OBC VOLUME 2 · SUPPLEMENTARY STANDARD SB-11Updated for the 2024 Ontario Building Code
SB-11 — Construction of Farm Buildings
Supplementary Standard SB-11 ("Construction of Farm Buildings") forms part of Volume 2 of the 2024 Ontario Building Code. The full text is reproduced below with a linked table of contents.
2024MMAH Supplementary Standard SB-11
SB-11 Construction of Farm Buildings
Section 1 General
1.1.1.Application
(1) This Section applies to farm buildings of low human occupancy.
1.1.2.Construction Requirements
(1) The construction of farm buildings of low human occupancy shall, subject to Article 2.1.3.5. in Division B of the
Building Code, conform to the requirements of Part 9 of Division B of the Building Code except as provided in this
Section.
1.2.1.Lumber Requirements
(1) Except as permitted by Article 1.2.2., lumber shall conform to appropriate requirements in Subsection 9.3.2. of
Division B of the Building Code.
1.2.2.Ungraded Lumber
(1) Ungraded lumber may be used for wood posts, joists, rafters, lintels, beams and wall studs in a farm building of low
human occupancy of not more than one storey in building height.
(2) Ungraded lumber means lumber that has not been grade-stamped to indicate its grade, as determined by the NLGA
“Standard Grading Rules for Canadian Lumber (Interpretation Included)”, but that meets the following visual attributes:
(a) it is rough sawn to full nominal size,
(b) it has no evidence of decay,
(c) it has no tight knots that exceed 25 percent of the cross section and that are spaced closer than 150 mm on centres,
(d) it has no loose knots or holes that exceed 25 percent of the cross section and that are spaced closer than 600 mm on
centres,
(e) it has the slope of grain not exceeding 1 (vertical) in 4 (horizontal), and
(f) it is free of excessive warp.
1.3.1.Structural Design
(1) Except as provided in Articles 1.3.2. to 1.3.4., wood posts, joists, rafters, lintels, beams and wall studs shall be
designed in conformance with Section 9.4. of Division B of the Building Code.
1.3.2.Posts
(1) In a farm building of low human occupancy, the size of wood posts shall conform to Tables 1.3.2.A. to 1.3.2.J. for
the loads shown in the Tables.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
1.3.3.Spans
(1) In a farm building of low human occupancy, the spans of wood joists, rafters, lintels and beams shall conform to the
spans shown in Tables 1.3.3.K. to 1.3.3.T. for the loads shown in the Tables.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
1.3.4.Stud Size and Spacing
(1) In a farm building of low human occupancy, the size and spacing of wood studs shall conform to Tables 1.3.4.U. to
1.3.4.W. for the loads shown in the Tables.
Page 2 • SB-11
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.2.A.
Post Sizes for Diaphragm-Braced Farm Buildings of Low Human Occupancy
Forming Part of Sentence 1.3.2.(1)
Spruce-Pine-Fir, No. 1, Dressed (Post and Timber Grades)
For Wind Loading q10 ≤ 0.30 kPa
Building Wall
Post Spacing, 2.4 m Post Spacing, 3.6 m Post Spacing, 4.8 m
Width, m Height, m
Roof Load, kPa Roof Load, kPa Roof Load, kPa
1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3
≤3.0 A A A A A A A A A A A A B B B
3.6 A A A A A A A B B B B B B C C
9.14 4.2 B B B B B B B B C C B C C C C
4.8 B B B B B B C C C C C C C C C
6.0 C C C C C C C C D D C D D — —
≤3.0 A A A A A A A A B B A B B B C
3.6 A A A A B A B B B C B B C C C
12.1 4.2 B B B B B B B C C C C C C C C
4.8 B B B C C C C C C C C C D D D
6.0 C C C C C C C D D — D D — — —
≤3.0 A A A A A A A B B B B B B C C
3.6 A A A B B B B B C C B C C C C
15.2 4.2 B B B B C B C C C C C C C D D
4.8 B B C C C C C C C D C C D D —
6.0 C C C C D C D D — — D — — — —
≤3.0 A A A B B A B B B C B B C C C
3.6 A A B B B B B C C C C C C C D
18.2 4.2 B B B C C C C C C C C C D D D
4.8 B C C C C C C C D D C D D — —
6.0 C C C D D D D — — — — — — — —
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Legend - Post Sizes:
A = 89 mm x 140 mm B = 140 mm x 140 mm C = 140 mm x 184 mm D = 184 mm x 184 mm
Notes to Table 1.3.2.A.:
(1) Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
(2) Posts shall be oriented with the long dimension parallel to the building width.
(3) Bracing systems shall be specified by a competent designer.
(4) Posts shall be situated on footings and shall be anchored to prevent wind uplift.
(5) Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor
help to meet this condition.
(6) Post designs are based on partial fixity condition due to embedment in soil.
(7) Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.2.B.
Post Sizes for Diaphragm-Braced Farm Buildings of Low Human Occupancy
Forming Part of Sentence 1.3.2.(1)
Spruce-Pine-Fir, No. 1, Dressed (Post and Timber Grades)
Building Wall For Wind Loading q10 ≤ 0.45 kPa
Width, Height, Post Spacing, 2.4 m Post Spacing, 3.6 m Post Spacing, 4.8 m
m m Roof Load, kPa Roof Load, kPa Roof Load, kPa
1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3
≤3.0 A A A A A A A A A B A B B B B
3.6 A A A A A A B B B B B B C C C
9.14 4.2 B B B B B B B C C C C C C C C
4.8 B B B C C C C C C C C C C D D
6.0 C C C C C C D D D D D — — — —
≤3.0 A A A A A A A B B B B B B C C
3.6 A A A B B B B B C C C C C C C
12.1 4.2 B B B B C C C C C C C C C C D
4.8 B C C C C C C C C C C D D D —
6.0 C C C C D D D D — — — — — — —
≤3.0 A A A A B A B B B C B B C C C
3.6 A A B B B B B C C C C C C C D
15.2 4.2 B B B C C C C C C C C C D D D
4.8 B C C C C C C C D D C D D — —
6.0 C C C D D D D — — — — — — — —
≤3.0 A A A B B B B B C C B C C C C
3.6 A B B B C B C C C C C C C D D
18.2 4.2 B B C C C C C C C D C D D D —
4.8 C C C C C C C D D — D D — — —
6.0 C C D D — D — — — — — — — — —
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Legend - Post Sizes:
A = 89 mm x 140 mm B = 140 mm x 140 mm C = 140 mm x 184 mm D = 184 mm x 184 mm
Notes to Table 1.3.2.B.:
(1) Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
(2) Posts shall be oriented with the long dimension parallel to the building width.
(3) Bracing systems shall be specified by a competent designer.
(4) Posts shall be situated on footings and shall be anchored to prevent wind uplift.
(5) Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor
help to meet this condition.
(6) Post designs are based on partial fixity condition due to embedment in soil.
(7) Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.
Page 4 • SB-11
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.2.C.
Post Sizes for Knee-Braced Farm Buildings of Low Human Occupancy
Forming Part of Sentence 1.3.2.(1)
Spruce-Pine-Fir, No. 1, Dressed (Post and Timber Grades)
Building Wall For Wind Loading q10 ≤ 0.30 kPa
Width, Height, Post Spacing, 2.4 m Post Spacing, 3.6 m Post Spacing, 4.8 m
m m Roof Load, kPa Roof Load, kPa Roof Load, kPa
1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3
≤3.0 A A A A A A A A B B A B B B C
3.6 A A A A B A B B B C B C C C C
9.14 4.2 B B B B B B C C C C C C C C C
4.8 C C C C C C C C C C C C C D D
6.0 C C C C C C D D D — D — — — —
≤3.0 A A A A A A A B B B B B C C C
3.6 A A B B B B B C C C C C C C C
12.1 4.2 B B B C C C C C C C C C C D D
4.8 C C C C C C C C D D C D D — —
6.0 C C C D D D D — — — — — — — —
≤3.0 A A A B B A B B C C B C C C C
3.6 A B B B C B C C C C C C C C D
15.2 4.2 B B C C C C C C C D C C D D —
4.8 C C C C C C C D D — D D — — —
6.0 C C D D — D — — — — — — — — —
≤3.0 A A B B B B B C C C B C C C D
3.6 B B B C C C C C C C C C C D D
18.2 4.2 B C C C C C C C D D C D D — —
4.8 C C C C D C D D — — D — — — —
6.0 C D D — — — — — — — — — — — —
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Legend - Post Sizes:
A = 89 mm x 140 mm B = 140 mm x 140 mm C = 140 mm x 184 mm D = 184 mm x 184 mm
Notes to Table 1.3.2.C.:
(1) Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
(2) Posts shall be oriented with the long dimension parallel to the building width.
(3) Bracing systems shall be specified by a competent designer.
(4) Posts shall be situated on footings and shall be anchored to prevent wind uplift.
(5) Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor
help to meet this condition.
(6) Post designs are based on partial fixity condition due to embedment in soil.
(7) Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.2.D.
Post Sizes for Knee-Braced Farm Buildings of Low Human Occupancy
Forming Part of Sentence 1.3.2.(1)
Spruce-Pine-Fir, No. 1, Dressed (Post and Timber Grades)
Building Wall For Wind Loading q10 ≤ 0.45 kPa
Width, Height, Post Spacing, 2.4 m Post Spacing, 3.6 m Post Spacing, 4.8 m
m m Roof Load, kPa Roof Load, kPa Roof Load, kPa
1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3
≤3.0 A A A A A A A B B B B B B C C
3.6 A A A B B B B B C C C C C C C
9.14 4.2 B B B B C C C C C C C C C C D
4.8 C C C C C C C C C D C D D D —
6.0 C C C C D D D — — — — — — — —
≤3.0 A A A A B A B B B C B B C C C
3.6 B B B B B B C C C C C C C C C
12.1 4.2 B B C C C C C C C C C C D D D
4.8 C C C C C C C D D D D D — — —
6.0 C C D D D D — — — — — — — — —
≤3.0 A A B B B B B B C C B C C C C
3.6 A B B C C C C C C C C C C D D
15.2 4.2 B C C C C C C C D D C D D — —
4.8 C C C C C C D D D — D — — — —
6.0 C D D — — — — — — — — — — — —
≤3.0 A A B B B B B C C C C C C C D
3.6 B B C C C C C C C D C C D D —
18.2 4.2 C C C C C C C D D D D D — — —
4.8 C C C D D C D — — — D — — — —
6.0 D D — — — — — — — — — — — — —
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Legend - Post Sizes:
A = 89 mm x 140 mm B = 140 mm x 140 mm C = 140 mm x 184 mm D = 184 mm x 184 mm
Notes to Table 1.3.2.D.:
(1) Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
(2) Posts shall be oriented with the long dimension parallel to the building width.
(3) Bracing systems shall be specified by a competent designer.
(4) Posts shall be situated on footings and shall be anchored to prevent wind uplift.
(5) Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor
help to meet this condition.
(6) Post designs are based on partial fixity condition due to embedment in soil.
(7) Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.
Page 6 • SB-11
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.2.E.
Post Sizes for Diaphragm-Braced Farm Buildings of Low Human Occupancy
Forming Part of Sentence 1.3.2.(1)
Ungraded Lumber, Full-Dimensioned
Building Wall For Wind Loading q10 ≤ 0.30 kPa
Width, Height, Post Spacing, 2.4 m Post Spacing, 3.6 m Post Spacing, 4.8 m
m m Roof Load, kPa Roof Load, kPa Roof Load, kPa
1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3
≤3.0 A A A A A A A A B B A B B C C
3.6 A A A A B A B B B C B C C C C
9.14 4.2 B B B B B B B C C C C C C C D
4.8 B B B B C C C C C C C C C D D
6.0 C C C C C C C D D D D D — — —
≤3.0 A A A A B A B B B C B B C C C
3.6 A A B B B B B C C C C C C C D
12.1 4.2 B B B B C B C C C C C C D D D
4.8 B B C C C C C C C D C D D D —
6.0 C C C C D C D D — — D — — — —
≤3.0 A A A B B B B C C C B C C D D
3.6 A B B B C B C C C C C C D D D
15.2 4.2 B B C C C C C C D D C D D — —
4.8 B C C C C C C D D D D D — — —
6.0 C C C D D D D — — — — — — — —
≤3.0 A A B B C B B C C D C C D D —
3.6 A B B C C C C C D D C D D — —
18.2 4.2 B C C C C C C D D D C D — — —
4.8 C C C C D C D D — — D — — — —
6.0 C C D D — D — — — — — — — — —
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Legend - Post Sizes:
A = 101.6 mm x 152.4 mm B = 152.4 mm x 152.4 mm C = 152.4 mm x 203.2 mm D = 203.2 mm x 203.2 mm
Notes to Table 1.3.2.E:
(1) Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
(2) Posts shall be oriented with the long dimension parallel to the building width.
(3) Bracing systems shall be specified by a competent designer.
(4) Posts shall be situated on footings and shall be anchored to prevent wind uplift.
(5) Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor
help to meet this condition.
(6) Post designs are based on partial fixity condition due to embedment in soil.
(7) Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.2.F.
Post Sizes for Diaphragm-Braced Farm Buildings of Low Human Occupancy
Forming Part of Sentence 1.3.2.(1)
Ungraded Lumber, Full-Dimensioned
Building Wall For Wind Loading q10 ≤ 0.45 kPa
Width, Height, Post Spacing, 2.4 m Post Spacing, 3.6 m Post Spacing, 4.8 m
m m Roof Load, kPa Roof Load, kPa Roof Load, kPa
1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3
≤3.0 A A A A A A A B B B B B C C C
3.6 A A A B B B B B C C C C C C C
9.14 4.2 B B B B C C C C C C C C C D D
4.8 B B C C C C C C C D C D D D —
6.0 C C C C C D D D — — — — — — —
≤3.0 A A A B B B B B C C B C C C C
3.6 A A B B B B C C C C C C C D D
12.1 4.2 B B B C C C C C C D C D D D —
4.8 B C C C C C C D D D D D — — —
6.0 C C C D D D D — — — — — — — —
≤3.0 A A B B B B B C C C C C C D D
3.6 A B B C C C C C C D C C D D —
15.2 4.2 B C C C C C C C D D D D D — —
4.8 C C C C C C D D D — D — — — —
6.0 C C D D — D — — — — — — — — —
≤3.0 A B B B C B C C C D C C D D —
3.6 B B C C C C C C D D C D D — —
18.2 4.2 B C C C C C C D D — D D — — —
4.8 C C C C D D D D — — — — — — —
6.0 C D D — — — — — — — — — — — —
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Legend - Post Sizes:
A = 101.6 mm x 152.4 mm B = 152.4 mm x 152.4 mm C = 152.4 mm x 203.2 mm D = 203.2 mm x 203.2 mm
Notes to Table 1.3.2.F:
(1) Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
(2) Posts shall be oriented with the long dimension parallel to the building width.
(3) Bracing systems shall be specified by a competent designer.
(4) Posts shall be situated on footings and shall be anchored to prevent wind uplift.
(5) Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor
help to meet this condition.
(6) Post designs are based on partial fixity condition due to embedment in soil.
(7) Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.
Page 8 • SB-11
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.2.G.
Post Sizes for Knee-Braced Farm Buildings of Low Human Occupancy
Forming Part of Sentence 1.3.2.(1)
Ungraded Lumber, Full-Dimensioned
Building For Wind Loading q10 ≤ 0.30 kPa
Width, Wall Post Spacing, 2.4 m Post Spacing, 3.6 m Post Spacing, 4.8 m
m Height, Roof Load, kPa Roof Load, kPa Roof Load, kPa
m
1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3
≤3.0 A A A A A A A B B B B B C C C
3.6 A A A B B B B B C C B C C C C
9.14 4.2 B B B B C B C C C C C C C D D
4.8 C C C C C C C C C D C C D D —
6 C C C C D C D D — — D — — — —
≤3.0 A A A B B A B B C C B C C C D
3.6 A B B B C B C C C C C C C D D
12.1 4.2 B B C C C C C C C D C C D D —
4.8 C C C C C C C D D D D D — — —
6.0 C C C D D D D — — — — — — — —
≤3.0 A A B B B B B C C C C C C D D
3.6 A B B C C C C C C D C C D D —
15.2 4.2 B C C C C C C D D D C D — — —
4.8 C C C C D C D D — — D — — — —
6.0 C D D D — D — — — — — — — — —
≤3.0 A B B C C B C C C D C C D D —
3.6 B B C C C C C C D D C D D — —
18.2 4.2 C C C C D C C D — — D D — — —
4.8 C C C D D C D — — — D — — — —
6.0 C D — — — — — — — — — — — — —
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Legend - Post Sizes:
A = 101.6 mm x 152.4 mm B = 152.4 mm x 152.4 mm C = 152.4 mm x 203.2 mm D = 203.2 mm x 203.2 mm
Notes to Table 1.3.2.G.:
(1) Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
(2) Posts shall be oriented with the long dimension parallel to the building width.
(3) Bracing systems shall be specified by a competent designer.
(4) Posts shall be situated on footings and shall be anchored to prevent wind uplift.
(5) Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor
help to meet this condition.
(6) Post designs are based on partial fixity condition due to embedment in soil.
(7) Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.2.H.
Post Sizes for Knee-Braced Farm Buildings of Low Human Occupancy
Forming Part of Sentence 1.3.2.(1)
Ungraded Lumber, Full-Dimensioned
Building Wall For Wind Loading q10 ≤ 0.45 kPa
Width, Height, Post Spacing, 2.4 m Post Spacing, 3.6 m Post Spacing, 4.8 m
m m Roof Load, kPa Roof Load, kPa Roof Load, kPa
1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3
≤3.0 A A A A B A B B B C B C C C C
3.6 A A B B B B C C C C C C C C D
9.14 4.2 B B B C C C C C C C C C D D D
4.8 C C C C C C C C D D D D D — —
6.0 C C C D D D D — — — — — — — —
≤3.0 A A B B B B B C C C C C C C D
3.6 A B B C C C C C C C C C D D D
12.1 4.2 B C C C C C C C D D C D D — —
4.8 C C C C C C D D D — D — — — —
6.0 C D D D — — — — — — — — — — —
≤3.0 A B B B C B C C C C C C D D D
3.6 B B C C C C C C D D C D D — —
15.2 4.2 C C C C C C C D D — D D — — —
4.8 C C C D D D D — — — — — — — —
6.0 D D D — — — — — — — — — — — —
≤3.0 A B B C C C C C D D C D D — —
3.6 B C C C C C C D D — D D — — —
18.2 4.2 C C C C C C C D D — D D — — —
4.8 C C C C D C D D — — D — — — —
6.0 C C D D D D — — — — — — — — —
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Legend - Post Sizes:
A = 101.6 mm x 152.4 mm B = 152.4 mm x 152.4 mm C = 152.4 mm x 203.2 mm D = 203.2 mm x 203.2 mm
Notes to Table 1.3.2.H.:
(1) Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
(2) Posts shall be oriented with the long dimension parallel to the building width.
(3) Bracing systems shall be specified by a competent designer.
(4) Posts shall be situated on footings and shall be anchored to prevent wind uplift.
(5) Posts shall be constrained against lateral movement at ground level and at the footing. Concrete floor, splash-rail and uplift anchor
help to meet this condition.
(6) Post designs are based on partial fixity condition due to embedment in soil.
(7) Footing excavations should be backfilled with parent material unless otherwise specified by a competent designer.
Page 10 • SB-11
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.2.I.
Post Sizes for Farm Buildings of Low Human Occupancy (With Second Storey Loading)
Forming Part of Sentence 1.3.2.(1)
Spruce-Pine-Fir, No. 1, Dressed (Post and Timber Grades)
Total Wind load: q10 ≤ 0.30 kPa Wind load: q10 ≤ 0.45 kPa
Sidewall
Roof Second
Height, 2.4 m o.c. 3.6 m o.c. 2.4 m o.c. 3.6 m o.c.
Load, Storey
m Building Width, m Building Width, m Building Width, m Building Width, m
kPa Plate,
9.14 12.2 15.2 18.3 9.14 12.2 15.2 18.3 9.14 12.2 15.2 18.3 9.14 12.2 15.2 18.3 kN/m
1.9 A A A A A A B B A A A A A B B B
2.4 A A A A A B B B A A A B A B B B
3.0 14.6
2.8 A A A B A B B C A A B B B B B C
3.3 A A B B B B B C A A B B B B C C
1.9 A A A B A B B C A A B B B B C C
2.4 A A B B B B C C A B B B B C C C
3.6 14.6
2.8 A B B B B B C C A B B B B C C C
3.3 A B B C B C C C B B B C C C C C
1.9 A A A A A A B B A A A A A A B B
2.4 A A A A A A B B A A A A A B B B
3.0 7.3
2.8 A A A B A B B B A A A B B B B C
3.3 A A B B B B B C A A B B B B C C
1.9 A A A B A B B B A A B B B B C C
2.4 A A B B B B C C A B B B B B C C
3.6 7.3
2.8 A A B B B B C C A B B B B C C C
3.3 A B B B B C C C B B B C C C C C
1.9 A A A A A A A B A A A A A A B B
2.4 A A A A A A B B A A A A A B B B
3.0 3.6
2.8 A A A B A B B B A A A B B B B C
3.3 A A A B A B B C A A B B B B C C
1.9 A A A B A B B B A A A B B B B C
2.4 A A B B B B B C A A B B B B C C
3.6 3.6
2.8 A A B B B B C C A B B B B C C C
3.3 A B B B B C C C A B B C B C C C
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Legend - Post Sizes:
A = 89 mm x 140 mm B = 140 mm x 140 mm C = 140 mm x 184 mm
Notes to Table 1.3.2.I.:
(1) Designs are based on load combinations of total roof load, wind load and stored product acting at the same time on a closed building.
(2) All notes following Table 1.3.2.A. apply, with the following conditions/exceptions:
• 14.6 kN/m loading: Full 4.8 m sidewall hay/straw storage space above. It is supported by beams spaced at 3.6 m o.c.
The outside plate carries a 1.8 m floor width. If the loading is greater, refer to a qualified person for
design.
• 7.3 kN/m loading: Full 2.4 m sidewall hay/straw storage space above or a gambrel roof structure > 9.14 m in total width.
Floor support beams as above.
• 3.6 kN/m loading: Small gambrel roof structure or storage space for light storage. Floor support beams as above.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3 2.J.
Round Posts
Forming Part of Sentence 1.3.2.(1)
Ungraded Lumber Full-dimension Size, Equivalent Diameter Full Size,
mm mm
50.8 x 101.6 101.6
50.8 x 152.4 127.0
50.8 x 203.2 152.4
50.8 x 254.0 177.8
50.8 x 304.8 203.2
76.2 x 304.8 228.6
76.2 x 355.6 254.0
101.6 x 152.4 158.8
101.6 x 304.8 203.2
101.6 x 355.6 279.4
127.0 x 203.2 209.6
127.0 x 254.0 241.3
152.4 x 152.4 190.5
152.4 x 203.2 222.3
152.4 x 254.0 260.4
203.2 x 203.2 247.7
203.2 x 254.0 285.8
203.2 x 304.8 317.5
254.0 x 304.8 342.9
254.0 x 355.6 381.0
Column 1 2
Notes to Table 1.3.2.J.:
(1) When selecting round, ungraded lumber, ensure that the material is of good quality.
(2) Any timber that is in contact with ground shall be chemically treated to resist growth of fungus and decay.
(3) Equivalent diameter indicated in this Table refers to the smallest diameter of a tapering pole.
(4) Used hydro or telephone poles may be used if they are of good quality and are chemically treated to prevent decay.
(5) Indicated equivalent diameter will provide bending, shear and deflection resisting capabilities equal to or better than the rectangular
section that it replaces.
Page 12 • SB-11
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.3.K.
Common Rafter Sizes for Farm Buildings of Low Human Occupancy
Forming Part of Sentence 1.3.3.(1)
Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber)
Rafter Rafter Spacing
Span, 305 mm 406 mm 610 mm
m Live Load, kPa Live Load, kPa Live Load, kPa
1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3
2.4 A A B B B A B B B B B B B B B
3.0 B B B B B B B B B C B B C C D
3.6 B B C C C B C C C C C C D D D
4.2 B C C C C C C C D D C D D E E
4.8 C C D D D C D D E E D E E — —
5.4 C D D D E D D E E — E E — — —
6.0 D D D E — D E E — — E — — — —
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Legend - Rafter Sizes:
A = 38 mm x 89 mm C = 38 mm x 184 mm B = 38 mm x 140 mm D = 38 mm x 235 mm E = 38 mm x 286 mm
Notes to Table 1.3.3.K.:
(1) The rafter span is the unsupported length of the rafter from plate to plate or from plate to ridge. A dead load of 0.24 kPa is
incorporated to allow for weight of the roof sheathing and rafter.
Table 1.3.3.L.
Common Rafter Sizes for Farm Buildings of Low Human Occupancy
Forming Part of Sentence 1.3.3.(1)
Ungraded Lumber, Full-Dimension
Rafter Rafter Spacing
Span, 305 mm 406 mm 610 mm
m Live Load, kPa Live Load, kPa Live Load, kPa
1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3 1.4 1.9 2.4 2.8 3.3
2.4 A A B B B B B B B C B B C C D
3.0 B B B C C B C C C D C C D D E
3.6 B C C D D C C D D E D D E F F
4.2 C C D D E D D E E F E F F F G
4.8 C D E E F D E F F F F F F G I
5.4 D E F F F E F F F G F G H I —
6.0 E F F F G F F G G I F H I — —
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Legend - Rafter Sizes:
A = 50.8 mm x 101.6 mm D = 50.8 mm x 254.0 mm G = 76.2 mm x 355.6 mm
B = 50.8 mm x 152.4 mm E = 50.8 mm x 304.8 mm H = 101.6 mm x 304.8 mm
C = 50.8 mm x 203.2 mm F = 76.2 mm x 304.8 mm I = 101.6 mm x 355.6 mm
Notes to Table 1.3.3.L.:
(1) The rafter span is the unsupported length of the rafter from plate to plate or from plate to ridge. A dead load of 0.24 kPa is
incorporated to allow for weight of the roof sheathing and rafter.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.3.M.
Floor Joists for Farm Buildings of Low Human Occupancy - Intermittent Loads(1)
Forming Part of Sentence 1.3.3.(1)
Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber)
Joist Spacing
Joist Span,
305 mm 406 mm 610 mm
m
Live Load, kPa Live Load, kPa Live Load, kPa
1.9 2.8 3.8 4.8 6.7 8.6 1.9 2.8 3.8 4.8 6.7 8.6 1.9 2.8 3.8 4.8 6.7 8.6
2.4 A B B B B C B B B B C C B B B C D D
3.0 B B B C C D B B C C D D B C C D E —
3.6 B C C C D D C C C D E E C D D E — —
4.2 C C D D E E C D D E — — D d E — — —
4.8 C D D E — — D D E E — — D E — — — —
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Legend - Joist Sizes:
A = 38 mm x 89 mm B = 38 mm x 140 mm C = 38 mm x 184 mm D = 38 mm x 235 mm E = 38 mm x 286 mm
Notes to Table 1.3.3.M.:
(1) Loads are applied to the floor intermittently. (When loads are applied for extended periods of time, use Table 1.3.3.N.).
(2) A dead load of 0.48 kPa is incorporated to allow for the dead weight of the floor system.
Table 1.3.3.N.
Floor Joists for Farm Buildings of Low Human Occupancy - Continuous Loads(1)
Forming Part of Sentence 1.3.3.(1)
Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber)
Joist Spacing
Joist Span,
305 mm 406 mm 610 mm
m
Live Load, kPa Live Load, kPa Live Load, kPa
1.9 2.8 3.8 4.8 6.7 8.6 1.9 2.8 3.8 4.8 6.7 8.6 1.9 2.8 3.8 4.8 6.7 8.6
2.4 A B B B C C B B B C D E B C C D — —
3.0 B B C C D E B C C D E — C D D E — —
3.6 B C D D E — C D D E — — D E — — — —
4.2 C D D E — — D E E — — — E — — — — —
4.8 D D E — — — D E — — — — — — — — — —
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Legend - Joist Sizes:
A = 38 mm x 89 mm B = 38 mm x 140 mm C = 38 mm x 184 mm D = 38 mm x 235 mm E = 38 mm x 286 mm
Notes to Table 1.3.3.N.:
(1) For use of floors that support hay, straw, grain or other continuous loads.
(2) A dead load of 0.48 kPa is incorporated to allow for the dead weight of the floor system.
Page 14 • SB-11
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.3.O.
Built-up Wood Beam Sizes for Farm Buildings of Low Human Occupancy - Intermittent Loads(1)
Forming Part of Sentence 1.3.3.(1)
Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber)
Beam Span, m Total Load on Beam, kN/m
5.84 8.76 11.67 14.59 17.51 20.43 23.35 26.27 29.19 32.11 35.03
1.8 A A A B B D D G G J L
2.4 A A B D E H J L — — —
3.0 A C E H J K — — — — —
3.6 C H J L — — — — — — —
4.2 E J L — — — — — — — —
4.8 I L — — — — — — — — —
Column 1 2 3 4 5 6 7 8 9 10 11 12
Legend - Beam Sizes:
A = 3 - 38 mm x 184 mm E = 3 - 38 mm x 286 mm I = 4 - 38 mm x 286 mm
B = 4 - 38 mm x 184 mm F = 4 - 38 mm x 235 mm J = 6 - 38 mm x 235 mm
C = 3 - 38 mm x 235 mm G = 6 - 38 mm x 184 mm K = 5 - 38 mm x 286 mm
D = 5 - 38 mm x 184 mm H = 5 - 38 mm x 235 mm L = 6 - 38 mm x 286 mm
Notes to Table 1.3.3.O.:
(1) Loads are applied to the beam intermittently.
(2) A dead load of 0.584 kN/m is assumed for all beams.
(3) Floors systems supporting heavy loads over larger spans will require the use of steel beams or other specialized materials.
Table 1.3.3.P.
Built-up Wood Beam Sizes for Farm Buildings of Low Human Occupancy - Continuous Loads(1)
Forming Part of Sentence 1.3.3.(1)
Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber)
Beam Span, m Total Load on Beam, kN/m
5.84 8.76 11.67 14.59 17.51 20.43 23.35
1.8 A A B D G J L
2.4 A C E J L — —
3.0 D H J L — — —
3.6 H K — — — — —
4.2 K — — — — — —
4.8 L — — — — — —
Column 1 2 3 4 5 6 7 8
Legend - Beam Sizes:
A = 3 - 38 mm x 184 mm E = 3 - 38 mm x 286 mm I = 4 - 38 mm x 286 mm
B = 4 - 38 mm x 184 mm F = 4 - 38 mm x 235 mm J = 6 - 38 mm x 235 mm
C = 3 - 38 mm x 235 mm G = 6 - 38 mm x 184 mm K = 5 - 38 mm x 286 mm
D = 5 - 38 mm x 184 mm H = 5 - 38 mm x 235 mm L = 6 - 38 mm x 286 mm
Notes to Table 1.3.3.P.:
(1) For use of floors that support hay, straw, grain or other continuous loads.
(2) A dead load of 0.48 kPa is assumed for all beams.
(3) Floor systems supporting heavy loads over larger spans will require use of steel beams or other specialized materials.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.3.Q.
Ungraded Lumber, Full-Dimension Roof Beam Sizes for Farm Buildings of Low Human Occupancy (1)
Forming Part of Sentence 1.3.3.(1)
Total Load on Built-up Wood Beam, kN/m
Beam Span, m
5.84 8.76 11.67 14.59 17.51 20.43 23.35 26.27
1.8 A A B C D F G H
2.4 B D E H I J — —
3.0 D G I — — — — —
3.6 G J — — — — — —
4.2 J — — — — — — —
Column 1 2 3 4 5 6 7 8 9
Legend - Built-up Wood Beam Sizes:
A = 3 - 50.8 mm x 203.2 mm D = 5 - 50.8 mm x 203.2 mm G = 5 - 50.8 mm x 254.0 mm
B = 4 - 50.8 mm x 203.2 mm E = 6 - 50.8 mm x 203.2 mm H = 4 - 50.8 mm x 304.8 mm
C = 3 - 50.8 mm x 254.0 mm F = 4 - 50.8 mm x 254.0 mm I = 5 - 50.8 mm x 304.8 mm
J = 6 - 50.8 mm x 304.8 mm
Notes to Table 1.3.3.Q.:
(1) Ungraded lumber, full-dimension, built-up wood beam.
(2) A dead load of 0.584 kN/m is assumed.
(3) Beams are sized for roof load only.
Table 1.3.3.R.
Ungraded Lumber, Full-Dimension Roof Beam Sizes for Farm Buildings of Low Human Occupancy (1)
Forming Part of Sentence 1.3.3.(1)
Total Load on Sawn Beam, kN/m
Beam Span, m
5.84 8.76 11.67 14.59 17.51 20.43 23.35 26.27
1.8 A A B C D E F G
2.4 A B D D F G — —
3.0 C D E F — — — —
3.6 D F G — — — — —
4.2 E G — — — — — —
Column 1 2 3 4 5 6 7 8 9
Legend - Sawn Beam Sizes:
A = 127.0 mm x 203.2 mm D = 203.2 mm x 254.0 mm G = 254.0 mm x 355.6 mm
B = 127.0 mm x 254.0 mm E = 203.2 mm x 304.8 mm
C = 152.4 mm x 254.0 mm F = 254.0 mm x 304.8 mm
Notes to Table 1.3.3.R.:
(1) Ungraded lumber, full-dimension, sawn wood beam.
(2) A dead load of 0.584 kN/m is assumed.
(3) Beams are sized for roof load only.
Page 16 • SB-11
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.3.S.
Roof Plate-Beams and Lintels for Farm Buildings of Low Human Occupancy
Forming Part of Sentence 1.3.3.(1)
Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber)
Building
Total Roof Load, kPa, with Post Spacing at 2.4 m
Width, m
A B C D E F G H I
7.3 1.67 2.77 3.68 2.49 4.11 5.50 3.35 5.55 7.42
8.5 1.43 2.34 3.16 2.15 3.54 4.74 2.87 4.74 6.36
9.7 1.24 2.05 2.77 1.86 3.11 4.11 2.53 4.16 5.55
10.9 — 1.81 2.44 1.67 2.72 3.68 2.25 3.68 4.93
12.1 — 1.62 2.20 1.48 2.49 3.30 2.01 3.30 4.45
13.4 — 1.48 2.01 1.34 2.25 3.01 1.81 3.01 4.02
14.6 — 1.38 1.81 1.24 2.05 2.72 1.67 2.77 3.68
15.8 — 1.24 1.67 — 1.91 2.53 1.53 2.53 3.40
17.0 — — 1.58 — 1.77 2.34 1.43 2.39 3.16
18.2 — — 1.48 — 1.62 2.20 1.34 2.20 2.96
Building Total Roof Load, kPa, with Post Spacing at 3.0 m
Width, m A B C D E F G H I
7.3 — 1.72 2.29 1.53 2.58 3.44 2.10 3.44 4.64
8.5 — 1.48 1.96 1.34 2.20 2.96 1.77 2.96 3.97
9.7 — 1.29 1.72 — 1.91 2.58 1.58 2.58 3.44
10.9 — — 1.53 — 1.72 2.29 1.38 2.29 3.06
12.1 — — 1.38 — 1.53 2.05 1.24 2.05 2.77
13.4 — — 1.24 — 1.38 1.86 — 1.86 2.53
14.6 — — — — 1.29 1.72 — 1.72 2.29
15.8 — — — — — 1.58 — 1.58 2.10
17.0 — — — — — 1.48 — 1.48 1.96
18.2 — — — — — 1.38 — 1.38 1.81
Building Total Roof Load, kPa, with Post Spacing at 3.6 m
Width, m A B C D E F G H I
7.3 — 1.38 1.81 1.24 2.05 2.72 1.67 2.77 3.68
8.5 — — 1.58 — 1.77 2.34 1.43 2.39 3.16
9.7 — — 1.38 — 1.53 2.05 1.24 2.05 2.77
10.9 — — 1.19 — 1.38 1.81 — 1.81 2.44
12.1 — — — — 1.24 1.62 — 1.67 2.20
13.4 — — — — — 1.48 — 1.48 2.01
14.6 — — — — — 1.38 — 1.38 1.81
15.8 — — — — — 1.24 — 1.29 1.67
17.0 — — — — — — — — 1.58
18.2 — — — — — — — — 1.48
Column 1 2 3 4 5 6 7 8 9 10
Legend - Roof Plate-Beam and Lintel Sizes:
A = 2 - 38 mm x 184 mm D = 2 - 38 mm x 235 mm G = 2 - 38 mm x 286 mm
B = 3 - 38 mm x 184 mm E = 3 - 38 mm x 235 mm H = 3 - 38 mm x 286 mm
C = 4 - 38 mm x 184 mm F = 4 - 38 mm x 235 mm I = 4 - 38 mm x 286 mm
Notes to Table 1.3.3.S.:
(1) Trusses are at 1.2 m on centres.
(2) Plate-beam/lintel loading can be very significant.
(3) Specifications for anchorage at supporting posts must be specified by a competent designer.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.3.T.
Roof Plate-Beams and Lintels for Farm Buildings of Low Human Occupancy
Forming Part of Sentence 1.3.3.(1)
Ungraded Lumber-Full Dimension
Building
Total Roof Load, kPa, with Post Spacing at 2.4 m
Width, m
A B C D E F G H I
7.3 — 1.72 2.29 1.48 2.44 3.25 1.91 3.20 4.26
8.5 — 1.43 1.96 1.24 2.10 2.77 1.67 2.72 3.68
9.7 — 1.29 1.72 — 1.81 2.44 1.43 2.39 3.20
10.9 — — 1.53 — 1.62 2.15 1.29 2.15 2.87
12.1 — — 1.34 — 1.48 1.96 — 1.91 2.58
13.4 — — 1.24 — 1.34 1.77 — 1.72 2.34
14.6 — — — — 1.19 1.62 — 1.58 2.15
15.8 — — — — — 1.48 — 1.48 1.96
17.0 — — — — — 1.38 — 1.38 1.81
18.2 — — — — — 1.29 — 1.29 1.72
Building Total Roof Load, kPa, with Post Spacing at 3.0 m
Width, m A B C D E F G H I
7.3 — — 1.43 — 1.53 2.05 1.19 2.01 2.68
8.5 — — 1.19 — 1.29 1.72 — 1.72 2.29
9.7 — — — — — 1.53 — 1.48 2.01
10.9 — — — — — 1.34 — 1.34 1.77
12.1 — — — — — 1.19 — — 1.58
13.4 — — — — — — — — 1.43
14.6 — — — — — — — — 1.34
15.8 — — — — — — — — 1.24
17.0 — — — — — — — — —
18.2 — — — — — — — — —
Building Total Roof Load, kPa, with Post Spacing at 3.6 m
Width, m A B C D E F G H I
7.3 — — — — 1.19 1.62 — 1.58 2.15
8.5 — — — — — 1.38 — 1.38 1.81
9.7 — — — — — 1.19 — — 1.58
10.9 — — — — — — — — 1.43
12.1 — — — — — — — — 1.29
13.4 — — — — — — — — —
14.6 — — — — — — — — —
15.8 — — — — — — — — —
17.0 — — — — — — — — —
18.2 — — — — — — — — —
Column 1 2 3 4 5 6 7 8 9 10
Legend - Roof Plate-Beam and Lintel Sizes:
A = 2 - 50.8 mm x 203.2 mm D = 2 - 50.8 mm x 254.0 mm G = 2 - 50.8 mm x 304.8 mm
B = 3 - 50.8 mm x 203.2 mm E = 3 - 50.8 mm x 254.0 mm H = 3 - 50.8 mm x 304.8 mm
C = 4 - 50.8 mm x 203.2 mm F = 4 - 50.8 mm x 254.0 mm I = 4 - 50.8 mm x 304.8 mm
Notes to Table 1.3.3.T.:
(1) Trusses are at 1.2 m on centres.
(2) Plate-beam/lintel loading can be very significant.
(3) Specifications for anchorage at supporting posts must be specified by a competent designer.
Page 18 • SB-11
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.4.U.
Stud Sizes for Farm Buildings of Low Human Occupancy (Single Storey)
Forming Part of Sentence 1.3.4.(1)
Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber)
Total Wind Load: q10 ≤ 0.30 kPa Wind Load: q10 ≤ 0.45 kPa
Sidewall Roof
406 mm o.c. 610 mm o.c. 406 mm o.c. 610 mm o.c.
Height, m Load,
kPa Building Width, m Building Width, m Building Width, m Building Width, m
9.14 12.2 15.2 18.3 9.14 12.2 15.2 18.3 9.14 12.2 15.2 18.3 9.14 12.2 15.2 18.3
1.9 A A A A A A A B A A A A A A A B
2.4 A A A A A A B B A A A A A A B B
3.0
2.8 A A A A A A B B A A A A A B B B
3.3 A A A B A B B B A A A B A B B B
1.9 A A A B A B B B A A A B B B B B
2.4 A A B B B B B B A A B B B B B B
3.6
2.8 A B B B B B B B A B B B B B B B
3.3 A B B B B B B B A B B B B B B B
1.9 B B B B B B B B B B B B B B B B
2.4 B B B B B B B B B B B B B B B B
4.2
2.8 B B B B B B B B B B B B B B B B
3.3 B B B B B B B B B B B B B B B B
1.9 B B B B B B B B B B B B B B B B
2.4 B B B B B B B B B B B B B B B C
4.8
2.8 B B B B B B B C B B B B B B C C
3.3 B B B B B B C C B B B B B B C C
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Legend - Stud Sizes:
A = 38 mm x 89 mm
B = 38 mm x 140 mm
C = 38 mm x 184 mm or double 38 mm x 140 mm under the trusses, with an intermediate 38 mm x 140 mm stud at 610 mm.
Notes to Table 1.3.4.U.:
(1) Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
(2) It is assumed that the double top plate is rigid enough to cause load sharing amongst all studs regardless of the spacing 406 mm or
610 mm.
(3) Solid bridging shall be used on all walls as follows:
≤ 3.0 m: 1 row at mid-height.
3.6 m - 4.2 m: 2 rows at third-points.
4.8 m: 3 rows at quarter-points.
(4) Wind bracing shall not impose additional bending forces onto the stud.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.4.V.
Stud Sizes for Farm Buildings of Low Human Occupancy (With Second Storey Loading)
Forming Part of Sentence 1.3.4.(1)
Spruce-Pine-Fir, No. 1 and No. 2 (Dressed Lumber)
Total Wind Load: q10 ≤ 0.30 kPa Wind Load: q10 ≤ 0.45 kPa Second
Sidewall Roof Storey
406 mm o.c. 610 mm o.c. 406 mm o.c. 610 mm o.c.
Height, m Load, Plate,
kPa Building Width, m Building Width, m Building Width, m Building Width, m kN/m
9.14 12.2 15.2 18.3 9.14 12.2 15.2 18.3 9.14 12.2 15.2 18.3 9.14 12.2 15.2 18.3
1.9 B B B B B B B B B B B B B B B B
2.4 B B B B B B B B B B B B B B B B
3.0 14.6
2.8 B B B B B B B B B B B B B B B B
3.3 B B B B B B B B B B B B B B B B
1.9 B B B B B B B C B B B B B B C C
2.4 B B B B B B C C B B B B B C C C
3.6 14.6
2.8 B B B B B B C C B B B B B C C C
3.3 B B B B B C C C B B B B C C C C
1.9 A A B B B B B B B B B B B B B B
2.4 A B B B B B B B B B B B B B B B
3.0 7.3
2.8 A B B B B B B B B B B B B B B B
3.3 B B B B B B B B B B B B B B B B
1.9 B B B B B B B B B B B B B B B B
2.4 B B B B B B B B B B B B B B B B
3.6 7.3
2.8 B B B B B B B B B B B B B B B B
3.3 B B B B B B B B B B B B B B B C
1.9 A A A A A B B B A A A A B B B B
2.4 A A A B B B B B A A A A B B B B
3.0 3.6
2.8 A A B B B B B B A A B B B B B B
3.3 A A B B B B B B A B B B B B B B
1.9 A B B B B B B B B B B B B B B B
2.4 B B B B B B B B B B B B B B B B
3.6 3.6
2.8 B B B B B B B B B B B B B B B B
3.3 B B B B B B B B B B B B B B B B
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Legend - Stud Sizes:
A = 38 mm x 89 mm
B = 38 mm x 140 mm
C = 38 mm x 184 mm or double 38 mm x 140 mm
Notes to Table 1.3.4.V.:
(1) Design is based on load combinations of total roof load, wind load and stored product acting at the same time on a closed building.
(2) All notes following Table 1.3.4.U. apply, with the following conditions/exceptions:
• 14.6 kN/m loading: Full 4.8 m sidewall hay/straw storage space above. It is supported by beams spaced at 3.6 m o.c. The
outside plate carries a 1.8 m floor width. If the loading is greater, refer to a qualified person for design.
• 7.3 kN/m loading: Full 2.4 m sidewall hay/straw storage space above or a gambrel roof structure >9.14 m in total width.
Floor support beams as above.
• 3.6 kN/m loading: Small gambrel roof structure or storage space for light storage. Floor support beams as above.
Page 20 • SB-11
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Table 1.3.4.W.
Stud Sizes for Farm Buildings of Low Human Occupancy (Single Storey)
Forming Part of Sentence 1.3.4.(1)
Ungraded Lumber, Full-Dimensioned
Total Wind Load: q10 ≤ 0.30 kPa Wind Load: q10 ≤ 0.45 kPa
Sidewall Roof
406 mm o.c. 610 mm o.c. 406 mm o.c. 610 mm o.c.
Height, m Load,
kPa Building Width, m Building Width, m Building Width, m Building Width, m
9.14 12.2 15.2 18.3 9.14 12.2 15.2 18.3 9.14 12.2 15.2 18.3 9.14 12.2 15.2 18.3
1.9 A A A A A A A B A A A A A A B B
2.4 A A A A A A B B A A A A A B B B
3.0
2.8 A A A A A B B B A A A B B B B B
3.3 A A A B A B B B A A A B A B B B
1.9 A A A B A B B B A A A B B B B B
2.4 A A B B B B B B A A B B B B B B
3.6
2.8 A B B B B B B B A B B B B B B B
3.3 A B B B B B B B B B B B B B B C
1.9 B B B B B B B B B B B B B B B B
2.4 B B B B B B B B B B B B B B B C
4.2
2.8 B B B B B B B C B B B B B B C C
3.3 B B B B B B C C B B B B B C C C
1.9 B B B B B B B C B B B B B B C C
2.4 B B B B B B C C B B B B B C C C
4.8
2.8 B B B B B B C C B B B C C C C C
3.3 B B B B B C C C B B B C C C C C
Column 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Legend - Stud Sizes:
A = 50.8 mm x 101.6 mm
B = 50.8 mm x 152.4 mm
C = 50.8 mm x 203.2 mm or double 50.8 mm x 152.4 mm under the trusses, with an intermediate 50.8 mm x 152.4 mm stud at 610 mm
Notes to Table 1.3.4.W.:
(1) Designs are based on load combinations of total roof load and wind load acting at the same time on a closed building.
(2) It is assumed that the double top plate is rigid enough to cause load sharing amongst all studs regardless of the spacing 406 mm or
610 mm.
(3) Solid bridging shall be used on all walls as follows:
≤ 3.0 m: 1 row at mid-height.
3.6 m to 4.2 m: 2 rows at third-points.
4.8 m: 3 rows at quarter-points.
(4) Wind bracing shall not impose additional bending forces onto the stud.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
2024MMAH Supplementary Standard SB-11
Page 22 • SB-11
Ministry of Municipal Affairs
Building and Development Branch
MMA Supplementary Standard SB-12
MMAH Supplementary Standard SB-12
Energy Efficiency For Housing
July 7, 2016 update
2024MMA Supplementary Standard SB-12
COMMENCEMENT
MMA Supplementary Standard SB-12 comes into force on the 1st day of January, 2025.
EDITORIAL
e1 Editorial correction issued for January 1, 2025.
© Copyright
©
Copyright King’s Printer for Ontario 2024
All rights reserved.
Questions regarding copyright, including reproduction and distribution, may be directed to the Director,
Building and Development Branch of the Ministry of Municipal Affairs and Housing.
Understand any provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Try BUILDAiD Beta
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.