Loadbearing W10d • no absorptive material 1h 1.5 h 48 • 12.7 mm Type X gypsum board(7) • two rows 38 mm x 89 mm wood studs each spaced 406 mm or 610 mm o.c. staggered on common 38 mm x 140 mm plate • 89 mm thick absorptive material on one side or W11 65 mm thick on each side(6) • resilient metal channels on one side spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on resilient channel side • 1 layer of gypsum board on other side W11 with W11a 1h 1h 56 • 15.9 mm Type X gypsum board(7) W11 with 45 min W11b 1h 54 • 12.7 mm Type X gypsum board(7) [1 h](8) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Fire-Resistance Rating(2)(3)(4) Typical Sound Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing • two rows 38 mm x 89 mm wood studs each spaced 406 mm or 610 mm o.c. staggered on common 38 mm x 140 mm plate • Wood Studs • 89 mm thick absorptive material on one side or 65 mm thick on each side(6) • Two Rows W12 • resilient metal channels on one side spaced Staggered on 406 mm or 610 mm o.c. 38 mm x 140 mm • 1 layer of gypsum board on resilient metal channel plate side • 2 layers of gypsum board on other side • Loadbearing or Non-Loadbearing W12 with W12a 45 min 1h 56 • 15.9 mm Type X gypsum board(7) W12 with W12b 45 min 1h 54 • 12.7 mm Type X gypsum board(7) • two rows 38 mm x 89 mm wood studs each spaced 406 mm or 610 mm o.c. on separate 38 mm x W13 89 mm plates set 25 mm apart • with or without absorptive material • 1 layer of gypsum board on each side W13 with W13a • 89 mm thick absorptive material on each side(6)(13) 1h 1h 57 • 15.9 mm Type X gypsum board(7) • Wood Studs W13 with 45 min 45 min W13b • 89 mm thick absorptive material on each side(6)(13) 57 • Two Rows on [1 h](8) [1 h](8) • 12.7 mm Type X gypsum board(7) Separate Plates W13 with • Loadbearing or W13c • 89 mm thick absorptive material on one side only(6)(13) 1h 1h 54 Non-Loadbearing • 15.9 mm Type X gypsum board(7) W13 with W13d • 89 mm thick absorptive material on one side only(6)(13) 45 min 45 min 53 • 12.7 mm Type X gypsum board(7) W13 with W13e • no absorptive material 1h 1h 45 • 15.9 mm Type X gypsum board(7) W13 with W13f • no absorptive material 45 min 45 min 45 • 12.7 mm Type X gypsum board(7) Column 1 2 3 4 5 6 Page 8 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Fire-Resistance Rating(2)(3)(4) Typical Sound Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing • two rows 38 mm x 89 mm wood studs each spaced 406 mm or 610 mm o.c. on separate 38 mm x 89 mm plates set 25 mm apart W14 • with or without absorptive material • 2 layers of gypsum board on one side • 1 layer of gypsum board on other side W14 with 1h W14a • 89 mm thick absorptive material on each side(6)(13) 1h 61 [1.5 h](8) • 15.9 Type X gypsum board(7) W14 with W14b • 89 mm thick absorptive material on each side(6)(13) 45 min 1h 61 • 12.7 Type X gypsum board(7) • with W14 W14c • 89 mm thick absorptive material on one side only(6)(13) 1h 1h 57 • 15.9 Type X gypsum board(7) W14 with W14d • 89 mm thick absorptive material on one side only(6)(13) 45 min 1h 57 • Wood Studs • 12.7 Type X gypsum board(7) W14 with • Two Rows on W14e • no absorptive material 1h 1h 51 Separate Plates • 15.9 Type X gypsum board(7) • Loadbearing or W14 with Non-Loadbearing W14f • no absorptive material 45 min 1h 51 • 12.7 Type X gypsum board(7) • two rows 38 mm x 89 mm wood studs each spaced 406 mm or 610 mm o.c. on separate 38 mm x W15 89 mm plates set 25 mm apart • with or without absorptive material • 2 layers of gypsum board on each side W15 with W15a • 89 mm thick absorptive material on each side(6)(13) 1.5 h 2h 66 • 15.9 mm Type X gypsum board(7) W6 with W15b • 89 mm thick absorptive material on each side(6)(13) 1h 1.5 h 65 • 12.7 mm Type X gypsum board(7) W15 with W15c • 89 mm thick absorptive material on each side(6)(13) 45 min 1h 61 • 12.7 mm regular gypsum board(7) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing W15 with • 89 mm thick absorptive material on one side W15d 1.5 h 2h 62 only(6)(13) • 15.9 mm Type X gypsum board(7) W15 with • 89 mm thick absorptive material on one side W15e 1h 1.5 h 60 only(6)(13) • 12.7 mm Type X gypsum board(7) W15 with • 89 mm thick absorptive material on one side W15f 45 min 1h 57 only(6)(13) • 12.7 mm regular gypsum board(7) W15 with W15g • no absorptive material 1.5 h 2h 56 • 15.9 mm Type X gypsum board(7) W15 with W15h • no absorptive material 1h 1.5 h 55 • Wood Studs • 12.7 mm Type X gypsum board(7) • Two Rows on W15 with Separate Plates W15i • no absorptive material 45 min 1h 51 • 12.7 mm regular gypsum board(7) • Loadbearing or Non-Loadbearing • two rows 38 mm x 89 mm studs, each spaced 406 mm or 610 mm o.c. on separate 38 mm x 89 mm plates set 25 mm apart W16 • resilient metal channels on one side spaced 406 mm or 610 mm o.c. • with or without absorptive material • 2 layers of gypsum board on each side W16 with W16a • 89 mm thick absorptive material on each side(6)(13) 1.5 h 2h 66 • 15.9 mm Type X gypsum board(7) W16 with • studs spaced 406 mm o.c. with blocking at mid- height(10) • 89 mm thick rock or slag fibre insulation on each W16b 2h 2h – side(11) • resilient metal channels on one side spaced 406 mm o.c. • 15.9 mm Type X gypsum board(7)(14) Column 1 2 3 4 5 6 Page 10 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing W16 with W16c • 89 mm thick absorptive material on each side(6)(13) 1h 1.5 h 65 • 12.7 mm Type X gypsum board(7) W16 with • 89 mm thick absorptive material on one side W16d 1.5 h 2h 62 only(6)(13) • Wood Studs • 15.9 mm Type X gypsum board(7) • Two Rows on W16 with Separate Plates • 89 mm thick absorptive material on one side W16e 1h 1.5 h 60 only(6)(13) • Loadbearing or • 12.7 mm Type X gypsum board(7) Non-Loadbearing W16 with W16f • no absorptive material 1.5 h 2h 56 • 12.7 mm regular gypsum board(7) W16 with W16g • no absorptive material 1h 1.5 h 55 • 15.9 mm Type X gypsum board(7) • wood studs • rock or slag fibre insulation(11) EW1 • 1 layer of gypsum board on inside • exterior sheathing and cladding EW1 with • 38 mm x 89 mm wood studs spaced 406 mm or 610 mm o.c. EW1a 1h 1h N/A • Exterior • 15.9 mm Type X gypsum board(7)(15)(16) • exterior OSB or plywood sheathing(17) or exterior • Wood Studs gypsum sheathing(18) and cladding(19) EW1 with • Single Row • 38 mm x 89 mm studs spaced 406 mm or 610 mm o.c. • Loadbearing and EW1b 45 min 1h N/A • 15.9 mm Type X gypsum board(7)(15) Non-Loadbearing • exterior OSB or plywood sheathing(17) or exterior gypsum sheathing(18) and cladding(19) EW1 with • 38 mm x 89 mm studs spaced 406 mm or 610 mm o.c. EW1c 45 min 1h N/A • 12.7 mm Type X gypsum board(7)(15)(16) • exterior OSB or plywood sheathing(17) or exterior gypsum sheathing(18) and cladding(19) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing EW1 with • 38 mm x 89 mm studs spaced 406 mm or 610 mm o.c. EW1d – 45 min N/A • 12.7 mm Type X gypsum board(7)(15) • exterior OSB or plywood sheathing(17) or exterior gypsum sheathing(18) and cladding(19) EW1 with • 38 mm x 140 mm studs spaced 406 mm o.c. • 15.9 mm Type X gypsum board(7)(15)(16) EW1e 45 min 45 min N/A • exterior wood sheathing, exterior gypsum sheathing, or insulated exterior sheathing(20) • masonry veneer cladding not less than 89 mm thick • wood studs • glass fibre insulation(21) EW2 • 1 layer of gypsum board on inside • Exterior • exterior sheathing and cladding EW2 with • Wood Studs • 38 mm × 89 mm studs spaced 406 mm o.c. EW2a • 15.9 mm Type X gypsum board(7)(15)(22) 1h 1h N/A • Single Row • exterior OSB or plywood sheathing(17) or exterior gypsum sheathing(23) and cladding(19) • Loadbearing and Non-Loadbearing EW2 with • 38 mm x 89 mm studs spaced 406 mm or 610 mm o.c. EW2b 45 min 1h N/A • 15.9 mm Type X gypsum board(7)(15)(16) • exterior OSB or plywood sheathing(17) or exterior gypsum sheathing(18) and cladding(19) EW2 with • 38 mm x 89 mm studs spaced at 406 mm o.c. EW2c • 15.9 mm Type X gypsum board(7)(15) 45 min 1h N/A • exterior OSB or plywood sheathing(17) and cladding(19) EW2 with • 38 mm x 89 mm studs spaced at 610 mm o.c. EW2d • 15.9 mm Type X gypsum board(7)(15) -– 45 min N/A • exterior OSB or plywood sheathing(17) and cladding(19) Column 1 2 3 4 5 6 Page 12 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing EW2 with • 38 mm x 89 mm studs spaced 406 mm or EW2e 610 mm o.c. -– 45 min N/A • 15.9 mm Type X gypsum board(7)(15) • exterior gypsum sheathing(18) and cladding(19) EW2 with • 38 mm x 89 mm studs spaced at 406 mm o.c. EW2f 45 min 1h N/A • 12.7 mm Type X gypsum board(7)(15)(16) exterior OSB or plywood sheathing(17) and cladding(19) EW2 with • 38 mm x 89 mm studs spaced at 610 mm o.c. EW2g • 12.7 mm Type X gypsum board(7)(15)(16) – 45 min N/A • exterior OSB or plywood sheathing(17) and cladding(19) EW2 with • 38 mm x 89 mm studs spaced 406 mm or • Exterior EW2h 610 mm o.c. – 45 min N/A • 12.7 mm Type X gypsum board(7)(15)(16) • Wood Studs • exterior gypsum sheathing(18) and cladding(19) • Single Row EW2 with • 38 mm x 89 mm studs spaced at 406 mm o.c. • Loadbearing and EW2i • 12.7 mm Type X gypsum board(7)(15) – 45 min N/A Non-Loadbearing • exterior OSB or plywood sheathing(17) and cladding(19) EW2 with • 38 mm x 140 mm studs spaced at 406 mm o.c. • 15.9 mm Type X gypsum board(7)(15)(16) EW2j 45 min 45 min N/A • exterior wood sheathing, exterior gypsum sheathing or insulated exterior sheathing(20) • masonry veneer cladding not less than 89 mm thick • wood studs • dry-blown cellulose fibre insulation(12) EW3 • 1 layer of gypsum board on inside • exterior sheathing and cladding EW3 with • 38 mm x 89 mm studs spaced at 406 mm o.c. EW3a • 15.9 mm Type X gypsum board(7)(15)(16) 1h 1h N/A • exterior OSB or plywood sheathing(17) or exterior gypsum sheathing(18) and cladding(19) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing EW3 with • 38 mm x 89 mm studs spaced at 610 mm o.c. EW3b • 15.9 mm Type X gypsum board(7)(15)(16) 1h 1h N/A • exterior OSB or plywood sheathing(17) and cladding(19) EW3 with • 38 mm x 89 mm studs spaced at 610 mm o.c. EW3c 45 min 1h N/A • 15.9 mm Type X gypsum board(7)(15)(16) exterior gypsum sheathing(18) and cladding(19) EW3 with • 38 mm x 89 mm studs spaced at 406 mm o.c. EW3d • 15.9 mm Type X gypsum board(7)(15) 45 min 1h N/A exterior OSB or plywood sheathing(17) or exterior • Exterior gypsum sheathing(18) and cladding(19) EW3 with • Wood Studs • 38 mm x 89 mm studs spaced at 610 mm o.c. EW3e • 15.9 mm Type X gypsum board(7)(15) 45 min 1h N/A • Single Row • exterior OSB or plywood sheathing(17) and cladding(19) • Loadbearing and Non-Loadbearing EW3 with • 38 mm x 89 mm studs spaced at 406 mm o.c. EW3f • 12.7 mm Type X gypsum board(7)(15)(16) 45 min 1h N/A • exterior OSB or plywood sheathing(17) or exterior gypsum sheathing(18) and cladding(19) EW3 with • 38 mm x 89 mm studs spaced at 610 mm o.c. EW3g • 12.7 mm Type X gypsum board(7)(15)(16) 45 min 1h N/A • exterior OSB or plywood sheathing(17) and cladding(19) EW3 with • 38 mm x 89 mm studs spaced at 610 mm o.c. EW3h — 45 min N/A • 12.7 mm Type X gypsum board(7)(15)(16) • exterior gypsum sheathing(18) and cladding(19) Column 1 2 3 4 5 6 Page 14 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing EW3 with • 38 mm x 89 mm studs spaced at 406 mm o.c. EW3i • 12.7 mm Type X gypsum board(7)(15) — 45 min N/A • exterior OSB or plywood sheathing(17) or exterior gypsum sheathing(18) and cladding(19) • Exterior EW3 with • Wood Studs • 38 mm x 89 mm studs spaced at 610 mm o.c. EW3j • 12.7 mm Type X gypsum board(7)(15) — 45 min N/A • Single Row • exterior OSB or plywood sheathing(17) and cladding(19) • Loadbearing and EW3 with Non-Loadbearing • 38 mm x 140 mm studs spaced at 406 mm o.c. • 15.9 mm Type X gypsum board(7)(15)(16) EW3k 45 min 45 min N/A • exterior wood sheathing, exterior gypsum sheathing or insulated exterior sheathing(20) • masonry veneer cladding not less than 89 mm thick • 31 mm x 64 mm steel studs spaced 406 mm or 610 mm o.c. S1 • with or without absorptive material • 1 layer of gypsum board on each side S1 with • studs spaced 610 mm o.c. 45 min S1a — 43 • 65 mm thick absorptive material(6) [1 h](8) • Non-Loadbearing Steel Studs • 15.9 mm Type X gypsum board(7) S1 with • 0.46 mm (25 Gauge) • studs spaced 406 mm o.c. 45 min S1b — 39 • 65 mm thick absorptive material(6) [1 h](8) • 15.9 mm Type X gypsum board(7) S1 with • studs spaced 406 mm or 610 mm o.c. S1c — 45 min 35 • no absorptive material • 15.9 mm Type X gypsum board(7) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing • 31 mm x 64 mm steel studs spaced 406 mm or 610 mm o.c. S2 • with or without absorptive material • 1 layer of gypsum board on one side • 2 layers of gypsum board on other side S2 with • studs spaced 610 mm o.c. S2a — 1h 50 • 65 mm thick absorptive material(6) • 15.9 mm Type X gypsum board(7) S2 with • studs spaced 406 mm o.c. S2b — 1h 44 • 65 mm thick absorptive material(6) • 15.9 mm Type X gypsum board(7) S2 with • studs spaced 610 mm o.c. S2c — 1h 50 • 65 mm thick absorptive material(6) • Non-Loadbearing • 12.7 mm Type X gypsum board(7) Steel Studs S2 with • studs spaced 406 mm o.c. • 0.46 mm (25 Gauge) S2d — 1h 42 • 65 mm thick absorptive material(6) • 12.7 mm Type X gypsum board(7) S2 with • studs spaced 610 mm o.c. S2e — 1h 41 • no absorptive material • 15.9 mm Type X gypsum board(7) S2 with • studs spaced 406 mm o.c. S2f — 1h 37 • no absorptive material • 15.9 mm Type X gypsum board(7) S2 with • studs spaced 610 mm o.c. S2g — 1h 40 • no absorptive material • 12.7 mm Type X gypsum board(7) S2 with • studs spaced 406 mm o.c. S2h — 1h 35 • no absorptive material • 12.7 mm Type X gypsum board(7) Column 1 2 3 4 5 6 Page 16 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing • 31 mm x 64 mm steel studs spaced 406 mm or 610 mm o.c. S3 • with or without absorptive material • 2 layers of gypsum board on each side S3 with • studs spaced 610 mm o.c. S3a — 2h 54 • 65 mm thick absorptive material(6) • 15.9 mm Type X gypsum board(7) S3 with • studs spaced 406 mm o.c. S3b — 2h 51 • 65 mm thick absorptive material(6) • 15.9 mm Type X gypsum board(7) S3 with • studs spaced 610 mm o.c. S3c — 1.5 h 53 • 65 mm thick absorptive material(6) • 12.7 mm Type X gypsum board(7) S3 with • studs spaced 406 mm o.c. S3d — 1.5 h 47 • 65 mm thick absorptive material(6) • 12.7 mm Type X gypsum board(7) • Non-Loadbearing S3 with Steel Studs • studs spaced 610 mm o.c. S3e — 1h 49 • 65 mm thick absorptive material(6) • 0.46 mm (25 Gauge) • 12.7 mm regular gypsum board(7) S3 with • studs spaced 406 mm o.c. S3f — 1h 41 • 65 mm thick absorptive material(6) • 12.7 mm regular gypsum board(7) S3 with • studs spaced 610 mm o.c. S3g — 2h 45 • no absorptive material • 15.9 mm Type X gypsum board(7) S3 with • studs spaced 406 mm o.c. S3h — 2h 42 • no absorptive material • 15.9 mm Type X gypsum board(7) S3 with • studs spaced 610 mm o.c. S3i — 1.5 h 44 • no absorptive material • 12.7 mm Type X gypsum board(7) S3 with • studs spaced 406 mm o.c. S3j — 1.5 h 39 • no absorptive material • 12.7 mm Type X gypsum board(7) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing S3 with • studs spaced 610 mm o.c. S3k — 1h 40 • no absorptive material • 12.7 mm regular gypsum board(7) S3 with • studs spaced 406 mm o.c. S3l — 1h 37 • no absorptive material • 12.7 mm regular gypsum board(7) • 31 mm x 92 mm steel studs spaced 406 mm or 610 mm o.c. S4 • with or without absorptive material • 1 layer of gypsum board on each side S4 with • studs spaced 610 mm o.c. 45 min S4a — 48 • 89 mm thick absorptive material(6) [1 h](8) • 15.9 mm Type X gypsum board(7) S4 with • studs spaced 406 mm o.c. 45 min S4b — 47 • 89 mm thick absorptive material(6) [1 h](8) • Non-Loadbearing • 15.9 mm Type X gypsum board(7) Steel Studs S4 with • 0.46 mm (25 Gauge) • studs spaced 610 mm o.c. S4c — 45 min 38 • no absorptive material • 15.9 mm Type X gypsum board(7) S4 with • studs spaced 406 mm o.c. S4d — 45 min 38 • no absorptive material • 15.9 mm Type X gypsum board(7) • 31 mm x 92 mm steel studs spaced 406 mm or 610 mm o.c. S5 • with or without absorptive material • 1 layer of gypsum board on one side • 2 layers of gypsum board on other side S5 with • studs spaced 610 mm o.c. 1h S5a — 53 • 89 mm thick absorptive material(6) [1.5 h](8) • 15.9 mm Type X gypsum board(7) S5 with • studs spaced 406 mm o.c. 1h S5b — 52 • 89 mm thick absorptive material(6) [1.5 h](8) • 15.9 mm Type X gypsum board(7) Column 1 2 3 4 5 6 Page 18 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing S5 with • studs spaced 610 mm o.c. 1h S5c — 51 • 89 mm thick absorptive material(6) [1.5 h](8) • 12.7 mm Type X gypsum board(7) S5 with • studs spaced 406 mm o.c. 1h S5d — 50 • 89 mm thick absorptive material(6) [1.5 h](8) • 12.7 mm Type X gypsum board(7) S5 with • studs spaced 610 mm o.c. S5e — 1h 43 • no absorptive material • 15.9 mm Type X gypsum board(7) S5 with • studs spaced 406 mm o.c. S5f — 1h 42 • no absorptive material • 15.9 mm Type X gypsum board(7) • Non-Loadbearing S5 with Steel Studs • studs spaced 610 mm o.c. S5g — 1h 41 • no absorptive material • 0.46 mm (25 Gauge) • 12.7 mm Type X gypsum board(7) S5 with • studs spaced 406 mm o.c. S5h — 1h 40 • no absorptive material • 12.7 mm Type X gypsum board(7) • 31 mm x 92 mm steel studs spaced 406 mm or 610 mm o.c. S6 • with or without absorptive material • 2 layers of gypsum board on each side S6 with • studs spaced 610 mm o.c. S6a — 2h 56 • 89 mm thick absorptive material(6) • 15.9 mm Type X gypsum board(7) S6 with • studs spaced 406 mm o.c. S6b — 2h 55 • 89 mm thick absorptive material(6) • 15.9 mm Type X gypsum board(7) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing S6 with • studs spaced 610 mm o.c. S6c — 1.5 h 55 • 89 mm thick absorptive material(6) • 12.7 mm Type X gypsum board(7) S6 with • studs spaced 406 mm o.c. S6d — 1.5 h 54 • 89 mm thick absorptive material(6) • 12.7 mm Type X gypsum board(7) S6 with • studs spaced 610 mm o.c. S6e — 1h 50 • 89 mm thick absorptive material(6) • 12.7 mm regular gypsum board(7) S6 with • studs spaced 406 mm o.c. S6f — 1h 48 • 89 mm thick absorptive material(6) • 12.7 mm regular gypsum board(7) S6 with • studs spaced 610 mm o.c. S6g — 2h 47 • Non-Loadbearing • no absorptive material Steel Studs • 15.9 mm Type X gypsum board(7) S6 with • 0.46 mm (25 Gauge) • studs spaced 406 mm o.c. S6h — 2h 45 • no absorptive material • 15.9 mm Type X gypsum board(7) S6 with • studs spaced 610 mm o.c. S6i — 1.5 h 45 • no absorptive material • 12.7 mm Type X gypsum board(7) S6 with • studs spaced 406 mm o.c. S6j — 1.5 h 44 • no absorptive material • 12.7 mm Type X gypsum board(7) S6 with • studs spaced 610 mm o.c. S6k — 1h 41 • no absorptive material • 12.7 mm regular gypsum board(7) S6 with • studs spaced 406 mm o.c. S6l — 1h 39 • no absorptive material • 12.7 mm regular gypsum board(7) Column 1 2 3 4 5 6 Page 20 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing • 31 mm x 152 mm steel studs spaced 406 mm or 610 mm o.c. S7 • with or without absorptive material • 1 layer of gypsum board on each side S7 with 45 min S7a • 150 mm thick absorptive material(6) — 51 [1 h](8) • 15.9 mm Type X gypsum board(7) S7 with S7b • no absorptive material — 45 min 41 • 15.9 mm Type X gypsum board(7) • 31 mm x 152 mm steel studs spaced 406 mm or 610 mm o.c. S8 • with or without absorptive material • 1 layer of gypsum board on one side • 2 layers of gypsum board on other side S8 with 1h S8a • 150 mm thick absorptive material(6) — 55 • Non-Loadbearing [1.5 h](8) • 15.9 mm Type X gypsum board(7) Steel Studs S8 with 1h S8b • 150 mm thick absorptive material(6) — 54 • 0.46 mm (25 Gauge) [1.5 h](8) • 12.7 mm Type X gypsum board(7) S8 with S8c • no absorptive material — 1h 45 • 15.9 mm Type X gypsum board(7) S8 with S8d • no absorptive material — 1h 44 • 12.7 mm Type X gypsum board(7) • 31 mm x 152 mm steel studs spaced 406 mm or 610 mm o.c. S9 • with or without absorptive material • 2 layers of gypsum board on each side S9 with S9a • 150 mm thick absorptive material(6) — 2h 59 • 15.9 mm Type X gypsum board(7) S9 with S9b • 150 mm thick absorptive material(6) — 1.5 h 57 • 12.7 mm Type X gypsum board(7) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing S9 with S9c • 150 mm thick absorptive material(6) — 1h 53 • 12.7 mm regular gypsum board(7) S9 with • Non-Loadbearing S9d • no absorptive material — 2h 49 Steel Studs • 15.9 mm Type X gypsum board(7) S9 with • 0.46 mm (25 Gauge) S9e • no absorptive material — 1.5 h 47 • 12.7 mm Type X gypsum board(7) S9 with S9f • no absorptive material — 1h 43 • 12.7 mm regular gypsum board(7) • 41 mm x 92 mm loadbearing steel studs spaced 406 mm or 610 mm o.c. S10 • with or without cross-bracing on one side • with or without absorptive material • 2 layers of gypsum board on each side S10 with S10a • 89 mm thick absorptive material(6) 1h — 38 • 15.9 mm Type X gypsum board(7) S10 with 45 min S10b • 89 mm thick absorptive material(6) — 38 • Loadbearing Steel [1 h](8) • 12.7 mm Type X gypsum board(7) Studs S10 with • 0.84 mm to 1.52 mm S10c • 89 mm thick absorptive material(6) — — 36 thickness • 12.7 mm regular gypsum board(7) S10 with S10d • no absorptive material 1h — 36 • 15.9 mm Type X gypsum board(7) S10 with S10e • no absorptive material 1h — 35 • 12.7 mm Type X gypsum board(7) S10 with S10f • no absorptive material — — 34 • 12.7 mm regular gypsum board(7) Column 1 2 3 4 5 6 Page 22 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing • 41 mm x 92 mm loadbearing steel studs spaced 406 mm or 610 mm o.c. • with or without cross-bracing on one side S11 • with or without absorptive material • resilient metal channels on one side • 1 layer of gypsum board on each side S11 with • 89 mm thick absorptive material(6) S11a — — 50 • resilient metal channels spaced at 610 mm o.c. • 15.9 mm Type X gypsum board(7) S11 with • 89 mm thick absorptive material(6) S11b — — 47 • resilient metal channels spaced at 406 mm o.c. • 15.9 mm Type X gypsum board(7) S11 with • no absorptive material S11c — — 41 • resilient metal channels spaced at 610 mm o.c. • Loadbearing Steel • 15.9 mm Type X gypsum board(7) Studs S11 with • no absorptive material • 0.84 mm to 1.52 mm S11d — — 39 • resilient metal channels spaced at 406 mm o.c. thickness • 15.9 mm Type X gypsum board(7) S11 with • 89 mm thick absorptive material(6) S11e — — 47 • resilient metal channels spaced at 610 mm o.c. • 12.7 mm Type X gypsum board(7) S11 with • 89 mm thick absorptive material(6) S11f — — 45 • resilient metal channels spaced at 406 mm o.c. • 12.7 mm Type X gypsum board(7) S11 with • no absorptive material S11g — — 38 • resilient metal channels spaced at 610 mm o.c. • 12.7 mm Type X gypsum board(7) S11 with • no absorptive material S11h — — 36 • resilient metal channels spaced at 406 mm o.c. • 12.7 mm Type X gypsum board(7) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing • 41 mm x 92 mm loadbearing steel studs spaced 406 mm or 610 mm o.c. • with or without cross-bracing on one side S12 • with or without absorptive material • resilient metal channels on one side • 2 layers of gypsum board on resilient channel side • 1 layer of gypsum board on other side S12 with • 89 mm thick absorptive material(6) S12a — — 54 • resilient metal channels spaced at 610 mm o.c. • 15.9 mm Type X gypsum board(7) S12 with • 89 mm thick absorptive material(6) S12b — — 52 • resilient metal channels spaced at 406 mm o.c. • 15.9 mm Type X gypsum board(7) S12 with • no absorptive material S12c — — 46 • resilient metal channels spaced at 610 mm o.c. • Loadbearing Steel • 15.9 mm Type X gypsum board(7) Studs S12 with • 0.84 mm to 1.52 mm • no absorptive material S12d — — 43 thickness • resilient metal channels spaced at 406 mm o.c. • 15.9 mm Type X gypsum board(7) S12 with • 89 mm thick absorptive material(6) S12e — — 52 • resilient metal channels spaced at 610 mm o.c. • 12.7 mm Type X gypsum board(7) S12 with • 89 mm thick absorptive material(6) S12f — — 50 • resilient metal channels spaced at 406 mm o.c. • 12.7 mm Type X gypsum board(7) S12 with • no absorptive material S12g — — 43 • resilient metal channels spaced at 610 mm o.c. • 12.7 mm Type X gypsum board(7) S12 with • no absorptive material S12h — — 41 • resilient metal channels spaced at 406 mm o.c. • 12.7 mm Type X gypsum board(7) Column 1 2 3 4 5 6 Page 24 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing • 41 mm x 92 mm loadbearing steel studs spaced 406 mm or 610 mm o.c. • with or without absorptive material • resilient metal channels on one side spaced at S13 406 mm o.c. • 2 layers of gypsum board on resilient channel side • 1 layer shear membrane and 1 layer gypsum board on other side S13 with • 89 mm thick absorptive material(6) S13a 30 min — 57 • 12.7 mm OSB shear membrane • 12.7 mm Type X gypsum board(7) • 41 mm x 92 mm loadbearing steel studs spaced 406 mm or 610 mm o.c. S14 • with or without absorptive material • resilient metal channels on one side • 2 layers of gypsum board on each side S14 with • Loadbearing Steel • 89 mm thick absorptive material(6) S14a 1h — 60 Studs • resilient metal channels spaced at 610 mm o.c. • 15.9 mm Type X gypsum board(7) • 0.84 mm to 1.52 mm S14 with thickness • 89 mm thick absorptive material(6) 45 min S14b — 57 • resilient metal channels spaced at 610 mm o.c. [1 h](8) • 12.7 mm Type X gypsum board(7) S14 with • 89 mm thick absorptive material(6) S14c — — 54 • resilient metal channels spaced at 610 mm o.c. • 12.7 mm regular gypsum board(7) S14 with • 89 mm thick absorptive material 45 min S14d — 55 • resilient metal channels spaced at 406 mm o.c. [1 h](8) • 12.7 mm Type X gypsum board(7) S14 with • no absorptive material S14e 1h — 51 • resilient metal channels spaced at 610 mm o.c. • 15.9 mm Type X gypsum board(7) S14 with • no absorptive material S14f — — 45 • resilient metal channels spaced at 610 mm o.c. • 12.7 mm regular gypsum board(7) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing S14 with • no absorptive material S14g 1h — 47 • resilient metal channels spaced at 406 mm o.c. • 12.7 mm Type X gypsum board(7) S14 with • studs at 610 mm o.c. S14h • 89 mm thick absorptive material 1h — 60 • resilient metal channels spaced at 406 mm o.c. • 15.9 mm Type X gypsum board(7) S14 with • studs at 406 mm o.c. S14i • 89 mm thick absorptive material 1h — 58 • resilient metal channels spaced at 406 mm o.c. • 15.9 mm Type X gypsum board(7) S14 with • studs at 610 mm o.c. S14j • no absorptive material 1h — 51 • resilient metal channels spaced at 406 mm o.c. • Loadbearing Steel • 15.9 mm Type X gypsum board(7) Studs S14 with • 0.84 mm to 1.52 mm • studs at 406 mm o.c. thickness S14k • no absorptive material 1h — 49 • resilient metal channels spaced at 406 mm o.c. • 15.9 mm Type X gypsum board(7) S14 with • studs at 406 mm o.c. S14l • no absorptive material 1h — 49 • resilient metal channels spaced at 610 mm o.c. • 12.7 mm Type X gypsum board(7) S14 with • studs at 610 mm o.c. S14m • no absorptive material 1h — 50 • resilient metal channels spaced at 610 mm o.c. • 12.7 mm regular gypsum board(7) • 2 rows of 41 mm x 92 mm loadbearing steel studs spaced 406 mm or 610 mm o.c. staggered on 152 mm common plate S15 • with cross-bracing • with or without absorptive material • 2 layers of gypsum board on each side Column 1 2 3 4 5 6 Page 26 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Fire-Resistance Rating(2)(3)(4) Typical Sound Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing (STC) Loadbearing S15 with S15a • 89 mm thick absorptive material in each cavity(6) 1h — 68 • 15.9 mm Type X gypsum board(7) S15 with • Loadbearing Steel S15b • 89 mm thick absorptive material in each cavity(6) 1h — 68 Studs • 12.7 mm Type X gypsum board(7) S15 with • 0.84 mm to 1.52 mm S15c • no absorptive material 1.5 h — 52 thickness • 15.9 mm Type X gypsum board(7) S15 with S15d • no absorptive material 1h — 52 • 12.7 mm Type X gypsum board(7) B1 • 140 mm or 190 mm concrete block B1a • 140 mm bare concrete block(5) 1h 1h 48 B1b • 190 mm bare concrete block(5) 1.5 h 1.5 h 50 • 140 mm or 190 mm concrete block • no absorptive material B2 • 1 layer of gypsum-sand plaster or gypsum board on each side • Hollow Concrete B2 with Block (Normal B2a • 140 mm concrete block 2h 2h 50 Weight Aggregate) • 12.7 mm gypsum-sand plaster B2 with • 140 mm concrete block B2b 2h 2h 47 • 12.7 mm Type X gypsum board or 15.9 mm Type X gypsum board(7) B2 with B2c • 140 mm concrete block 1.5 h 1.5 h 46 • 12.7 mm regular gypsum board(7) B2 with B2d • 190 mm concrete block 2.5 h 2.5 h 51 • 12.7 mm gypsum-sand plaster B2 with B2e • 190 mm concrete block 3h 3h 50 • 15.9 mm Type X gypsum board(7) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing Loadbearing (STC) B2 with B2f • 190 mm concrete block 2.5 h 2.5 h 49 • 12.7 mm Type X gypsum board(7) B2 with B2g • 190 mm concrete block 2h 2h 48 • 12.7 mm regular gypsum board(7) • 140 mm or 190 mm concrete block • resilient metal channels on one side spaced at 406 mm or 610 mm o.c. B3 • absorptive material filling resilient metal channel space(6) • 1 layer of gypsum board on each side B3 with • 140 mm concrete block B3a 2h 2h 51 • 12.7 mm Type X gypsum board or 15.9 mm Type X gypsum board(7) B3 with B3b • 140 mm concrete block 1.5 h 1.5 h 48 • 12.7 mm regular gypsum board(7)(9) • Hollow Concrete B3 with Block (Normal B3c • 190 mm concrete block 3h 3h 54 Weight Aggregate) • 15.9 mm Type X gypsum board(7) B3 with B3d • 190 mm concrete block 2.5 h 2.5 h 53 • 12.7 mm Type X gypsum board(7) B3 with B3e • 190 mm concrete block 2h 2h 51 • 12.7 mm regular gypsum board(7)(9) • 140 mm or 190 mm concrete block • resilient metal channels on each side spaced at B4 406 mm or 610 mm o.c. • with or without absorptive material • 1 layer of gypsum board on each side B4 with • 140 mm concrete block B4a 2h 2h 47 • 12.7 mm Type X gypsum board or 15.9 mm Type X gypsum board(7) B4 with B4b • 140 mm concrete block 1.5 h 1.5 h 42 • 12.7 mm regular gypsum board(7)(9) Column 1 2 3 4 5 6 Page 28 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Fire-Resistance Rating(2)(3)(4) Typical Sound Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing Loadbearing (STC) B4 with B4c • 190 mm concrete block 3h 3h 50 • 15.9 mm Type X gypsum board(7) B4 with B4d • 190 mm concrete block 2.5 h 2.5 h 49 • 12.7 mm Type X gypsum board(7) B4 with B4e • 190 mm concrete block 2h 2h 45 • 12.7 mm regular gypsum board(7)(9) • 190 mm concrete block • 38 mm x 38 mm horizontal or vertical wood B5 strapping on one side spaced at 610 mm o.c. • with or without absorptive material • 1 layer of gypsum board on each side B5 with B5a 3h 3h 54 • 15.9 mm Type X gypsum board(7) B5 with B5b 2.5 h 2.5 h 53 • 12.7 mm Type X gypsum board(7) • Hollow Concrete B5 with B5c 2h 2h 51 Block (Normal • 12.7 mm regular gypsum board(7)(9) Weight Aggregate) • 140 mm or 190 mm concrete block • 38 mm x 38 mm horizontal or vertical wood strapping on each side spaced at 610 mm o.c. B6 • absorptive material filling strapping space on each side(6) • 1 layer of gypsum board on each side B6 with • 140 mm concrete block B6a • 12.7 mm Type X gypsum board or 15.9 mm Type X 2h 2h 57 gypsum board(7) • B6 with B6b • 140 mm concrete block 1.5 h 1.5 h 56 • 12.7 mm regular gypsum board(7)(9) B6 with B6c • 190 mm concrete block 3h 3h 60 • 15.9 mm Type X gypsum board(7) B6 with B6d • 190 mm concrete block 2.5 h 2.5 h 59 • 12.7 mm Type X gypsum board(7) Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing Loadbearing (STC) B6 with B6e • 190 mm concrete block 2h 2h 57 • 12.7 mm regular gypsum board(7)(9) • 190 mm concrete block • 65 mm steel studs each side spaced at 610 mm o.c. B7 • absorptive material filling stud space on each side(6) • 1 layer of gypsum board on each side B7 with B7a 3h 3h 71 • 15.9 mm Type X gypsum board(7) B7 with B7b 2.5 h 2.5 h 70 • 12.7 mm Type X gypsum board(7) B7 with B7c 2h 2h 69 • 12.7 mm regular gypsum board(7)(9) • 190 mm concrete block • 38 mm x 64 mm wood studs on each side spaced B8 at 610 mm o.c. • absorptive material filling stud space on each side(6) • Hollow Concrete • 1 layer of gypsum board on each side Block (Normal Weight Aggregate) B8 with B8a 3h 3h 71 • 15.9 mm Type X gypsum board(7) B8 with B8b 2.5 h 2.5 h 70 • 12.7 mm Type X gypsum board(7) B8 with B8c • 12.7 mm regular gypsum board(7)(9) 2h 2h 69 • • 190 mm concrete block • 50 mm metal Z-bars on each side spaced at 610 mm o.c. (or 38 mm x 38 mm horizontal or vertical wood strapping plus resilient metal B9 channels) • absorptive material filling Z-bar space on each side(6) • 1 layer of gypsum board on each side B9 with B9a 3h 3h 65 • 15.9 mm Type X gypsum board(7) B9 with B9b 2.5 h 2.5 h 64 • 12.7 mm Type X gypsum board(7) B9 with B9c 2h 2h 63 • 12.7 mm regular gypsum board(7)(9) Column 1 2 3 4 5 6 Page 30 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 1 (Cont’d) Fire and Sound Resistance of Walls(1) Typical Sound Fire-Resistance Rating(2)(3)(4) Wall Transmission Type of Wall Description Number Non- Class(2)(4)(5) Loadbearing Loadbearing (STC) • 190 mm concrete block • resilient metal channels on one side spaced at 610 mm o.c. B10 • absorptive material filling resilient metal channel space(6) • 2 layers of gypsum board on one side only B10 with B10a 3h 3h 56 • 15.9 mm Type X gypsum board(7) B10 with B10b 2.5 h 2.5 h 55 • 12.7 mm Type X gypsum board(7) B10 with B10c 2h 2h 54 • 12.7 mm regular gypsum board(7) Column 1 2 3 4 5 6 Notes to Table 1: (1) Reserved. (2) Fire-resistance ratings and STC ratings of wood-frame construction were evaluated only for assemblies with solid-sawn 38 mm × 89 mm lumber. However, the fire-resistance ratings and STC ratings provided for 38 mm × 89 mm wood-frame assemblies may be applied to wood-frame assemblies with solid-sawn 38 mm × 140 mm lumber; in some cases the ratings may be conservative. Where 38 mm × 140 mm framing is used and absorptive material is called for, the absorptive material must be 140 mm thick. (See 1.2.1.(2) in MMAH Supplementary Standard SB-2 for the significance of fire-resistance ratings). The STC ratings may also be applied to fingerjoined lumber. The fire-resistance ratings are applicable to wall assemblies using fingerjoined lumber that has been manufactured with a heat-resistant adhesive (HRA) in accordance with NLGA special product standard SPS-1-2017 “Fingerjoined Structural Lumber”, or SPS-3-2017, “Fingerjoined ‘Vertical Stud Use Only’ Lumber”. (See also Appendix Note A-9.23.10.4.(1) under Division B in Appendix A of the Building Code). (3) For all fire-resistance ratings, the given spacing for framing is a maximum value. (4) Sound ratings listed are based on the most reliable laboratory test data available for specimens conforming to installation details required by CSA A82.31-M1980, “Gypsum Board Application”. Results of specific tests may differ slightly because of measurement precision and minor variations in construction details. These results should only be used where the actual construction details, including spacing of fasteners and supporting framing, correspond exactly to the details of the test specimens on which the ratings are based. For wood- and steel-framed assemblies, if the fasteners are spaced less than 300 mm o.c., subtract 1 from the sound transmission class value; if the fasteners are spaced less than 200 mm o.c., subtract 2 from the sound transmission class value. Narrower fastener spacing is not detrimental to the fire-resistance rating. Assemblies with sound transmission class ratings of 50 or more require methods to minimize airborne sound transmission at electrical boxes and other openings, and at the junction of intersecting walls and floors, except intersection of walls constructed of concrete or solid masonry units where the masonry joints at the intersection are mortared. (5) Sound ratings are only valid where there are no discernible cracks or voids in the visible surfaces. For concrete block walls, surfaces must be sealed by at least 2 coats of paint or other surface finish described in Section 9.29. of Division B of the Building Code to prevent sound leakage. (6) Sound absorptive material includes fibre processed from rock, slag, glass or cellulose fibre. It must fill at least 90% of the cavity thickness for the wall to provide the listed STC value. The absorptive material should not overfill the cavity to the point of producing significant outward pressure on the finishes; such an assembly will not achieve the STC rating. Where the absorptive material used with steel stud assemblies is in batt form, “steel stud batts”, which are wide enough to fill the cavity from the web of one stud to the web of the adjacent studs, must be used.

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

(7) The complete descriptions of indicated finishes are as follows: • 12.7 mm regular gypsum board — 12.7 mm regular gypsum board conforming to Article 9.29.5.2. of Division B of the Building Code. • 12.7 mm Type X gypsum board — 12.7 mm special fire-resistant Type X gypsum board conforming to Article 9.29.5.2. of Division B of the Building Code. • 15.9 mm Type X gypsum board — 15.9 mm special fire-resistant Type X gypsum board conforming to Article 9.29.5.2. of Division B of the Building Code. • Except for exterior walls (see Note 15), the outer layer of finish on both sides of the wall must have its joints taped and finished. • Except as otherwise required for fastener spacing (see Table Notes (14), (16) and (22)), fastener type, spacing and penetration depth for the attachment of gypsum board must conform to Subsection 9.29.5. of Division B of the Building Code and fasteners must consist of • nails or screws when attaching gypsum board to wood studs or wood strapping, and • screws when attaching gypsum board to cold-formed steel studs or resilient metal channels. (8) Absorptive material required for the higher fire-resistance rating shall be mineral fibre processed from rock or slag with a mass pr unit of wall surface of at least 4.8 kg/m² for 150 mm thickness, 2.8 kg/m² for 89 mm thickness and 2.0 kg/m² for 65 mm thickness and shall completely fill the wall cavity. For assemblies with double wood studs on separate plates, absorptive material is required in the stud cavities on both sides. (9) Regular gypsum board used in single layer assemblies must be installed so all edges are supported. (10) The fire-resistance rating values are achieved as follows: • for a single row of studs, by installing blocking at a spacing of not more than 1 524 mm o.c. as shown in Case A of Figure 5, or • for two rows of studs on separate plates, by installing blocking in both rows at a spacing of not more than 1 524 mm o.c. as shown in Case B of Figure 5. (11) The mineral fibre insulation processed from rock or slag shall have a mass per unit area of wall surface of not less than 4.48 kg/m 2 for 140 mm thickness and 2.85 kg/m2 for 89 mm thickness and shall completely fill the wall cavity. (12) The dry-blown cellulose fibre insulation shall have a mass per unit area of wall surface of not less than 6.80 kg/m2 for 140 mm thickness and 4.32 kg/m2 for 89 mm thickness and shall completely fill the wall cavity. (13) Where bracing material, such as diagonal lumber or plywood, OSB, gypsum board or fibreboard sheathing is installed on the inner face of one row of studs in double stud assemblies, the STC rating will be reduced by 3 for any assemblies containing absorptive material in both rows of studs or in the row of studs opposite to that to which the bracing material is attached. Attaching such layers on both inner faces of the studs may drastically reduce the STC value but enough data to permit assignment of STC ratings for this situation is not available. The fire-resistance rating is not affected by the inclusion of such bracing. (14) For the attachment of the gypsum board, fasteners shall be spaced at not more than 200 mm (nominal) o.c. along the framing members and resilient metal channels in both the base and face layers. (15) For exterior walls, the finish joints must be taped and finished for the outer layer of the interior side only. (16) For the attachment of the gypsum board on the interior side of exterior wall assemblies, fasteners shall be spaced at not more than 200 mm (nominal) o.c. along the framing members. All joints shall be backed with lumber having the same dimensions as the framing members as shown in Figures 6 and 7. For EW1e, EW2j and EW3k walls, blocking shall be installed at a spacing of not more than 1 524 mm o.c. as shown in Case A of Figure 5 where joints are backed at a spacing of more than 1 524 mm o.c. along the height of the wall. (17) The exterior OSB or plywood sheathing shall be not less than 11.1 mm thick and shall be installed with a gap of not less than 2 mm between sheets. Fastener types and spacing shall conform to Table 9.23.3.5.-A of Division B of the Building Code. All joints shall be backed with lumber having the same dimensions as the framing members as shown in Figures 6 and 7. (18) The exterior gypsum sheathing shall be Type X gypsum sheathing not less than 15.9 mm thick. Fasteners shall be spaced at not more than 200 mm (nominal) o.c. along the framing members. (19) Any cladding allowed under Part 9 is permitted. The cladding can include foamed plastic and other insulations outboard of the sheathing, where permitted by spatial separation requirements in Subsection 9.10.14. or 9.10.15. of Division B of the Building Code. Where OSB or plywood sheathing acts as the cladding, no additional outboard cladding is required, but is permitted. Page 32 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

(20) Includes any exterior wall sheathing listed in Table 9.23.17.2.-A of Division B of the Building Code and masonry veneer cladding conforming to Section 9.20. of Division B of the Building Code. Foamed plastic sheathing is permitted in EW1e, EW2j and EW3k walls without the use of other sheathing, provided it is directly attached to the framing. (21) The glass fibre insulation shall have a mass per unit area of wall surface of not less than 1.30 kg/m 2 for 140 mm thickness and 1.0 kg/m2 for 89 mm thickness and shall completely fill the wall cavity. (22) For the attachment of the gypsum board on the interior side of exterior wall assemblies, fasteners shall be spaced at not more than 150 mm (nominal) o.c. along the edges and 200 mm (nominal) o.c. along the intermediate supports. All joints shall be backed with lumber having the same dimensions as the framing members as shown in Figures 6 and 7. (23) The exterior gypsum sheathing shall be not less than 12.7 mm thick. Fasteners shall be spaced at not more than 200 mm (nominal) o.c. along the framing members.

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Section 2 Fire and Sound Resistance of Floors, Ceilings and Roofs Table 2 Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F1 • concrete floors • 90 mm reinforced concrete with 20 mm minimum F1a 1h 47 23 cover over reinforcing steel • 130 mm reinforced concrete with 25 mm F1b minimum 2h 52 27 Concrete Slabs cover over reinforcing steel • pre-stressed hollow core slab 200 mm deep with F1c 1h 50 28 25 mm minimum cover over reinforcing steel • 150 mm composite slab on 75 mm steel deck F1d — 51 21 with 152 x 152 x MW3.8 x MW3.8 wire mesh • 150 mm composite slab on 75 mm steel deck with 152 x 152 x MW3.8 x MW3.8 wire mesh • resilient metal channels spaced 406 mm or F1e 1.5 h 57 36 610 mm o.c. • 2 layers of 12.7 mm Type X gypsum board or 2 layers of 15.9 mm Type X gypsum board F2 • open web steel joists with concrete floor Open Web Steel Joists • 50 mm thick concrete deck • on open web steel joists spaced 406 mm o.c. • steel furring channels spaced not more than F2a 45 min 53 27 610 mm o.c. wired to underside of joists • 1 layer of 15.9 mm Type X gypsum board on ceiling side Column 1 2 3 4 5 6 Page 34 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Assembly Fire- Resistance Transmission Insulation Type of Assembly Description(2)(3)(4) Number Rating(5)(6)(7)(8) Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) (STC) (IIC) Floors and Ceilings • 65 mm regular concrete minimum 155 kg/m2 • on composite steel joists spaced 1250 mm o.c. • steel furring channels spaced not more than Open Web Steel Joists F2b 1.5 h 53 28 610 mm o.c. wired to underside of joists • 1 layer of 12.7 mm Type X gypsum board or 15.9 mm Type X gypsum board on ceiling side • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F3(14) • on wood joists or wood I-joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 1 layer of gypsum board on ceiling side F3 with F3a • no absorptive material in cavity — 29 27 • 15.9 mm Type X gypsum board F3 with F3b • absorptive material in cavity — 31 30 Wood Floor Joists(13) • 15.9 mm Type X gypsum board F3 with F3c • no absorptive material in cavity — 27 26 • 12.7 mm Type X gypsum board F3 with F3d • absorptive material in cavity — 29 29 • 12.7 mm Type X gypsum board F3 with F3e • no absorptive material in cavity — 27 25 • 12.7 mm regular gypsum board F3 with F3f • absorptive material in cavity — 29 28 • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Assembly Fire- Resistance Transmission Insulation Type of Assembly Description(2)(3)(4) Number Rating(5)(6)(7)(8) Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) (STC) (IIC) Floors and Ceilings • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F4(14) • on wood joists or wood I-joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 2 layers of gypsum board on ceiling side F4 with • wood joists or wood I-joists spaced 406 mm F4a 1h 33 31 o.c. • no absorptive material in cavity • 15.9 F4 withmm Type X gypsum board • wood joists or wood I-joists spaced 610 mm F4b 1h 34 31 o.c. • no absorptive material in cavity • 15.9 F4 withmm Type X gypsum board • wood joists or wood I-joists spaced 406 mm 45 min F4c 35 34 o.c. [1 h](15) Wood Floor Joists(13) • absorptive material in cavity • 15.9 F4 withmm Type X gypsum board • wood joists or wood I-joists spaced 610 mm F4d 45 min 38 34 o.c. • absorptive material in cavity • 15.9 F4 withmm Type X gypsum board • wood joists or wood I-joists spaced 406 mm F4e 1h 32 30 o.c. • no absorptive material in cavity • 12.7 F4 withmm Type X gypsum board • wood joists or wood I-joists spaced 610 mm F4f 45 min 33 30 o.c. • no absorptive material in cavity • 12.7 F4 withmm Type X gypsum board • wood joists or wood I-joists spaced 406 mm F4g 45 min 34 33 o.c. • absorptive material in cavity • 12.7 F4 withmm Type X gypsum board • wood joists or wood I-joists spaced 610 mm F4h — 35 33 o.c. • absorptive material in cavity Column 1 2 • 12.7 mm Type X gypsum 3 board 4 5 6 Page 36 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F4 with F4i • no absorptive material in cavity — 31 30 • 12.7 mm regular gypsum board F4 with F4j • absorptive material in cavity — 33 33 • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood joists or wood I-joists spaced not more than 610 mm o.c. F5(13) • with or without absorptive material in cavity • steel furring channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F5 with • no absorptive material in cavity F5a 30 min 35 37 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board Wood Floor Joists(13) F5 with • no absorptive material in cavity F5b 30 min 37 30 • steel furring channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F5 with • absorptive material in cavity 30 min F5c 38 30 • steel furring channels spaced 406 mm o.c. [45 min](16) • 15.9 mm Type X gypsum board F5 with • absorptive material in cavity F5d 30 min 40 33 • steel furring channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F5 with • no absorptive material in cavity F5e 30 min 33 26 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F5 with • no absorptive material in cavity F5f 30 min 35 29 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F5 with • absorptive material in cavity 30 min F5g 36 29 • steel furring channels spaced 406 mm o.c. [45 min](16) • 12.7 mm Type X gypsum board F5 with • absorptive material in cavity F5h 30 min 38 32 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F5 with • no absorptive material in cavity F5i < 30 min 33 25 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F5 with • no absorptive material in cavity F5j < 30 min 35 28 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F5 with • absorptive material in cavity F5k < 30 min 36 28 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board Wood Floor Joists(13) F5 with • absorptive material in cavity F5l < 30 min 38 33 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood joists or wood I-joists spaced not more than 610 mm o.c. F6(14) • with or without absorptive material in cavity • steel furring channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side F6 with • no absorptive material in cavity F6a(17) 1h 39 32 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F6 with • no absorptive material in cavity F6b(17) 1h 41 32 • steel furring channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 38 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F6 with • absorptive material in cavity F6c(17) 1h 42 35 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F6 with • absorptive material in cavity F6d(17) 1h 44 37 • steel furring channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F6 with • no absorptive material in cavity F6e(17) 1h 38 30 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F6 with • no absorptive material in cavity F6f(17) 1h 40 33 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F6 with • absorptive material in cavity F6g(17) 1h 41 33 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board Wood Floor Joists(13) F6 with • absorptive material in cavity 45 min F6h(17) 43 36 • steel furring channels spaced 610 mm o.c. [1 h](18) • 12.7 mm Type X gypsum board F6 with • no absorptive material in cavity F6i — 37 30 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F6 with • no absorptive material in cavity F6j — 39 33 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F6 with • absorptive material in cavity F6k — 40 33 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F6 with • absorptive material in cavity F6l — 42 36 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood joists or wood I-joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 1 layer of gypsum board attached directly to joists F7(14) on ceiling side • resilient metal channels spaced 406 mm or 610 mm o.c. attached to joists through gypsum board • 1 layer of gypsum board attached to resilient channels F7 with • no absorptive material in cavity F7a(17) • 15.9 mm Type X gypsum board 1h 35 27 • resilient metal channels • 15.9 mm Type X gypsum board F7 with • absorptive material in cavity F7b(17) • 15.9 mm Type X gypsum board 1h 37 30 • resilient metal channels Wood Floor Joists(13) • 15.9 mm Type X gypsum board F7 with • no absorptive material in cavity F7c(17) • 12.7 mm Type X gypsum board 1h 35 27 • resilient metal channels • 12.7 mm Type X gypsum board F7 with • absorptive material in cavity F7d(17) • 12.7 mm Type X gypsum board 1h 37 30 • resilient metal channels • 12.7 mm Type X gypsum board F7 with • no absorptive material in cavity F7e • 12.7 mm regular gypsum board — 32 26 • resilient metal channels • 12.7 mm regular gypsum board F7 with • absorptive material in cavity F7f • 12.7 mm regular gypsum board — 35 28 • resilient metal channels • 12.7 mm regular gypsum board Column 1 2 3 4 5 6 Page 40 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood joists or wood I-joists spaced not more than 610 mm o.c. F8(14) • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F8 with • no absorptive material in cavity F8a 30 min 41 33 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F8 with • no absorptive material in cavity F8b 30 min 43 36 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F8 with Wood Floor Joists(13) • absorptive material in cavity 30 min F8c 48 41 • resilient metal channels spaced 406 mm o.c. [45 min](16) • 15.9 mm Type X gypsum board F8 with • absorptive material in cavity F8d 30 min 50 44 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F8 with • no absorptive material in cavity F8e 30 min 39 32 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F8 with • no absorptive material in cavity F8f 30 min 41 35 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F8 with • absorptive material in cavity 30 min F8g 46 40 • resilient metal channels spaced 406 mm o.c. [45 min](16) • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F8 with • absorptive material in cavity F8h 30 min 48 43 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F8 with • no absorptive material in cavity F8i < 30 min 41 31 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F8 with • no absorptive material in cavity F8j < 30 min 41 34 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F8 with • absorptive material in cavity F8k < 30 min 46 39 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F8 with • absorptive material in cavity Wood Floor Joists(13) F8l < 30 min 48 42 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood joists or wood I-joists spaced not more than 610 mm o.c. F9(14) • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side F9 with • no absorptive material in cavity F9a(17) 1h 45 38 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F9 with • no absorptive material in cavity F9b(17) 1h 47 40 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 42 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F9 with • absorptive material in cavity 1h 52 F9c(17) 46 • resilient metal channels spaced 406 mm o.c. [1.5 h](19) [54](19) • 15.9 mm Type X gypsum board F9 with • absorptive material in cavity 1h 54 F9d(17) 48 • resilient metal channels spaced 610 mm o.c. [1.5 h](19) [56](19) • 15.9 mm Type X gypsum board F9 with • no absorptive material in cavity F9e(17) 1h 44 36 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F9 with • no absorptive material in cavity F9f(17) 1h 46 39 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F9 with • absorptive material in cavity 1h 51 F9g(17) 44 • resilient metal channels spaced 406 mm o.c. [1.5 h](19) [53](19) • 12.7 mm Type X gypsum board Wood Floor Joists(12) F9 with • absorptive material in cavity 45 min F9h(17) 53 47 • resilient metal channels spaced 610 mm o.c. [1 h](18) • 12.7 mm Type X gypsum board F9 with • no absorptive material in cavity F9i — 43 36 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F9 with • no absorptive material in cavity F9j — 45 39 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F9 with • absorptive material in cavity F9k — 50 44 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F9 with • absorptive material in cavity F9l — 52 47 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • one subfloor layer of 11 mm sanded plywood, or OSB or waferboard • one subfloor layer of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood joists or wood I-joists spaced not more F10(14) than 610 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 305 mm, 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F10 with • no absorptive material in cavity F10a 30 min 44 34 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F10 with • no absorptive material in cavity F10b 30 min 46 37 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F10 with Wood Floor Joists(13) • absorptive material in cavity 30 min F10c 51 42 • resilient metal channels spaced 406 mm o.c. [45 min](18) • 15.9 mm Type X gypsum board F10 with • absorptive material in cavity 30 min F10d 53 45 • resilient metal channels spaced 610 mm o.c. [45 min](16) • 15.9 mm Type X gypsum board F10 with • wood joists spaced 406 mm o.c. F10e • absorptive material in cavity 1 h(20) 53(20) 44 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F10 with • wood I-joists spaced 406 mm o.c. F10f(21) • absorptive material in cavity 1 h(20) 52(20) 43 • resilient metal channels spaced 305 mm o.c. • 15.9 mm Type X gypsum board F10 with • no absorptive material in cavity F10g 30 min 42 33 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 44 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Assembly Fire- Resistance Transmission Insulation Type of Assembly Description(2)(3)(4) Number Rating(5)(6)(7)(8) Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) (STC) (IIC) Floors and Ceilings F10 with • no absorptive material in cavity F10h 30 min 44 36 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F10 with • absorptive material in cavity 30 min F10i 49 41 • resilient metal channels spaced 406 mm o.c. [45 min](18) • 12.7 mm Type X gypsum board F10 with • absorptive material in cavity 30 min F10j 51 44 • resilient metal channels spaced 610 mm o.c. [45 min](16) • 12.7 mm Type X gypsum board F10 with • no absorptive material in cavity F10k — 42 33 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F10 with • no absorptive material in cavity F10l — 44 35 • resilient metal channels spaced 610 mm o.c. Wood Floor Joists(13) • 12.7 mm regular gypsum board F10 with • absorptive material in cavity F10m — 49 41 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F10 with • absorptive material in cavity F10n — 51 43 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • one subfloor layer of 11 mm sanded plywood, or OSB or waferboard • one subfloor layer of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F11(14) • on wood joists or wood I-joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F11 with • no absorptive material in cavity F11a(17) 1h 48 39 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F11 with • no absorptive material in cavity F11b(17) 1h 50 42 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F11 with • absorptive material in cavity 1h 55 F11c(17) 47 • resilient metal channels spaced 406 mm o.c. [1.5 h](19) [56](19) • 15.9 mm Type X gypsum board F11 with • absorptive material in cavity 1h 57 F11d(17) 50 • resilient metal channels spaced 610 mm o.c. [1.5 h](19) [58](19) • 15.9 mm Type X gypsum board F11 with • wood joists spaced 406 mm o.c. F11e(17) • absorptive material in cavity 1.5 h(22) 56(22) 47 Wood Floor Joists(13) • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F11 with • wood I-joists spaced 406 mm o.c. F11f(21) • absorptive material in cavity 1.5 h(22) 56(22) 46 • resilient metal channels spaced 305 mm o.c. • 15.9 mm Type X gypsum board F11 with • no absorptive material in cavity F11g(17) 1h 47 38 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F11 with • no absorptive material in cavity F11h(17) 1h 49 40 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F11 with • absorptive material in cavity 1h 54 F11i(17) 46 • resilient metal channels spaced 406 mm o.c. [1.5 h](19) [55](19) • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 46 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F11 with • absorptive material in cavity 45 min F11j(17) 56 48 • resilient metal channels spaced 610 mm o.c. [1 h](18) • 12.7 mm Type X gypsum board F11 with • no absorptive material in cavity F11k — 46 37 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F11 with • no absorptive material in cavity F11l — 48 40 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F11 with • absorptive material in cavity F11m — 53 45 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F11 with • absorptive material in cavity F11n — 55 48 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Wood Floor Joists(13) • 25 mm gypsum-concrete topping (at least 44 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F12(14) • on wood joists or wood I-joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 1 layer of gypsum board on ceiling side F12 with F12a • no absorptive material in cavity — 41 13 • 15.9 mm Type X gypsum board F12 with F12b • absorptive material in cavity — 43 16 • 15.9 mm Type X gypsum board F12 with F12c • no absorptive material in cavity — 39 12 • 12.7 mm Type X gypsum board F12 with F12d • absorptive material in cavity — 41 15 • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F12 with F12e • no absorptive material in cavity — 39 12 • 12.7 mm regular gypsum board F12 with F12f • absorptive material in cavity — & 41 15 • 12.7 mm regular gypsum board • 25 mm gypsum-concrete topping (at least 44 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F13(14) • on wood joists or wood I-joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 2 layers of gypsum board on ceiling side F13 with • wood joists or wood I-joists spaced 406 mm o.c. F13a 1h 43 16 Wood Floor Joists(13) • no absorptive material in cavity • 15.9 mm Type X gypsum board F13 with • wood joists or wood I-joists spaced 610 mm o.c. F13b 1h 45 16 • no absorptive material in cavity • 15.9 mm Type X gypsum board F13 with • wood joists or wood I-joists spaced 406 mm o.c. 45 min F13c 45 19 • absorptive material in cavity [1 h](15) • 15.9 mm Type X gypsum board F13 with • wood joists or wood I-joists spaced 610 mm o.c. F13d 45 min 47 19 • absorptive material in cavity • 15.9 mm Type X gypsum board F13 with • wood joists or wood I-joists spaced 406 mm o.c. F13e 1h 42 15 • no absorptive material in cavity • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 48 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F13 with • wood joists or wood I-joists spaced 610 mm o.c. F13f 45 min 44 15 • no absorptive material in cavity • 12.7 mm Type X gypsum board F13 with • wood joists or wood I-joists spaced 406 mm o.c. F13g 45 min 44 18 • absorptive material in cavity • 12.7 mm Type X gypsum board F13 with • wood joists or wood I-joists spaced 610 mm o.c. F13h — 46 18 • absorptive material in cavity • 12.7 mm Type X gypsum board F13 with F13i • no absorptive material in cavity — 41 14 • 12.7 mm regular gypsum board F13 with F13j • absorptive material in cavity — 45 14 • 12.7 mm regular gypsum board • 25 mm gypsum-concrete topping (at least Wood Floor Joists(13) 44 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood joists or wood I-joists spaced not more F14(14) than 610 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 305 mm, 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F14 with • no absorptive material in cavity F14a — 53 22 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F14 with • no absorptive material in cavity F14b — 55 22 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F14 with • absorptive material in cavity 30 min F14c 60 30 • resilient metal channels spaced 406 mm o.c. [45 min](18) • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F14 with • absorptive material in cavity F14d — 62 30 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F14 with • wood joists spaced 406 mm o.c. F14e • absorptive material in cavity 1 h(20) 60(20) 31 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F14 with • wood I-joists spaced 406 mm o.c. F14f(21) • absorptive material in cavity 1 h(20) 61(20) 31 • resilient metal channels spaced 305 mm o.c. • 15.9 mm Type X gypsum board F14 with • no absorptive material in cavity F14g — 51 21 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F14 with Wood Floor Joists(13) • no absorptive material in cavity F14h — 53 21 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F14 with • absorptive material in cavity F14i — 58 29 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F14 with • absorptive material in cavity F14j — 60 29 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F14 with • no absorptive material in cavity F14k — 51 21 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F14 with • no absorptive material in cavity F14l — 53 21 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6 Page 50 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F14 with • absorptive material in cavity F14m — 58 29 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F14 with • absorptive material in cavity F14n — 60 29 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • 25 mm gypsum-concrete topping (at least 44 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood joists or wood I-joists spaced not more F15(14) than 610 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side F15 with Wood Floor Joists(13) • no absorptive material in cavity F15a(17) 1 h(23) 57 25 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F15 with • no absorptive material in cavity F15b(17) 1h 59 25 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F15 with • absorptive material in cavity 1h 64 F15c(17) 33 • resilient metal channels spaced 406 mm o.c. [1.5 h](19) [65](19) • 15.9 mm Type X gypsum board F15 with • absorptive material in cavity 1h 66 F15d(17) 33 • resilient metal channels spaced 610 mm o.c. [1.5 h](19) [67](19) • 15.9 mm Type X gypsum board F15 with • wood joists spaced 406 mm o.c. F15e(17) • absorptive material in cavity 1.5 h(22) 65(22) 33 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F15 with • wood I-joists spaced 406 mm o.c. F15f(21) • absorptive material in cavity 1.5 h(22) 64(22) 33 • resilient metal channels spaced 305 mm o.c. • 15.9 mm Type X gypsum board F15 with • no absorptive material in cavity F15g(17) 1h 56 24 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F15 with • no absorptive material in cavity F15h(17) 1h 58 24 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F15 with • absorptive material in cavity 1h 63 F15i(17) 32 • resilient metal channels spaced 406 mm o.c. [1.5 h](19) [64](19) • 12.7 mm Type X gypsum board F15 with Wood Floor Joists(13) • absorptive material in cavity 45 min F15j(17) 65 32 • resilient metal channels spaced 610 mm o.c. [1 h](18) • 12.7 mm Type X gypsum board F15 with • no absorptive material in cavity F15k — 55 23 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F15 with • no absorptive material in cavity F15l — 57 23 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F15 with • absorptive material in cavity F15m — 62 31 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F15 with • absorptive material in cavity F15n — 64 31 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6 Page 52 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F16(14) • on wood joists or wood I-joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 1 layer of gypsum board on ceiling side F16 with F16a • no absorptive material in cavity — 44 22 • 15.9 mm Type X gypsum board F16 with F16b • absorptive material in cavity — 46 25 • 15.9 mm Type X gypsum board F16 with F16c • no absorptive material in cavity — 43 21 • 12.7 mm Type X gypsum board Wood Floor Joists(13) F16 with F16d • absorptive material in cavity — 45 24 • 12.7 mm Type X gypsum board F16 with F16e • no absorptive material in cavity — 42 21 • 12.7 mm regular gypsum board F16 with F16f • absorptive material in cavity — 44 24 • 12.7 mm regular gypsum board • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F17(14) • on wood joists or wood I-joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 2 layers of gypsum board on ceiling side Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F17 with • wood joists or wood I-joists spaced 406 mm o.c. F17a 1h 48 24 • no absorptive material in cavity • 15.9 mm Type X gypsum board F17 with • wood joists or wood I-joists spaced 610 mm o.c. F17b 1h 51 24 • no absorptive material in cavity • 15.9 mm Type X gypsum board F17 with • wood joists or wood I-joists spaced 406 mm o.c. 45 min F17c 48 27 • absorptive material in cavity [1 h](15) • 15.9 mm Type X gypsum board F17 with • wood joists or wood I-joists spaced 610 mm o.c. F17d 45 min 51 27 • absorptive material in cavity • 15.9 mm Type X gypsum board F17 with • wood joists or wood I-joists spaced 406 mm o.c. F17e 1h 47 23 • no absorptive material in cavity Wood Floor Joists(13) • 12.7 mm Type X gypsum board F17 with • wood joists or wood I-joists spaced 610 mm o.c. F17f 45 min 48 23 • no absorptive material in cavity • 12.7 mm Type X gypsum board F17 with • wood joists or wood I-joists spaced 406 mm o.c. F17g 45 min 49 26 • absorptive material in cavity • 12.7 mm Type X gypsum board F17 with • wood joists or wood I-joists spaced 610 mm o.c. F17h — 50 26 • absorptive material in cavity • 12.7 mm Type X gypsum board F17 with F17i • no absorptive material in cavity — 47 23 • 12.7 mm regular gypsum board F17 with F17j • absorptive material in cavity — 49 26 • 12.7 mm regular gypsum board Column 1 2 3 4 5 6 Page 54 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood joists or wood I-joists spaced not more F18(14) than 610 mm o.c. • with or without absorptive material in cavity • steel furring channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F18 with • no absorptive material in cavity F18a — 50 25 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F18 with • no absorptive material in cavity F18b — 52 25 • steel furring channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F18 with Wood Floor Joists(13) • absorptive material in cavity F18c — 53 28 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F18 with • absorptive material in cavity F18d — 55 28 • steel furring channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F18 with • no absorptive material in cavity F18e — 49 24 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F18 with • no absorptive material in cavity F18f — 51 24 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F18 with • absorptive material in cavity F18g — 52 27 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F18 with • absorptive material in cavity F18h — 54 27 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F18 with • no absorptive material in cavity F18i — 48 24 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F18 with • no absorptive material in cavity F18j — 50 24 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F18 with • absorptive material in cavity F18k — 51 27 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F18 with • absorptive material in cavity Wood Floor Joists(13) F18l — 53 27 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood joists or wood I-joists spaced not more F19(14) than 610 mm o.c. • with or without absorptive material in cavity • steel furring channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side F19 with • no absorptive material in cavity F19a(17) 1h 54 27 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F19 with • no absorptive material in cavity F19b(17) 1h 56 27 • steel furring channels spaced 610 mm o.c • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 56 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F19 with • absorptive material in cavity F19c(17) 1h 57 30 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F19 with • absorptive material in cavity F19d(17) 1h 59 30 • steel furring channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F19 with • no absorptive material in cavity F19e(17) 1h 53 26 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F19 with • no absorptive material in cavity F19f(17) 1h 55 26 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F19 with • absorptive material in cavity F19g(17) 1h 56 29 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board Wood Floor Joists(13) F19 with • absorptive material in cavity F19h(17) 1h 58 29 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F19 with • no absorptive material in cavity F19i — 53 26 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F19 with • no absorptive material in cavity F19j — 55 26 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F19 with • absorptive material in cavity F19k — 56 29 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F19 with • absorptive material in cavity F19l — 58 29 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood joists or wood I-joists spaced not more F20(14) than 610 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 305 mm, 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F20 with • no absorptive material in cavity F20a [45 min](23) 56 31 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F20 with • no absorptive material in cavity F20b — 58 31 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F20 with • absorptive material in cavity 30 min F20c 63 39 Wood Floor Joists(13) • resilient metal channels spaced 406 mm o.c. [45 min](18)(23) • 15.9 mm Type X gypsum board F20 with • absorptive material in cavity F20d — 65 39 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F20 with • wood joists spaced 406 mm o.c. F20e • absorptive material in cavity 1 h(20) 64(20) 40 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F20 with • wood I-joists spaced 406 mm o.c. F20f(21) • absorptive material in cavity 1 h(20) 65(20) 40 • resilient metal channels spaced 305 mm o.c. • 15.9 mm Type X gypsum board F20 with • no absorptive material in cavity F20g — 55 30 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 58 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F20 with • no absorptive material in cavity F20h — 57 30 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F20 with • absorptive material in cavity F20i — 62 38 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F20 with • absorptive material in cavity F20j — 64 38 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F20 with • no absorptive material in cavity F20k — 54 30 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F20 with • no absorptive material in cavity F20l — 56 30 Wood Floor Joists(13) • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F20 with • absorptive material in cavity F20m — 61 38 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F20 with • absorptive material in cavity F20n — 63 38 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood joists or wood I-joists spaced not more F21(14) than 610 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 305 mm, 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F21 with • no absorptive material in cavity F21a(17) 1h 60 33 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F21 with • no absorptive material in cavity F21b(17) 1h 62 33 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F21 with • absorptive material in cavity 1h 67 41 F21c(17) • resilient metal channels spaced 406 mm o.c. [1.5 h](19) [68](19) [42](19) • 15.9 mm Type X gypsum board F21 with • absorptive material in cavity 1h 69 41 F21d(17) • resilient metal channels spaced 610 mm o.c. [1.5 h](19) [70](19) [42](19) • 15.9 mm Type X gypsum board F21 with • wood joists spaced 406 mm o.c. F21e(17) • absorptive material in cavity [1.5 h](22) 68(22) 42 Wood Floor Joists(13) • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F21 with • wood I-joists spaced 406 mm o.c. F21f(21) • absorptive material in cavity [1.5 h](22) 68(22) 42 • resilient metal channels spaced 305 mm o.c. • 15.9 mm Type X gypsum board F21 with • no absorptive material in cavity F21g(17) 1h 59 32 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F21 with • no absorptive material in cavity F21h(17) 1h 61 32 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F21 with • absorptive material in cavity 1h 66 F21i(17) 40 • resilient metal channels spaced 406 mm o.c. [1.5 h](19) [67](19) • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 60 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F21 with • absorptive material in cavity F21j(17) 1h 68 40 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F21 with • no absorptive material in cavity F21k — 59 32 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F21 with • no absorptive material in cavity Wood Floor Joists(13) F21l — 61 32 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F21 with • absorptive material in cavity F21m — 66 40 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F21 with • absorptive material in cavity F21n — 68 40 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood trusses spaced not more than 610 mm F22 o.c. • with or without absorptive material in cavity • 1 layer of gypsum board on ceiling side F22 with F22a • no absorptive material in cavity — 29 27 • 15.9 mm Type X gypsum board Wood Floor Trusses(24) F22 with F22b • absorptive material in cavity — 31 30 • 15.9 mm Type X gypsum board F22 with F22c • no absorptive material in cavity — 28 26 • 12.7 mm Type X gypsum board F22 with F22d • absorptive material in cavity — 30 29 • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F22 with F22e • no absorptive material in cavity — 27 25 • 12.7 mm regular gypsum board F22 with F22f • absorptive material in cavity — 31 28 • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood trusses spaced not more than 610 mm F23 o.c. • with or without absorptive material in cavity • 2 layers of gypsum board on ceiling side F23 with • wood trusses spaced 406 mm o.c. F23a 1h 34 31 • no absorptive material in cavity • 15.9 mm Type X gypsum board F23 with • wood trusses spaced 610 mm o.c. F23b 1h 35 31 • no absorptive material in cavity Wood Floor Trusses(24) • 15.9 mm Type X gypsum board F23 with • wood trusses spaced 406 mm o.c. 45 min F23c 36 34 • absorptive material in cavity [1 h](15) • 15.9 mm Type X gypsum board F23 with • wood trusses spaced 610 mm o.c. F23d 45 min 37 34 • absorptive material in cavity • 15.9 mm Type X gypsum board F23 with • wood trusses spaced 406 mm o.c. F23e 1h 32 30 • no absorptive material in cavity • 12.7 mm Type X gypsum board F23 with • wood trusses spaced 610 mm o.c. F23f 45 min 33 30 • no absorptive material in cavity • 12.7 mm Type X gypsum board F23 with F23g • absorptive material in cavity — 34 33 • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 62 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F23 with F23h • no absorptive material in cavity — 32 30 • 12.7 mm regular gypsum board F23 with F23i • absorptive material in cavity — 34 33 • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood trusses spaced not more than 610 mm o.c. F24 • with or without absorptive material in cavity • steel furring channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F24 with • no absorptive material in cavity F24a — 35 27 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F24 with Wood Floor Trusses(24) • no absorptive material in cavity F24b — 37 30 • steel furring channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F24 with • absorptive material in cavity F24c — 38 30 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F24 with • absorptive material in cavity F24d — 40 33 • steel furring channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F24 with • no absorptive material in cavity F24e — 33 26 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F24 with • no absorptive material in cavity F24f — 36 29 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F24 with • absorptive material in cavity F24g — 37 29 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F24 with • absorptive material in cavity F24h — 39 32 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F24 with • no absorptive material in cavity F24i — 33 25 • steel furring channels spaced 406 mm • 12.7 mm regular gypsum board F24 with • no absorptive material in cavity F24j — 35 28 • steel furring channels spaced 610 mm • 12.7 mm regular gypsum board F24 with • absorptive material in cavity F24k — 36 28 • steel furring channels spaced 406 mm Wood Floor Trusses(24) • 12.7 mm regular gypsum board F24 with • absorptive material in cavity F24l — 38 31 • steel furring channels spaced 610 mm • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood trusses spaced not more than 610 mm F25 o.c. • with or without absorptive material in cavity • steel furring channels spaced 406 mm or 610 mm o.c. • 2 layers F25 with of gypsum board on ceiling side • no absorptive material in cavity F25a 1h 40 32 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F25 with • no absorptive material in cavity F25b 1h 42 34 • steel furring channels spaced 610 mm o.c • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 64 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F25 with • absorptive material in cavity F25c 1h 43 35 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F25 with • absorptive material in cavity 45 min F25d 45 37 • steel furring channels spaced 610 mm o.c. [1 h](18) • 15.9 mm Type X gypsum board F25 with • no absorptive material in cavity F25e 1h 38 30 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F25 with • no absorptive material in cavity F25f 1h 40 33 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F25 with • absorptive material in cavity F25g 1h 41 33 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board Wood Floor Trusses(24) F25 with • absorptive material in cavity 45 min F25h 43 36 • steel furring channels spaced 610 mm o.c. [1 h](18) • 12.7 mm Type X gypsum board F25 with • no absorptive material in cavity F25i — 38 30 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F25 with • no absorptive material in cavity F25j — 40 33 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F25 with • absorptive material in cavity F25k — 41 33 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F25 with • no absorptive material in cavity F25l — 43 36 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood trusses spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 1 layer of gypsum board attached directly to F26 trusses on ceiling side • resilient metal channels spaced 406 mm or 610 mm o.c. attached to trusses through the gypsum board • 1 layer of gypsum board attached to resilient metal channels F26 with • no absorptive material in cavity F26a • 15.9 mm Type X gypsum board — 35 27 • resilient metal channels • 15.9 mm Type X gypsum board F26 with • absorptive material in cavity F26b • 15.9 mm Type X gypsum board — 37 30 • resilient metal channels Wood Floor Trusses(24) • 15.9 mm Type X gypsum board F26 with • no absorptive material in cavity F26c • 12.7 mm Type X gypsum board — 35 27 • resilient metal channels • 12.7 mm Type X gypsum board F26 with • absorptive material in cavity F26d • 12.7 mm Type X gypsum board — 37 30 • resilient metal channels • 12.7 mm Type X gypsum board F26 with • no absorptive material in cavity F26e • 12.7 mm regular gypsum board — 32 26 • resilient metal channels • 12.7 mm regular gypsum board F26 with • absorptive material in cavity F26f • 12.7 mm regular gypsum board — 35 28 • resilient metal channels • 12.7 mm regular gypsum board Column 1 2 3 4 5 6 Page 66 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood trusses spaced not more than 610 mm o.c. F27 • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F27 with • no absorptive material in cavity F27a — 41 33 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F27 with • no absorptive material in cavity F27b — 43 36 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F27 with • absorptive material in cavity 30 min F27c 48 41 • resilient metal channels spaced 406 mm o.c. [45 min](25) • 15.9 mm Type X gypsum board Wood Floor Trusses(24) F27 with • absorptive material in cavity F27d — 50 44 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F27 with • no absorptive material in cavity F27e — 40 32 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F27 with • no absorptive material in cavity F27f — 42 35 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F27 with • absorptive material in cavity F27g — 47 40 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F27 with • absorptive material in cavity F27h — 49 43 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F27 with • no absorptive material in cavity F27i — 39 31 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F27 with • no absorptive material in cavity F27j — 41 34 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F27 with • absorptive material in cavity F27k — 46 39 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F27 with • absorptive material in cavity F27l — 48 42 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood trusses spaced not more than 610 mm Wood Floor Trusses(24) F28 o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers F28 with of gypsum board on ceiling side • no absorptive material in cavity F28a 1h 46 38 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F28 with • no absorptive material in cavity F28b 1h 48 40 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F28 with • absorptive material in cavity F28c 1h 54 46 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F28 with • absorptive material in cavity 45 min F28d 55 48 • resilient metal channels spaced 610 mm o.c. [1 h](18) • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 68 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F28 with • no absorptive material in cavity F28e 1h 44 36 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F28 with • no absorptive material in cavity F28f 1h 46 39 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F28 with • absorptive material in cavity F28g 1h 51 44 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F28 with • absorptive material in cavity 45 min F28h 53 47 • resilient metal channels spaced 610 mm o.c. [1 h](18) • 12.7 mm Type X gypsum board Wood Floor Trusses(24) F28 with • no absorptive material in cavity F28i — 44 36 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F28 with • no absorptive material in cavity F28j — 46 39 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F28 with • absorptive material in cavity F28k — 51 44 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F28 with • absorptive material in cavity F28l — 53 47 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • one subfloor layer 11 mm sanded plywood, or OSB or waferboard • one subfloor layer of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F29 • on wood trusses spaced not more than 610 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F29 with • no absorptive material in cavity F29a — 44 35 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F29 with • no absorptive material in cavity F29b — 46 37 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F29 with • absorptive material in cavity 30 min F29c 51 43 Wood Floor Trusses(24) • resilient metal channels spaced 406 mm o.c. [45 min](25) • 15.9 mm Type X gypsum board F29 with • absorptive material in cavity F29d — 53 45 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F29 with • no absorptive material in cavity F29e — 43 33 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F29 with • no absorptive material in cavity F29f — 45 36 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F29 with • absorptive material in cavity F29g — 50 41 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F29 with • absorptive material in cavity F29h — 52 44 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 70 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F29 with • no absorptive material in cavity F29i — 42 34 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F29 with • no absorptive material in cavity F29j — 44 36 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F29 with • absorptive material in cavity F29k — 49 41 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F29 with • absorptive material in cavity F29l — 51 44 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • one subfloor layer 11 mm sanded plywood, or OSB or waferboard • one subfloor layer of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber Wood Floor Trusses(24) F30 • on wood trusses spaced not more than 610 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side F30 with • no absorptive material in cavity F30a 1h 49 39 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F30 with • no absorptive material in cavity F30b 1h 51 42 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F30 with • absorptive material in cavity 1h 56 47 F30c • resilient metal channels spaced 406 mm o.c. [1.5 h](26) [58](26) [50](26) • 15.9 mm Type X gypsum board F30 with • absorptive material in cavity 45 min F30d 58 50 • resilient metal channels spaced 610 mm o.c. [1 h](18) • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F30 with • no absorptive material in cavity F30e 1h 47 38 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F30 with • no absorptive material in cavity F30f 1h 49 40 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F30 with • absorptive material in cavity F30g 1h 54 46 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F30 with • absorptive material in cavity 45 min F30h 56 48 • resilient metal channels spaced 610 mm o.c. [1 h](18) • 12.7 mm Type X gypsum board F30 with • no absorptive material in cavity F30i — 47 37 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board Wood Floor Trusses(24) F30 with • no absorptive material in cavity F30j — 49 40 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F30 with • absorptive material in cavity F30k — 54 45 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F30 with • absorptive material in cavity F30l — 56 48 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • 25 mm gypsum-concrete topping (at least 44 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F31 • on wood trusses spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 1 layer of gypsum board on ceiling side Column 1 2 3 4 5 6 Page 72 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F31 with F31a • no absorptive material in cavity — 41 17 • 15.9 mm Type X gypsum board F31 with F31b • absorptive material in cavity — 43 20 • 15.9 mm Type X gypsum board F31 with F31c • no absorptive material in cavity — 40 17 • 12.7 mm Type X gypsum board F31 with F31d • absorptive material in cavity — 42 20 • 12.7 mm Type X gypsum board F31 with F31e • no absorptive material in cavity — 39 16 • 12.7 mm regular gypsum board F31 with F31f • absorptive material in cavity — 41 19 • 12.7 mm regular gypsum board Wood Floor Trusses(24) • 25 mm gypsum-concrete topping (at least 44 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F32 • on wood trusses spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 2 layers of gypsum board on ceiling side F32 with • wood trusses spaced 406 mm o.c. F32a 1h 46 20 • no absorptive material in cavity • 15.9 mm Type X gypsum board F32 with • wood trusses spaced 610 mm o.c. F32b 1h 47 20 • no absorptive material in cavity • 15.9 mm Type X gypsum board F32 with • wood trusses spaced 406 mm o.c. 45 min F32c 48 23 • absorptive material in cavity [1 h](15) • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F32 with • wood trusses spaced 610 mm o.c. F32d 45 min 49 23 • absorptive material in cavity • 15.9 mm Type X gypsum board F32 with • wood trusses spaced 406 mm o.c. F32e 1h 44 19 • no absorptive material in cavity • 12.7 mm Type X gypsum board F32 with • wood trusses spaced 610 mm o.c. F32f 45 min 45 19 • no absorptive material in cavity • 12.7 mm Type X gypsum board F32 with F32g • absorptive material in cavity — 46 19 • 12.7 mm Type X gypsum board F32 with F32h • no absorptive material in cavity — 44 19 • 12.7 mm regular gypsum board F32 with Wood Floor Trusses(24) F32i • absorptive material in cavity — 46 22 • 12.7 mm regular gypsum board • 25 mm gypsum-concrete topping (at least 44 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood trusses spaced not more than 610 mm F33 o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F33 with • no absorptive material in cavity F33a — 53 26 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F33 with • no absorptive material in cavity F33b — 55 26 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 74 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F33 with • absorptive material in cavity 30 min F33c 60 34 • resilient metal channels spaced 406 mm o.c. [45 min](25) • 15.9 mm Type X gypsum board F33 with • absorptive material in cavity F33d — 62 34 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F33 with • no absorptive material in cavity F33e — 52 26 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F33 with • no absorptive material in cavity F33f — 54 26 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F33 with • absorptive material in cavity F33g — 59 34 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board Wood Floor Trusses(24) F33 with • absorptive material in cavity F33h — 61 34 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F33 with • no absorptive material in cavity F33i — 51 25 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F33 with • no absorptive material in cavity F33j — 53 25 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F33 with • absorptive material in cavity F33k — 58 33 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F33 with • absorptive material in cavity F33l — 60 33 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • 25 mm gypsum-concrete topping (at least 44 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood trusses spaced not more than 610 mm F34 o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side F34 with • no absorptive material in cavity F34a 1h 57 29 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F34 with • no absorptive material in cavity F34b 1h 60 29 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F34 with Wood Floor Trusses(24) • absorptive material in cavity 1h 65 F34c 37 • resilient metal channels spaced 406 mm o.c. [1.5 h](26) [67](26) • 15.9 mm Type X gypsum board F34 with • absorptive material in cavity 45 min F34d 67 37 • resilient metal channels spaced 610 mm o.c. [1 h](18) • 15.9 mm Type X gypsum board F34 with • no absorptive material in cavity F34e 1h 56 28 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F34 with • no absorptive material in cavity F34f 1h 58 28 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F34 with • absorptive material in cavity F34g 1h 63 36 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 76 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F34 with • absorptive material in cavity 45 min F34h 65 36 • resilient metal channels spaced 610 mm o.c. [1 h](18) • 12.7 mm Type X gypsum board F34 with • no absorptive material in cavity F34i — 56 28 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F34 with • no absorptive material in cavity F34j — 58 28 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F34 with • absorptive material in cavity F34k — 63 36 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F34 with • absorptive material in cavity F34l — 65 36 • resilient metal channels spaced 610 mm o.c. Wood Floor Trusses(24) • 12.7 mm regular gypsum board • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F35 • on wood trusses spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 1 layer of gypsum board on ceiling side F35 with F35a • no absorptive material in cavity — 45 26 • 15.9 mm Type X gypsum board F35 with F35b • absorptive material in cavity — 47 29 • 15.9 mm Type X gypsum board F35 with F35c • no absorptive material in cavity — 43 26 • 12.7 mm Type X gypsum board F35 with F35d • absorptive material in cavity — 45 29 • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F35 with F35e • no absorptive material in cavity — 43 26 • 12.7 mm regular gypsum board F35 with F35f • absorptive material in cavity — 45 29 • 12.7 mm regular gypsum board • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F36 • on wood trusses spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 2 layers of gypsum board on ceiling side F36 with • wood trusses spaced 406 mm o.c. F36a 1h 49 28 • no absorptive material in cavity • 15.9 mm Type X gypsum board F36 with Wood Floor Trusses(24) • wood trusses spaced 610 mm o.c. F36b 1h 50 28 • no absorptive material in cavity • 15.9 mm Type X gypsum board F36 with • wood trusses spaced 406 mm o.c. 45 min F36c 51 31 • absorptive material in cavity [1 h](15) • 15.9 mm Type X gypsum board F36 with • wood trusses spaced 610 mm o.c. F36d 45 min 52 31 • absorptive material in cavity • 15.9 mm Type X gypsum board F36 with • wood trusses spaced 406 mm o.c. F36e 1h 48 27 • no absorptive material in cavity • 12.7 mm Type X gypsum board F36 with • wood trusses spaced 610 mm o.c. F36f 45 min 49 27 • no absorptive material in cavity • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 78 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F36 with F36g • absorptive material in cavity — 50 30 • 12.7 mm Type X gypsum board F36 with F36h • no absorptive material in cavity — 47 27 • 12.7 mm regular gypsum board F36 with F36i • absorptive material in cavity — 49 30 • 12.7 mm regular gypsum board • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood trusses spaced not more than 610 mm F37 o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F37 with Wood Floor Trusses(24) • no absorptive material in cavity F37a 45 min 56 35 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F37 with • no absorptive material in cavity F37b — 59 35 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F37 with • absorptive material in cavity 30 min F37c 63 43 • resilient metal channels spaced 406 mm o.c. [45 min](25) • 15.9 mm Type X gypsum board F37 with • absorptive material in cavity F37d — 66 43 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F37 with • no absorptive material in cavity F37e — 55 35 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F37 with • no absorptive material in cavity F37f — 57 35 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F37 with • absorptive material in cavity F37g — 62 43 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F37 with • absorptive material in cavity F37h — 64 43 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F37 with • no absorptive material in cavity F37i — 54 35 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F37 with • no absorptive material in cavity F37j — 57 35 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Wood Floor Trusses(24) F37 with • absorptive material in cavity F37k — 61 43 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F37 with • absorptive material in cavity F37l — 64 43 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on wood trusses spaced not more than 610 mm F38 o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side F38 with • no absorptive material in cavity F38a 1h 61 37 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 80 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F38 with • no absorptive material in cavity F38b 1h 63 37 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F38 with • absorptive material in cavity 1h 69 F38c 45 • resilient metal channels spaced 406 mm o.c. [1.5 h](26) [71](26) • 15.9 mm Type X gypsum board F38 with • absorptive material in cavity F38d 1h 70 45 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F38 with • no absorptive material in cavity F38e 1h 60 36 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F38 with • no absorptive material in cavity F38f 1h 62 36 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board Wood Floor Trusses(24) F38 with • absorptive material in cavity F38g 1h 67 44 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F38 with • absorptive material in cavity F38h 1h 69 44 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F38 with • no absorptive material in cavity F38i — 59 36 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F38 with • no absorptive material in cavity F38j — 61 36 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F38 with • absorptive material in cavity F38k — 66 44 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F38 with • absorptive material in cavity Wood Floor Trusses(24) F38l — 68 44 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F39 • on steel joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 1 layer of gypsum board on ceiling side F39 with F39a • no absorptive material in cavity — 29 27 • 15.9 mm Type X gypsum board F39 with F39b • absorptive material in cavity — 31 30 • 15.9 mm Type X gypsum board F39 with F39c • no absorptive material in cavity — 27 26 • 12.7 mm Type X gypsum board F39 with Cold Formed Steel F39d • absorptive material in cavity — 29 29 Floor Joists(27) • 12.7 mm Type X gypsum board F39 with F39e • no absorptive material in cavity — 27 25 • 12.7 mm regular gypsum board F39 with F39f • absorptive material in cavity — 29 28 • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F40 • on steel joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 2 layers of gypsum board on ceiling side F40 with • steel joists spaced 406 mm o.c. F40a 1h 34 31 • no absorptive material in cavity • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 82 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F40 with • steel joists spaced 610 mm o.c. F40b 45 min 35 31 • no absorptive material in cavity • 15.9 mm Type X gypsum board F40 with • steel joists spaced 406 mm o.c. F40c 45 min 36 34 • absorptive material in cavity • 15.9 mm Type X gypsum board F40 with • steel joists spaced 610 mm o.c. F40d 45 min 37 34 • absorptive material in cavity • 15.9 mm Type X gypsum board F40 with • steel joists spaced 406 mm o.c. F40e 1h 32 30 • no absorptive material in cavity • 12.7 mm Type X gypsum board Cold Formed Steel F40 with Floor Joists(27) • steel joists spaced 610 mm o.c. F40f 45 min 33 30 • no absorptive material in cavity • 12.7 mm Type X gypsum board F40 with • steel joists spaced 406 mm o.c. F40g 45 min 34 33 • absorptive material in cavity • 12.7 mm Type X gypsum board F40 with • steel joists spaced 610 mm o.c. F40h 45 min 35 33 • absorptive material in cavity • 12.7 mm Type X gypsum board F40 with F40i • no absorptive material in cavity — 31 30 • 12.7 mm regular gypsum board F40 with F40j • absorptive material in cavity — 33 33 • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on steel joists spaced not more than 610 mm o.c. F41 • with or without absorptive material in cavity • steel furring channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F41 with • no absorptive material in cavity F41a — 34 27 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F41 with • no absorptive material in cavity F41b — 37 30 • steel furring channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F41 with • absorptive material in cavity 30 min F41c 37 30 • steel furring channels spaced 406 mm o.c. [45 min](25) • 15.9 mm Type X gypsum board Cold Formed Steel F41 with Floor Joists(27) • absorptive material in cavity F41d 30 min 40 33 • steel furring channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F41 with • no absorptive material in cavity F41e — 33 26 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F41 with • no absorptive material in cavity F41f — 35 29 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F41 with • absorptive material in cavity 30 min F41g 36 29 • steel furring channels spaced 406 mm o.c. [45 min](25) • 12.7 mm Type X gypsum board F41 with • absorptive material in cavity F41h 30 min 38 32 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 84 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F41 with • no absorptive material in cavity F41i < 30 min 32 25 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F41 with • no absorptive material in cavity F41j < 30 min 35 28 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F41 with • absorptive material in cavity F41k < 30 min 35 28 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F41 with • absorptive material in cavity F41l < 30 min 38 31 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on steel joists spaced not more than 610 mm o.c. Cold Formed Steel F42 • with or without absorptive material in cavity Floor Joists(27) • steel furring channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side F42 with • no absorptive material in cavity F42a 1h 39 32 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F42 with • steel joists spaced 406 mm o.c. F42b • no absorptive material in cavity 45 min 42 34 • steel furring channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F42 with • steel joists spaced 610 mm o.c. F42c • no absorptive material in cavity 45 min 43 34 • steel furring channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F42 with • absorptive material in cavity F42d 1h 42 35 • steel furring channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F42 with • steel joists spaced 406 mm o.c. 45 min F42e • absorptive material in cavity 45 37 [1 h](28) • steel furring channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F42 with • steel joists spaced 610 mm o.c. 45 min F42f • absorptive material in cavity 46 37 [1 h](15) • steel furring channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F42 with • no absorptive material in cavity F42g 1h 38 30 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F42 with • steel joists spaced 406 mm o.c. F42h • no absorptive material in cavity 45 min 40 33 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F42 with Cold Formed Steel • steel joists spaced 610 mm o.c. Floor Joists(27) F42i • no absorptive material in cavity 45 min 41 33 • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F42 with • absorptive material in cavity F42j 1h 41 33 • steel furring channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F42 with • steel joists spaced 406 mm o.c. 45 min F42k • absorptive material in cavity 43 36 [1 h](28) • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F42 with • steel joists spaced 610 mm o.c. 45 min F42l • absorptive material in cavity 44 36 [1 h](15) • steel furring channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F42 with • no absorptive material in cavity F42m — 37 30 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6 Page 86 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F42 with • no absorptive material in cavity F42n — 39 33 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F42 with • absorptive material in cavity F42o — 40 33 • steel furring channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F42 with • absorptive material in cavity F42p — 42 36 • steel furring channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on steel joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 1 layer of gypsum board attached directly to joists F43 on ceiling side Cold Formed Steel • resilient metal channels spaced 406 mm or Floor Joists(27) 610 mm o.c. attached to joists through the gypsum board • 1 layer of gypsum board attached to resilient metal channels F43 with • no absorptive material in cavity F43a • 15.9 mm Type X gypsum board 1h 35 37 • resilient metal channels • 15.9 mm Type X gypsum board F43 with • absorptive material in cavity F43b • 15.9 mm Type X gypsum board 1h 37 30 • resilient metal channels • 15.9 mm Type X gypsum board F43 with • no absorptive material in cavity F43c • 12.7 mm Type X gypsum board 1h 35 27 • resilient metal channels • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F43 with • absorptive material in cavity F43d • 12.7 mm Type X gypsum board 1h 37 30 • resilient metal channels • 12.7 mm Type X gypsum board F43 with • no absorptive material in cavity F43e • 12.7 mm regular gypsum board — 32 26 • resilient metal channels • 12.7 mm regular gypsum board F43 with • absorptive material in cavity F43f • 12.7 mm regular gypsum board — 35 28 • resilient metal channels • 12.7 mm regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on steel joists spaced not more than 610 mm o.c. Cold Formed Steel F44 • with or without absorptive material in cavity Floor Joists(27) • resilient metal channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F44 with • no absorptive material in cavity F44a — 40 33 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F44 with • no absorptive material in cavity F44b — 43 36 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F44 with • absorptive material in cavity 30 min F44c 47 41 • resilient metal channels spaced 406 mm o.c. [45 min](25) • 15.9 mm Type X gypsum board F44 with • absorptive material in cavity F44d 30 min 50 44 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 88 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F44 with • no absorptive material in cavity F44e — 39 32 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F44 with • no absorptive material in cavity F44f — 41 35 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F44 with • absorptive material in cavity 30 min F44g 46 40 • resilient metal channels spaced 406 mm o.c. [45 min](25) • 12.7 mm Type X gypsum board F44 with • absorptive material in cavity F44h 30 min 48 43 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F44 with • no absorptive material in cavity F44i < 30 min 38 31 • resilient metal channels spaced 406 mm o.c. Cold Formed Steel • 12.7 regular gypsum board Floor Joists(27) F44 with • no absorptive material in cavity F44j < 30 min 41 34 • resilient metal channels spaced 610 mm o.c. • 12.7 regular gypsum board F44 with • absorptive material in cavity F44k < 30 min 45 39 • resilient metal channels spaced 406 mm o.c. • 12.7 regular gypsum board F44 with • absorptive material in cavity F44l < 30 min 48 42 • resilient metal channels spaced 610 mm o.c. • 12.7 regular gypsum board • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on steel joists spaced not more than 610 mm o.c. F45 • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F45 with • no absorptive material in cavity F45a 1h 45 38 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F45 with • steel joists spaced 406 mm F45b • no absorptive material in cavity 45 min 48 40 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F45 with • steel joists spaced 610 mm F45c • no absorptive material in cavity 45 min 49 40 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F45 with • absorptive material in cavity F45d 1h 52 46 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board Cold Formed Steel Floor Joists(27) F45 with • steel joists spaced 406 mm 45 min F45e • absorptive material in cavity 55 48 [1 h](28) • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F45 with • steel joists spaced 610 mm 45 min F45f • absorptive material in cavity 56 48 [1 h](15) • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F45 with • no absorptive material in cavity F45g 1h 44 36 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F45 with • steel joists spaced 406 mm F45h • no absorptive material in cavity 45 min 46 39 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 90 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F45 with • steel joists spaced 610 mm F45i • no absorptive material in cavity 45 min 47 39 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F45 with • absorptive material in cavity F45j 1h 51 44 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F45 with • steel joists spaced 406 mm o.c. 45 min F45k • absorptive material in cavity 53 47 [1 h](28) • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F45 with • steel joists spaced 610 mm 45 min F45l • absorptive material in cavity 54 47 Cold Formed Steel [1 h](15) • resilient metal channels spaced 610 mm o.c. Floor Joists(27) • 12.7 mm Type X gypsum board F45 with • no absorptive material in cavity F45m — 43 36 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F45 with • no absorptive material in cavity F45n — 45 39 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F45 with • absorptive material in cavity F45o — 50 44 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F45 with • absorptive material in cavity F45p — 52 47 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • one subfloor layer of 11 mm sanded plywood, or OSB or waferboard • one subfloor layer of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F46 • on steel joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F46 with • no absorptive material in cavity F46a — 43 34 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F46 with • no absorptive material in cavity F46b — 46 37 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F46 with • absorptive material in cavity F46c — 50 42 • resilient metal channels spaced 406 mm o.c. Cold Formed Steel • 15.9 mm Type X gypsum board Floor Joists(27) F46 with • absorptive material in cavity F46d — 53 45 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F46 with • no absorptive material in cavity F46e — 42 33 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F46 with • no absorptive material in cavity F46f — 44 36 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F46 with • absorptive material in cavity F46g — 49 41 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F46 with • absorptive material in cavity F46h — 51 44 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 92 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F46 with • no absorptive material in cavity F46i — 41 33 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F46 with • no absorptive material in cavity F46j — 44 36 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F46 with • absorptive material in cavity F46k — 48 41 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F46 with • absorptive material in cavity F46l — 51 44 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • one subfloor layer of 15.5 mm plywood or OSB or waferboard • one subfloor layer of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber Cold Formed Steel Floor Joists(27) F47 • on steel joists spaced not more than 406 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F47 with • no absorptive material in cavity F47a 30 min 45 35 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F47 with • no absorptive material in cavity F47b 30 min 47 38 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F47 with 30 min • absorptive material in cavity F47c [45 min](18) 51 45 • resilient metal channels spaced 406 mm o.c. [1 h](28) • 15.9 mm Type X gypsum board F47 with • absorptive material in cavity [30 min](18) F47d 53 47 • resilient metal channels spaced 610 mm o.c. [45 min](28) • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F47 with • no absorptive material in cavity F47e 30 min 43 44 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F47 with • no absorptive material in cavity F47f — 45 47 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F47 with • absorptive material in cavity [30 min](18) F47g 50 43 • resilient metal channels spaced 406 mm o.c. [45 min](28) • 12.7 mm Type X gypsum board F47 with • absorptive material in cavity F47h — 52 46 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board • one subfloor layer of 11 mm sanded plywood, or OSB or waferboard • one subfloor layer of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber Cold Formed Steel Floor Joists(27) F48 • on steel joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side F48 with • no absorptive material in cavity F48a 1h 48 39 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F48 with • no absorptive material in cavity F48b 1h 50 42 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F48 with • absorptive material in cavity F48c 1h 56 47 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F48 with • absorptive material in cavity F48d 1h 57 50 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 94 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F48 with • no absorptive material in cavity F48e 1h 47 38 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F48 with • no absorptive material in cavity F48f — 49 40 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F48 with • absorptive material in cavity F48g 1h 54 46 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F48 with • absorptive material in cavity F48h — 56 48 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F48 with • no absorptive material in cavity F48i — 46 37 • resilient metal channels spaced 406 mm o.c. Cold Formed Steel • 12.7 mm regular gypsum board Floor Joists(27) F48 with • no absorptive material in cavity F48j — 48 40 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F48 with • absorptive material in cavity F48k — 53 45 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F48 with • absorptive material in cavity F48l — 55 48 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • 25 mm gypsum-concrete topping (at least 44 kg/m2) • subfloor of 15.5 mm plywood, OSB or F49 waferboard, or 17 mm tongue and groove lumber • on steel joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 1 layer of gypsum board on ceiling side Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F49 with F49a • no absorptive material in cavity — 40 13 • 15.9 mm Type X gypsum board F49 with F49b • absorptive material in cavity — 42 16 • 15.9 mm Type X gypsum board F49 with F49c • no absorptive material in cavity — 39 12 • 12.7 mm Type X gypsum board F49 with F49d • absorptive material in cavity — 41 15 • 12.7 mm Type X gypsum board F49 with F49e • no absorptive material in cavity — 38 12 • 12.7 mm regular gypsum board F49 with F49f • absorptive material in cavity — 40 15 • 12.7 mm regular gypsum board Cold Formed Steel Floor Joists(27) • 25 mm gypsum-concrete topping (at least 44 kg/m2) • subfloor of 15.5 mm plywood, OSB or F50 waferboard, or 17 mm tongue and groove lumber • on steel joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • 2 layers of gypsum board on ceiling side F50 with F50a • no absorptive material in cavity — 45 16 • 15.9 mm Type X gypsum board F50 with F50b • absorptive material in cavity — 47 19 • 15.9 mm Type X gypsum board F50 with F50c • no absorptive material in cavity — 44 15 • 12.7 mm Type X gypsum board F50 with F50d • absorptive material in cavity — 46 18 • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6 Page 96 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F50 with F50e • no absorptive material in cavity — 43 14 • 12.7 mm regular gypsum board F50 with F50f • absorptive material in cavity — 45 17 • 12.7 mm regular gypsum board • 25 mm gypsum-concrete topping (at least 44 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F51 • on steel joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F51 with • no absorptive material in cavity F51a — 52 22 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board Cold Formed Steel F51 with Floor Joists(27) • no absorptive material in cavity F51b — 54 22 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F51 with • absorptive material in cavity F51c — 59 30 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F51 with • absorptive material in cavity F51d — 61 30 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F51 with • no absorptive material in cavity F51e — 51 21 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F51 with • no absorptive material in cavity F51f — 53 21 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F51 with • absorptive material in cavity F51g — 58 29 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F51 with • absorptive material in cavity F51h — 60 29 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F51 with • no absorptive material in cavity F51i — 50 21 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F51 with • no absorptive material in cavity F51j — 52 21 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F51 with • absorptive material in cavity F51k — 57 29 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board Cold Formed Steel F51 with Floor Joists(27) • absorptive material in cavity F51l — 59 29 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • 25 mm gypsum-concrete topping (at least 44 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber F52 • on steel joists spaced not more than 610 mm o.c. • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side F52 with • no absorptive material in cavity F52a 1h 57 25 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F52 with • no absorptive material in cavity F52b 1h 59 25 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 98 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F52 with • absorptive material in cavity F52c 1h 64 33 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F52 with • absorptive material in cavity 45 min F52d 66 33 • resilient metal channels spaced 610 mm o.c. [1 h](25) • 15.9 mm Type X gypsum board F52 with • no absorptive material in cavity F52e 1h 55 24 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F52 with • no absorptive material in cavity F52f 1h 58 24 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F52 with • absorptive material in cavity F52g 1h 62 32 • resilient metal channels spaced 406 mm o.c. Cold Formed Steel • 12.7 mm Type X gypsum board Floor Joists(25) F52 with • absorptive material in cavity 45 min F52h 65 32 • resilient metal channels spaced 610 mm o.c. [1 h](25) • 12.7 mm Type X gypsum board F52 with • no absorptive material in cavity F52i — 55 23 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F52 with • no absorptive material in cavity F52j — 57 23 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F52 with • absorptive material in cavity F52k — 62 31 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F52 with • absorptive material in cavity F52l — 64 31 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 12.5 mm plywood, OSB or F53 waferboard, or 17 mm tongue and groove lumber • on steel joists spaced not more than 610 mm o.c. • 1 layer of gypsum board on ceiling side F53 with F53a • no absorptive material in cavity — 44 22 • 15.9 mm Type X gypsum board F53 with F53b • absorptive material in cavity — 46 25 • 15.9 mm Type X gypsum board F53 with F53c • no absorptive material in cavity — 42 21 • 12.7 mm Type X gypsum board F53 with F53d • absorptive material in cavity — 44 24 Cold Formed Steel • 12.7 mm Type X gypsum board Floor Joists(27) F53 with F53e • no absorptive material in cavity — 42 21 • 12.7 mm regular gypsum board F53 with F53f • absorptive material in cavity — 44 24 • 12.7 mm regular gypsum board • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or F54 waferboard, or 17 mm tongue and groove lumber • on steel joists spaced not more than 610 mm o.c. • 2 layers of gypsum board on ceiling side F54 with F54a • no absorptive material in cavity — 48 24 • 15.9 mm Type X gypsum board F54 with F54b • absorptive material in cavity — 50 27 • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 100 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F54 with F54c • no absorptive material in cavity — 47 23 • 12.7 mm Type X gypsum board F54 with F54d • absorptive material in cavity — 49 26 • 12.7 mm Type X gypsum board F54 with F54e • no absorptive material in cavity — 47 23 • 12.7 mm regular gypsum board F54 with F54f • absorptive material in cavity — 49 26 • 12.7 mm regular gypsum board • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on steel joists spaced not more than 610 mm o.c. F55 • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 1 layer of gypsum board on ceiling side F55 with Cold Formed Steel • no absorptive material in cavity Floor Joists(27) F55a — 56 31 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F55 with • no absorptive material in cavity F55b — 58 31 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F55 with • absorptive material in cavity F55c — 63 39 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F55 with • absorptive material in cavity F55d — 65 39 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F55 with • no absorptive material in cavity F55e — 54 30 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F55 with • no absorptive material in cavity F55f — 56 30 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F55 with • absorptive material in cavity F55g — 61 38 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F55 with • absorptive material in cavity F55h — 63 38 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F55 with • no absorptive material in cavity F55i — 54 30 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F55 with • no absorptive material in cavity F55j — 56 30 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F55 with • absorptive material in cavity F55k — 61 38 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board Cold Formed Steel F55 with Floor Joists(27) • absorptive material in cavity F55l — 63 38 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • 38 mm concrete topping (at least 70 kg/m2) • subfloor of 15.5 mm plywood, OSB or waferboard, or 17 mm tongue and groove lumber • on steel joists spaced not more than 610 mm o.c. F56 • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side F56 with • no absorptive material in cavity 56a 1h 60 33 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F56 with • no absorptive material in cavity 56b 1h 62 33 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 102 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F56 with • absorptive material in cavity F56c 1h 67 41 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F56 with • absorptive material in cavity 45 min F56d 69 41 • resilient metal channels spaced 610 mm o.c. [1 h](25) • 15.9 mm Type X gypsum board F56 with • no absorptive material in cavity F56e 1h 59 32 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F56 with • no absorptive material in cavity F56f 1h 61 32 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F56 with • absorptive material in cavity F56g 1h 66 40 • resilient metal channels spaced 406 mm o.c. Cold Formed Steel • 12.7 mm Type X gypsum board Floor Joists(27) F56 with • absorptive material in cavity 45 min F56h 68 40 • resilient metal channels spaced 610 mm o.c. [1 h](25) • 12.7 mm Type X gypsum board F56 with • no absorptive material in cavity F56i — 58 32 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F56 with • no absorptive material in cavity F56j — 61 32 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F56 with • absorptive material in cavity F56k — 65 40 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F56 with • absorptive material in cavity F56l — 68 40 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings • 50 mm concrete • 0.46 mm metal pan with a 19 mm rib F57 • on steel joists spaced not more than 610 mm o.c. • 1 layer of gypsum board on ceiling side F57 with F57a • no absorptive material in cavity — 45 26 • 15.9 mm Type X gypsum board F57 with F57b • absorptive material in cavity — 47 29 • 15.9 mm Type X gypsum board F57 with F57c • no absorptive material in cavity — 44 25 • 12.7 mm Type X gypsum board F57 with F57d • absorptive material in cavity — 46 28 Cold Formed Steel • 12.7 mm Type X gypsum board Floor Joists(27) F57 with F57e • no absorptive material in cavity — 43 25 • 12.7 mm regular gypsum board F57 with F57f • absorptive material in cavity — 45 28 • 12.7 mm regular gypsum board • 50 mm concrete • 0.38 mm metal pan with a 16 mm rib F58 • on steel joists spaced not more than 610 mm o.c. • 2 layers of gypsum board on ceiling side F58 with F58a • no absorptive material in cavity — 50 27 • 15.9 mm Type X gypsum board F58 with F58b • absorptive material in cavity — 52 30 • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 104 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F58 with F58c • no absorptive material in cavity — 48 27 • 12.7 mm Type X gypsum board F58 with F58d • absorptive material in cavity — 50 30 • 12.7 mm Type X gypsum board F58 with F58e • no absorptive material in cavity — 48 27 • 12.7 mm regular gypsum board F58 with F58f • absorptive material in cavity — 50 30 • 12.7 mm regular gypsum board • 50 mm concrete • 0.38 mm metal pan with a 16 mm rib • on steel joists spaced not more than 610 mm o.c. F59 • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or Cold Formed Steel 610 mm o.c. Floor Joists(27) • 1 layer of gypsum board on ceiling side F59 with • no absorptive material in cavity F59a — 57 35 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F59 with • no absorptive material in cavity F59b — 59 35 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F59 with • absorptive material in cavity F59c — 64 43 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F59 with • absorptive material in cavity F59d — 66 43 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F59 with • no absorptive material in cavity F59e — 56 34 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F59 with • no absorptive material in cavity F59f — 56 34 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F59 with • absorptive material in cavity F59g — 63 42 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F59 with • absorptive material in cavity F59h — 65 42 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F59 with • no absorptive material in cavity F59i — 55 34 • resilient metal channels spaced 406 mm o.c. Cold Formed Steel • 12.7 mm regular gypsum board Floor Joists(27) F59 with • no absorptive material in cavity F59j — 57 34 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board F59 with • absorptive material in cavity F59k — 62 42 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F59 with • absorptive material in cavity F59l — 64 42 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • 50 mm concrete • 0.46 mm metal pan with a 19 mm rib • on steel joists spaced not more than 610 mm o.c. F60 • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side Column 1 2 3 4 5 6 Page 106 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F60 with • no absorptive material in cavity F60a 1h 62 36 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum F60 with • no absorptive material in cavity F60b 1h 64 36 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F60 with • absorptive material in cavity F60c 1h 69 44 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F60 with • absorptive material in cavity 45 min F60d 71 44 • resilient metal channels spaced 610 mm o.c. [1 h](25) • 15.9 mm Type X gypsum board F60 with • no absorptive material in cavity F60e 1h 60 36 • resilient metal channels spaced 406 mm o.c. Cold Formed Steel • 12.7 mm Type X gypsum board Floor Joists(27) F60 with • no absorptive material in cavity F60f 1h 62 36 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F60 with • absorptive material in cavity F60g 1h 67 44 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F60 with • absorptive material in cavity 45 min F60h 69 44 • resilient metal channels spaced 610 mm o.c. [1 h](25) • 12.7 mm Type X gypsum board F60 with • no absorptive material in cavity F60i — 60 36 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F60 with • no absorptive material in cavity F60j — 62 36 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F60 with • absorptive material in cavity F60k — 67 44 • resilient metal channels spaced 406 mm o.c. • 12.7 mm regular gypsum board F60 with • absorptive material in cavity F60l — 69 44 • resilient metal channels spaced 610 mm o.c. • 12.7 mm regular gypsum board • 50 mm concrete • 0.38 mm metal pan with a 16 mm rib • on steel joists spaced not more than 610 mm o.c. F61 • with or without absorptive material in cavity • resilient metal channels spaced 406 mm or 610 mm o.c. • 2 layers of gypsum board on ceiling side F61 with • no absorptive material in cavity F61a 1h 62 32 • resilient metal channels spaced 406 mm o.c. Cold Formed Steel • 15.9 mm Type X gypsum board Floor Joists(27) F61 with • steel joists spaced 406 mm o.c. F61b • no absorptive material in cavity 1h 64 32 • resilient metal channels spaced 610 mm o.c • 15.9 mm Type X gypsum board F61 with • steel joists spaced 610 mm o.c. F61c • no absorptive material in cavity — 65 29 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F61 with • absorptive material in cavity F61d 1h 68 37 • resilient metal channels spaced 406 mm o.c. • 15.9 mm Type X gypsum board F61 with • steel joists spaced 406 mm o.c. F61e • absorptive material in cavity 1h 66 34 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Page 108 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Floors and Ceilings F61 with • steel joists spaced 610 mm o.c. F61f • absorptive material in cavity — 71 34 • resilient metal channels spaced 610 mm o.c. • 15.9 mm Type X gypsum board F61 with • no absorptive material in cavity F61g 1h 62 32 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F61 with • steel joists spaced 406 mm o.c. F61h • no absorptive material in cavity 1h 64 32 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F61 with • steel joists spaced 610 mm o.c. Cold Formed Steel F61i • no absorptive material in cavity — 64 28 Floor Joists(27) • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F61 with • absorptive material in cavity F61j 1h 68 36 • resilient metal channels spaced 406 mm o.c. • 12.7 mm Type X gypsum board F61 with • steel joists spaced 406 mm o.c. F61k • absorptive material in cavity 1h 64 32 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board F61 with • steel joists spaced 610 mm o.c. F61l • no absorptive material in cavity — 70 34 • resilient metal channels spaced 610 mm o.c. • 12.7 mm Type X gypsum board Column 1 2 3 4 5 6

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Table 2 (Cont'd) Fire and Sound Resistance of Floors, Ceilings and Roofs(1) Typical Sound Typical Impact Fire- Assembly Transmission Insulation Type of Assembly Description(2)(3)(4) Resistance Number Class(5)(6)(7)(9)(10)(11) Class(5)(9)(12) Rating (5)(6)(7)(8) (STC) (IIC) Roofs • wood roof trusses spaced not more than Wood Roof Trusses R1 610 mm o.c. 45 min — — • 1 layer 15.9 mm Type X gypsum board Roofs - Rating Provided by Membrane Only • supporting members spaced not more than M1 610 mm o.c. 30 min — — • 1 layer 15.9 mm Type X gypsum board • supporting members spaced not more than M2 610 mm o.c. 1h — — • 2 layers 15.9 mm Type X gypsum board Column 1 2 3 4 5 6 Notes to Table 2: (1) Reserved. (2) For assemblies with a ceiling consisting of a single layer of gypsum board on resilient metal channels to obtain the listed ratings, the resilient metal channel arrangement at the gypsum board butt end joints should be as shown in Figure 1. (3) For assemblies with a ceiling consisting of 2 layers of gypsum board on resilient metal channels to obtain the listed ratings, the fastener and resilient metal channel arrangement at the gypsum board butt end joints should be as shown in Figure 2. (4) The fire-resistance rating and sound transmission class values given are for a minimum thickness of subfloor or deck as shown. Minimum subfloor thickness required is determined by structural member spacing (see Table 9.23.15.5.A. of Division B of the Building Code). Thicker subflooring or decking is also acceptable. (5) Sound absorptive material includes (i) fibre processed from rock, slag or glass, and (ii) loose-fill or spray-applied cellulose fibre. To obtain the listed sound transmission class rating, the nominal insulation thickness is 150 mm for rock, slag, or glass fibres or loose- fill cellulose fibre, and 90 mm for spray-applied cellulose fibre, unless otherwise specified. Absorptive material will affect the sound transmission class by approximately adding or subtracting 1 per 50 mm change of thickness. However, no additional sound transmission class value is achieved by adding a greater thickness of insulation than the depth of the assembly. (6) The fire-resistance rating and sound transmission class values are based on the spacing of ceiling supports as noted. [See also Table Note (10)]. A narrower spacing will be detrimental to the sound transmission class rating, but not to the fire-resistance rating. (7) To obtain the listed rating, fastener type, spacing and penetration depth for the attachment of gypsum board must conform to Subsection 9.29.5. of Division B of the Building Code, and (i) fastener distance to board edges and butt ends shall be no less than 38 mm, except for fasteners on the butt ends of the base layer in ceilings with two layers (see Figure 2), (ii) fasteners are spaced not more than 305 mm o.c., (iii) fasteners must consist of nails or screws when attaching gypsum board to wood members, and (iv) fasteners must consist of screws when attaching gypsum board to cold-formed steel channels or resilient metal channels. For wood- and steel-framed assemblies, if fasteners are spaced less than 300 mm o.c., subtract 1 from the sound transmission class value; if fasteners are spaced less than 200 mm o.c., subtract 2 from the sound transmission class value. Narrower fastener spacing is not detrimental to the fire-resistance rating. Page 110 • SB-3

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

(8) See Sentence 1.2.1.(2) in MMAH Supplementary Standard SB-2, “Fire Performance Ratings” for the significance of fire-resistance ratings. (9) The sound transmission class values given in the Table are for the minimum depth of structural member noted in the description and applicable Table notes. To obtain sound transmission class values for structural members deeper than that minimum, add 1 to the sound transmission class value in the Table for each 170 mm increase in structural member depth. (10) The sound transmission class values given in the Table are for structural member spacing of 305 mm o.c., unless otherwise noted in the description and applicable Table notes. To obtain sound transmission class values for assemblies with structural members spaced more than 500 mm o.c., add 1 to the sound transmission class value in the Table. (11) Assemblies with sound transmission class ratings of 50 or more require methods to minimize airborne sound transmission at electrical boxes and other openings, and at wall/wall and wall/floor junctions, except at junctions constructed of concrete-to-concrete, concrete- to-masonry, or masonry-to-masonry where the intersecting joint along the junction is cast or mortared. (12) The impact insulation class values given are for floor assemblies tested with no finished flooring. (13) Wood floor joists are: (i) wood joists with a minimum member size of 38 mm (width) x 235 mm (depth), except as otherwise noted [See Table Note (16)], or (ii) wood I-joists with a minimum flange size of 38 mm x 38 mm, a minimum OSB or plywood web thickness of 9.5 mm, and a minimum joist depth of 241 mm. (14) Except where assemblies with wood I-joists are tested according to CAN/ULC-S101-14, "Fire Endurance Tests of Building Construction and Materials”, the fire-resistance rating values apply only to I-joists that have been fabricated with a phenolic-based structural wood adhesive complying with CSA O112.10-08, “Evaluation of Adhesives for Structural Wood Products (Limited Moisture Exposure)”. For I-joists with flanges made of laminated veneer lumber (LVL), the fire-resistance rating values apply only where the adhesive used in the LVL fabrication is a phenolic-based structural wood adhesive complying with CSA O112.9-10, "Evaluation of Adhesives for Structural Wood Products (Exterior Exposure)”. (15) The fire-resistance rating value within square brackets is achieved only where absorptive material includes spray-applied cellulose fibre with (i) adhesive that is capable of providing a minimum cohesive/adhesive bond strength per unit area of 5 times the weight of the material under the test plate when tested in accordance with ASTM E736/E736M-17, “Cohesion/Adhesion of Sprayed Fire- Resistive Materials Applied to Structural Members”, (ii) a minimum density of 35 kg/m3, and (iii) a minimum thickness of 90 mm on the underside of the subfloor or deck, of 90 mm on the sides of the structural members, and for cold-formed steel joists, of 13 mm on the underside of the bottom flange other than at resilient metal channel locations. (16) The fire-resistance rating value within square brackets only applies to assemblies with solid wood joists and is achieved only where absorptive material includes: (i) fibre processed from rock or slag with a minimum thickness of 90 mm and a minimum surface area mass of 2.8 kg/m 2, or (ii) spray-applied cellulose fibre with a minimum density of 50 kg/m3 and a minimum depth of 90 mm on the underside of the subfloor and of 90 mm on the sides of the floor joists. (17) The fire-resistance rating, sound transmission class and impact insulation class values given are also applicable to assemblies with 38 mm (width) x 184 mm (depth) solid wood joists. (18) The fire-resistance rating value within square brackets is achieved only where absorptive material includes: (i) fibre processed from rock or slag with a minimum thickness of 90 mm and a minimum surface area mass of 2.8 kg/m 2, or (ii) spray-applied cellulose fibre with a minimum density of 50 kg/m3 and a minimum depth of 90 mm on the underside of the subfloor and of 90 mm on the webs or the sides of the structural members. (19) The fire-resistance rating, sound transmission class and impact insulation class values within the square brackets only apply to assemblies with solid wood joists and are achieved only where absorptive material includes dry-blown cellulose fibre with a minimum density of 40 kg/m3 filling the entire cavity; the cellulose fibre is supported on zinc-coated (galvanized) steel poultry fence fabric conforming to ASTM A390-06, “Zinc-Coated (Galvanized) Steel Poultry Fence Fabric (Hexagonal and Straight Line)” which has 25 mm wide hexagonal mesh openings and 0.81 mm thick (20-gauge) wire and is attached to wood joists with metal staples having legs that are 50 mm long.

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

(20) The fire-resistance rating and sound transmission class values are achieved only where absorptive material includes: (i) fibre processed from rock or slag that fills the joist cavity and has a minimum surface area mass of 2.8 kg/m 2, and for structural members at least 270 mm in depth, the fibre includes three layers each of which has a minimum thickness of 90 mm, or (ii) dry-blown cellulose fibre with a minimum density of 40 kg/m3 filling the entire cavity; the cellulose fibre is supported on zinc- coated (galvanized) steel poultry fence fabric conforming to ASTM A390-06, “Zinc-Coated (Galvanized) Steel Poultry Fence Fabric (Hexagonal and Straight Line)” which has 25 mm wide hexagonal mesh openings and 0.81 mm thick (20-gauge) wire and is attached to wood joists or wood I-joists with metal staples having legs that are 50 mm or 30 mm long, respectively. (21) The fire-resistance rating value only applies to assemblies with wood l-joists with flanges with a minimum thickness of 38 mm and a minimum width of 63 mm. (22) The fire-resistance rating and sound transmission class values are achieved only where absorptive material includes: (i) fibre processed from rock or slag that fills the joist cavity and has a minimum surface area mass of 2.8 kg/m2, and for structural members at least 270 mm in depth, the fibre includes three layers each of which has a minimum thickness of 90 mm, or (ii) dry-blown cellulose fibre with a minimum density of 40 kg/m3 filling the entire cavity; the cellulose fibre is supported on zinc-coated (galvanized) steel poultry fence fabric conforming to ASTM A390-06, “Zinc-Coated (Galvanized) Steel Poultry Fence Fabric (Hexagonal and Straight Line)” which has 25 mm wide hexagonal mesh openings and 0.81 mm thick (20-gauge) wire and is attached to wood joists with metal staples having legs that are 50 mm long. (23) The fire-resistance rating values given only apply to assemblies with solid wood joists spaced not more than 406 mm o.c. No information is available for assemblies constructed with wood I-joists. (24) Wood floor trusses are: (i) metal plate-connected wood trusses with wood framing members not less than 38 mmx 64 mm, metal connector plates not less than 1 mm (nominal) thick with teeth not less than 8 mm long, and a minimum truss depth of 305 mm, (ii) metal web wood trusses with wood chords not less than 38 mm x 64 mm, V-shaped webs made from galvanized steel of 1 mm (nominal) thickness with plate areas having teeth not less than 8 mm long, and a minimum truss depth of 286 mm, or (iii) fingerjoined wood trusses with glued fingerjoined connections, chord members not less than 38 mm x 64 mm, web members not less than 38 mm x 38 mm and a minimum truss depth of 330 mm, all of which is glued together with an R-14 phenol- resorcinol resin conforming to CSA O112.10-08, "Evaluation of Adhesives for Structural Wood Products (Limited Moisture Exposure)”. (25) The fire-resistance rating value within square brackets is achieved only where absorptive material includes fibre processed from rock or slag with a minimum thickness of 90 mm and a minimum surface area mass of 2.8 kg/m2. (26) The fire-resistance rating and sound transmission class values within square brackets are achieved only where absorptive material includes dry-blown cellulose fibre with a minimum density of 40 kg/m3 filling the entire cavity; the cellulose fibre is supported on zinc- coated (galvanized) steel poultry fence fabric conforming to ASTM A390-06, “Zinc-Coated (Galvanized) Steel Poultry Fence Fabric (Hexagonal and Straight Line)” which has 25 mm wide hexagonal mesh openings and 0.81 mm thick (20-gauge) wire and is attached to wood trusses with metal staples having legs that are 38 mm long. (27) Cold-formed steel floor joists (C-shaped joists) are members with a minimum size of 41 mm (width) x 203 mm (depth) x 1.22 mm (material thickness). (28) The fire-resistance rating value within square brackets is achieved only where absorptive material includes spray-applied cellulose fibre with a minimum density of 50 kg/m3 and a minimum thickness of 90 mm on the underside of the subfloor, of 90 mm on the sides of the cold-formed steel floor joists, and of 13 mm on the underside of the bottom flange other than at resilient metal channel locations. Page 112 • SB-3

2024MMAH Supplementary Standard SB-3

Figures 1 to 7 Figure 1 Butt Joint Detail of Single Gypsum Board Layer Application Notes to Figure 1: (1) Figure is for illustration purposes only and is not to scale. (2) The structural member can be any one of the types described in the Table. (3) Adjacent gypsum board butt ends are to be attached to separate resilient channels using regular Type S screws, located a minimum of 38 mm from the butt end. Figure 2 Butt Joint Detail of Double Gypsum Board Layer Application Notes to Figure 2: (1) Figure is for illustration purposes only and is not to scale. (2) The structural member can be any one of the types described in the Table. (3) Base layer butt ends can be attached to a single resilient channel using regular Type S screws. (4) Type G screws measuring a minimum of 32 mm in length and located a minimum of 38 mm from the butt end are to be used to fasten the butt ends of the face layer to the base layer.

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

2024MMAH Supplementary Standard SB-3

Figure 3 Example of Steel Furring Channel Notes to Figure 3: (1) Figure is for illustration purposes only and is not to scale. Figure 4 Example of Resilient Metal Channel Notes to Figure 4: (1) Figure is for illustration purposes only and is not to scale. Page 114 • SB-3

2024MMAH Supplementary Standard SB-3

Figure 5 Blocking for Lightweight Wood-Frame Walls With a Single or Double Row of Studs Notes to Figure 5: (1) Figure is for illustrative purposes only and is not to scale. Figure 6 Vertical Application of Exterior Wall Sheathing or Interior Wall Finish With All Joints Backed With Lumber Having the Same Dimensions as the Framing Members Notes to Figure 6: (1) Figure is for illustration purposes only and is not to scale.

2024MMAH Supplementary Standard SB-3

Figure 7 Horizontal Application of Exterior Wall Sheathing or Interior Wall Finish With All Joints Backed With Lumber Having the Same Dimensions as the Framing Members Notes to Figure 7: (1) Figure is for illustration purposes only and is not to scale. Page 116 • SB-3 Ministry of Municipal Affairs and Housing Building and Development Branch MMAH Supplementary Standard SB-4 MMAH Supplementary Standard SB-4 Measures for Fire Safety in High Buildings January 1, 2024

2024MMAH Supplementary Standard SB-4

COMMENCEMENT MMAH Supplementary Standard SB-4 comes into force on the 1st day of January 2025. © Copyright © Copyright King's Printer for Ontario 2024 All rights reserved. Questions regarding copyright, including reproduction and distribution, may be directed to the Director, Building and Development Branch of the Ministry of Municipal Affairs and Housing.

2024MMAH Supplementary Standard SB-4

CONTENTS Page Introduction ............................................................................................................................................... 1 Section 1: Building Code Provisions ...................................................................................................... 2 Section 2: Scope of Measures for Fire Safety in Existing High Buildings .......................................... 12 Section 3: Measures for Life Safety in Existing High Buildings .......................................................... 30 Appendix A to SB-4: Graphs for Applying Smoke Control Measures ................................................. 53 Appendix B to SB-4: Assumptions Used in Developing Fire Safety Measures.................................. 59 Appendix C to SB-4: Check of a Smoke Control System ..................................................................... 69 References ................................................................................................................................................. 70

Understand any provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.