OBC VOLUME 2 · APPENDIX A · NOTES TO PART 5Updated for the 2024 Ontario Building Code
Appendix A — Explanatory Notes to Part 5
Appendix A explanatory notes for Part 5 of Division B of the 2024 Ontario Building Code. These notes are advisory: they explain the intent behind code provisions and how to apply them.
A-5.1.1.1.(1)Scope.
Part 5 provides explicit requirements related to the transfer of heat, air, moisture and sound in various forms. Control of the
ingress of radon and other soil gases is addressed by the requirements related to air leakage.
A-5.1.2.1.(1)Application.
Subsection 1.3.3. of Division A specifies that Part 5 applies to all buildings except those within the scope of Part 2, Part 9 or
the scope of the National Farm Building Code of Canada 1995. Because of their intended use, many buildings need only
provide a limited degree of separation from the outdoor environment, the ground, or between interior spaces. The provisions
in Part 5 are written to allow exemptions for these buildings.
Part 5 applies to building elements that separate dissimilar environments and to site conditions that may affect environmental
loading on the building envelope.
The provisions address
• the design and construction, or selection, of building components, such as windows and doors,
• the design and construction of building assemblies, such as walls, floors and roofs,
• the design and construction of the interfaces between the above-mentioned elements, and
• the design or selection, and installation, of site materials, components and assemblies, such as backfill and drainage,
and grading.
Part 5 applies not only to building elements that separate indoor space from outdoor space, but also to those elements that
separate indoor space from the ground and that separate adjacent indoor spaces having significantly different environments.
Indoor spaces that require separation include interior conditioned spaces adjacent to indoor unconditioned spaces, and
adjacent interior conditioned spaces that are intended to provide different environments. An extreme example of the last
would be a wall that separates an indoor ice rink from a swimming pool.
Some building elements are exposed to exterior environmental loads but do not separate dissimilar environments. Solid
guards on exterior walkways are one example. Such elements are subject to the application of Part 5.
A-5.1.4.1.Application of Structural Design to Other Building Elements.
Part 4, as currently written, applies primarily to buildings as a whole and to structural members. Requirements defining
structural loads and design to accommodate or resist those loads, however, apply not only to buildings as a whole and
components that are traditionally recognized as structural members, but also apply to other elements of the building that are
subject to structural loading. This is addressed to some extent in Part 4 by the requirements that pertain, for example, to wind
loads on cladding. A range of structural loads and effects, as defined in Subsection 4.1.2., may be imposed on non-
loadbearing elements such as backing walls, roofing, interior partitions and their connections. These must generally be
addressed using the same load determination and structural design procedures as used for structural members.
Responsibility for the structural design of buildings as a whole and their structural members is commonly assigned to the
designer of record. The application of Part 4 reflects this, and as such, “non-structural” elements are not explicitly identified
in the Part 4 provisions. Rather, the application of Part 4 to these elements is specified in cross-references from other Parts of
the Code, e.g. Part 5, which recognizes the fact that the structural design of these elements is often carried out by designers
other than the designer of record.
Part 4 does not generally apply to the structural design of building services, such as heating, ventilating, air-conditioning,
plumbing, electrical, electronic or fire safety systems, though these may be subject to structural loads. It does, however,
apply to the design of the connections of building services to address earthquake loads (see Article 4.1.8.18.).
Page 128 Appendix A • Volume 2
A-5.1.4.1.(2)Materials, Components and Assemblies with Multiple Functions.
Where materials, components or assemblies are used to fulfill multiple functions, the designer may have to take into account
their function with regard to structural loads, heat transfer, air leakage, vapour diffusion, and protection from precipitation,
surface and ground water, and sound transmission. Materials should be selected taking into account the environmental loads
to which they will be subjected, their physical and chemical characteristics, and their installation. Design and construction
details should satisfy all intended functions and ensure continuity within and between assemblies, without adversely
impacting adjacent materials, components or assemblies. The designer should also anticipate unintended consequences when
materials that may fulfill multiple functions are used. For example, building membranes consisting of modified bitumen
compounds, which are commonly used to control both water ingress and air leakage, also typically have low vapour
transmission characteristics. Similarly, extruded polystyrene boards, which are used as thermal insulation, may also act as a
component of an air barrier assembly, thus requiring wind loads to be considered.
An increasing number of manufactured systems are being used to serve more than one (and sometimes all) of the functions of
an environmental separator: examples include pre-engineered building systems, exterior insulation finish systems, insulated
metal panel systems, windows, other fenestration assemblies, and insulated precast concrete wall panels. These systems
consist of combinations of pre-manufactured and/or site-built components, which are supposed to be assembled in a
prescribed manner.
Ensuring compliance with one Section of Part 5 may impact compliance with other Sections of Part 5: for example, air
barriers that are integral to some systems may also act as vapour barriers and impact condensation control. By extension,
ensuring compliance with the requirements of Part 5 may impact compliance with other Parts of the Building Code: for
example, increasing the thickness of the insulation to improve an assembly’s thermal performance may impact its compliance
with Part 3 with regard to fire resistance.
Compliance with a standard listed in Section 5.9. does not ensure that a system is appropriate for the intended application.
The designer should consider all relevant criteria, beyond the standard tests, when selecting an appropriate product for a
project.
A-5.1.4.1.(5)Past Performance as Basis for Compliance with Respect to
Structural Loads.
As discussed in Note A-5.1.4.1., a range of structural loads and effects can be imposed on materials, components and
assemblies in environmental separators and assemblies exposed to the exterior. In many instances, compliance with Sentence
5.1.4.1.(1) for structural loads must be determined based on the loads and calculation methods described in Part 4 as specified
in Sentence 5.1.4.1.(3) and the referenced Subsection 5.2.2., e.g. for cladding. In practice, compliance for some materials,
components or assemblies of environmental separators and assemblies exposed to the exterior is determined by relying on
provisions governing the use of alternative solutions (such as Clause 1.2.1.1.(l)(b) of Division A).
For some very common building elements and installations, however, there is a very large body of evidence of proven
performance over a long period of time. In these cases, imposing the degree of analysis, or documentation of performance,
required by Part 4 or Section 2.1. of Division C would be unnecessary and onerous. Clause 5.1.4.1.(5)(b) is intended to
address these particular cases. Because these common building elements and assemblies are so widely accepted throughout
the industry and the body of evidence is so substantial (though not necessarily documented in an organized fashion), detailed
analysis or documentation is unnecessary.
Whether compliance of a particular material, component or assembly may be determined based on past performance depends
not only on the type of material, component or assembly, but also on its intended function, the particular loads to which it
will be subject and the magnitude of those loads. Because the possible number of combinations and permutations is
astronomical, only guidelines can be provided as to when past performance is a reasonable basis for determining compliance.
In determining compliance based on past performance, the period of past performance considered should be a substantial
number of years. For example, 30 years is often used to do life-cycle cost analysis of the viability of investments in building
improvements. This period is more than long enough for most deficiencies to show up. There should be no question as to
the structural adequacy of a material, component or assembly that has been successfully used in a given application for such a
period.
Appendix A • Volume 2 Page 129
The determination of compliance may be based on past performance only where the function of the material, component or
assembly is identical to that of the materials, components or assemblies used as a reference, and where the expected loads do
not exceed those imposed on the reference materials, components or assemblies. For example, the acceptance of gypsum
board, and its fastening, to serve as part of the backing wall supporting cladding cannot be based on the performance of
gypsum board that has served only as an interior finish.
The determination of compliance may be based on past performance only where the properties of the material, component or
assembly are identical or superior to those of the materials, components or assemblies used as a reference. For example,
where a component of a certain gauge of a particular metal has provided acceptable performance, the same component made
of the same metal or a stronger one would be acceptable.
Compliance with respect to various loads may be determined individually. A particular material may have to be designed to
Part 4 to establish acceptable resistance to wind or earthquake loads, for example, but past performance may be adequate to
determine that the material and normal fastening will support the material’s dead load and will resist loads imposed by
thermal and moisture-related expansion and contraction.
Past performance is a reasonable basis for determining compliance for lighter materials, components or assemblies not
subject to wind load; for example, semi-rigid thermal insulation installed in wall assemblies where other materials,
components or assemblies are installed to resist air pressure loads.
Past performance is an appropriate basis for determining compliance for some smaller elements that will be subject to wind
loads but are continually supported or fastened behind elements that are designed for wind loads, for example, standard
flashing over wall penetrations.
It should be noted that this particular approach to demonstrating compliance pertains only to the resistance or accommodation
of structural loads described in Part 4. The resistance or accommodation of environmental loads, resistance to deterioration,
and material compatibility must still be addressed in accordance with Part 5.
A.5.1.4.1.(6)(b) and (c) Accommodating Movement.
It is well understood that the deflection of the backing assembly in a wall can have significant effects on the performance of
the cladding. For example, CSA S304, “Design of Masonry Structures”, specifies the maximum deflection criteria for
backing assemblies to masonry veneer. Clauses 5.1.4.1.(6)(b) and (c) are written in very general terms in recognition of the
fact that not only can the deflection of cladding affect the performance of the backing assembly, but that the excessive
deflection of any element has the potential to adversely affect the performance of any adjacent element. Similarly, inter-
storey drift has the potential to adversely affect the performance of components and assemblies of environmental separators.
CSA O86, “Engineering Design in Wood”, specifies a method for calculating building movement due to changes in moisture
content. The effects of movement should be avoided or accommodated.
A-5.1.4.2.Deterioration.
Environmental loads that must be considered include but are not limited to: sound, light and other types of radiation,
temperature, moisture, air pressure, acids and alkalis.
Mechanisms of deterioration include:
• structural (impact, air pressure)
• hygrothermal (freeze-thaw, differential movement due to thermal expansion and contraction, ice lensing)
• electrochemical (oxidation, electrolytic action, galvanic action, solar deterioration)
• biochemical (biological attack, intrusion by insects and rodents).
Information on the effects of deformations in building elements can be found in the Commentary entitled “Effects of
Deformations in Building Components” in the “Structural Commentaries (User's Guide – NBC 2020: Part 4 of Division B)”.
Resistance to deterioration may be determined based on rational analysis, such as hygrothermal modeling, field performance,
accelerated testing, or compliance with guidelines provided by evaluation agencies recognized by the authority having
jurisdiction. Designers of buildings covered in Part 5 can find design guidance in the NRC publication entitled “Guideline on
Page 130 Appendix A • Volume 2
Design for Durability of Building Envelopes”, and in CSA S478, “Durability in Buildings”, which presents updated
methodologies for analyzing resistance to deterioration that provide quantitative results to support informed design decisions.
It is noted that the effects of future climate change and their potential impact on the durability of buildings are not
fully known and, as such, are still being researched and studied. How future climate change and the issues of climate
resilience are incorporated in building design should be carefully considered within the context of existing Code
provisions related to structural design, fire and life safety, etc.
It is also noted that CSA S478 contains requirements for actions beyond the scope of the Building Code, which may not
be the responsibility of the designer, builder or authority having jurisdiction. These include requirements relating to
quality assurance, inspection, maintenance, minimum design service lives and potential impacts of climate change,
which are not addressed in the Code. The reference herein to CSA S478 is not intended to imply that the designer,
builder or authority having jurisdiction adopt, apply or enforce any of these requirements.
Building components should be designed with some understanding of the length of time over which they will effectively
perform their intended function. Actual service life will depend on the materials used and the environment to which they are
exposed. The design should take into consideration these factors, the particular function of the component and the
implications of premature failure, the ease of access for maintenance, repair or replacement, and the cost of repair or
replacement.
Many buildings are designed such that access for maintenance, repair or replacement is not possible without damaging – or
seriously risking damaging – other building elements. This can become a considerable deterrent to proper maintenance thus
compromising the performance of the subject materials, components and assemblies, or other elements of the building. In
cases where it is known or expected that maintenance, repair or replacement is likely to be required for certain elements
before such time as the building undergoes a major retrofit, special consideration should be given to providing easy access to
those elements. Anchorage points for maintenance personnel should be considered during the design of multi-storey
buildings, including those of wood-frame construction, as adding them post-construction can be difficult.
Where the use of a building or space, or the services for a building or space, are changed significantly, an assessment of the
impact of the changes on the environmental separators should be conducted to preclude premature failures that could create
hazardous conditions.
A-5.2.1.1.(3)Soil Temperatures.
In theory, soil temperatures are needed to determine the conformance of a design to the requirements related to heat transfer
and vapour diffusion. In practice, standard construction in a particular area may have proven to perform quite adequately and
detailed calculations of soil temperature are unnecessary. (See also Sentence 5.2.1.3.(2).)
A-5.2.1.2.(1)Interior Environmental Loads.
The interior environmental conditions required depend on the intended use of the spaces in the building as defined in the
building program. Spaces in different types of buildings and different spaces within a single building may impose different
loads on the separators between interior and exterior spaces and between adjacent interior spaces. The separators must be
designed to withstand the expected loads.
A-5.2.2.1.(2)(c)Determination of Structural Loads and Effects.
For the design of post-disaster buildings, the effects of earthquake loads on the ability of materials, components and
assemblies and their interfaces to resist or accommodate environmental loads must be taken into account. For such buildings,
seismic effects must be taken into account in the design for environmental separation, as these buildings are required to have
an adequate degree of functionality after the seismic event to meet their intended function (see Article 4.1.8.13. for
deflections and drift limits for post-disaster buildings). For all other buildings, damage to building components during
seismic events is anticipated and these buildings are not intended to be functional after the event. However, for post-disaster
buildings, seismic effects must be taken into account in the design for environmental separation, as these buildings are
required to have an adequate degree of functionality after the design event to meet their intended function (see Article
4.1.8.13. for deflections and drift limits for post-disaster buildings).
Appendix A • Volume 2 Page 131
However, it is important to note that earthquake effects must be taken into account in the seismic design of all building
materials, components and assemblies and their interfaces covered by Article 4.1.8.18. to address life safety and the structural
protection of buildings.
A-5.2.2.2.Resistance to Wind and Other Air Pressure Loads.
The wind load provisions apply to roofing and other materials subject to wind-uplift loads.
Note that, although Article 5.2.2.2. is specifically concerned with wind loads and directly references only two Sentences from
Part 4, Sentence 5.2.2.1.(1) references all of Part 4 and would invoke Article 4.1.7.10. for example, that is concerned with air
pressure loads on interior walls and partitions.
A-5.2.2.2.(4)Membrane Roofing Systems.
Wind loads for membrane roofing systems must be calculated in accordance with Part 4. The tested uplift resistance and
factored load should satisfy the requirements of the Commentary entitled “Limit States Design” in the “Structural
Commentaries (User's Guide – NBC 2020: Part 4 of Division B)”.
The test method described in CAN/CSA-A123.21, “Standard Test Method for the Dynamic Wind Uplift Resistance of
Membrane-Roofing Systems”, applies only to membrane roofing systems whose components’ resistance to wind uplift is
achieved by fasteners or adhesives. It does not apply to roofing systems that use ballasts, such as gravel or pavers, to secure
the membrane against wind uplift.
In the case of membrane roofing systems in which the waterproof membrane is attached to the structural deck using
mechanical fasteners, the wind-induced forces and the roofing system’s response are time- and space-dependent and, thus,
dynamic in nature. Further information on the design and evaluation of such systems can be found in “A Guide for the Wind
Design of Mechanically Attached Flexible Membrane Roofs”, published by NRC.
The wind uplift resistance obtained from the test method in CAN/CSA-A123.21 is limited to configurations with specific
fastener or adhesive patterns. To extrapolate the test data to non-tested configurations, refer to ANSI/SPRI WD-1, "Wind
Design Standard Practice for Roofing Assemblies", for a rational calculation procedure. However, in using this extrapolation
procedure, wind loads should be calculated in accordance with the NBC. NRC's guide for wind design referenced above
provides further guidance and examples of wind load calculations.
A-5.3.Heat Transfer.
In addressing issues related to health and safety, Section 5.3. calls up levels of thermal resistance needed to minimize
condensation on or within environmental separators, and to ensure thermal conditions appropriate for the building use.
Part 12 specifies levels of thermal resistance required for energy efficiency or calls up energy performance levels, which
relate to levels of thermal resistance. Where Part 5 calls for levels of thermal resistance higher than those required by
Part 12, the requirements of Part 5 take precedence.
A-5.3.1.1.Required Resistance to Heat Transfer.
The control of heat flow is required wherever there is an intended temperature difference across the building assembly. The
use of the term “intended” is important since, whenever interior space is separated from exterior space, temperature
differences will occur.
The interior of an unheated warehouse, for example, will often be at a different temperature from the exterior due to solar
radiation, radiation from the building to the night sky and the time lag in temperature change due to the thermal mass of the
building and its contents. If this temperature difference is not “intended,” no special consideration need be given to the
control of heat flow.
If the warehouse is heated or cooled, thus making the temperature difference “intended,” some consideration would have to
be given to the control of heat flow.
Page 132 Appendix A • Volume 2
It should be noted, however, that in many cases, such as with adjacent interior spaces, there will be an intended temperature
difference but the difference will not be great. In these cases, the provisions to control heat flow may be little or no more
than would be provided by any standard interior separator. That is, materials typically used in the construction of partitions
may provide the separation needed to meet the requirements of Section 5.3. without adding what are generally considered to
be “insulating” materials.
A-5.3.1.2.Material and Component Properties and Condensation.
Total prevention of condensation is generally unnecessary and its achievement is rarely a certainty at design conditions.
Part 5, therefore, requires that condensation be minimized. The occurrence of condensation should be sufficiently rare, or the
quantities accumulated should be sufficiently small and dry rapidly enough, to avoid material deterioration and the growth of
mould and fungi.
The Harmonized North American Fenestration Standard, AAMA/WDMA/CSA 101/I.S.2/A440, “NAFS – North
American Fenestration Standard/Specification for Windows, Doors, and Skylights”, identifies procedures to determine the
condensation resistance and thermal transmittance of windows, doors and skylights though testing for condensation
resistance is presented as optional in the standard. As such, a fenestration product that meets the standard’s requirements on
air leakage, water penetration, uniform load and other performance requirements may not meet the condensation resistance
performance level needed for a given application.
Only the physical test procedure presented in CSA A440.2, “Fenestration Energy Performance”, can be used to establish the
temperature index (I) value, which denotes condensation resistance performance evaluation criteria. It is recommended that
designers specify I values for a given application to minimize the potential for condensation. Further guidance on the
selection of the correct I value is provided in CSA A440.3, “User Guide to CSA A440.2-19, Fenestration Energy
Performance”.
The scope of AAMA/WDMA/CSA 101/I.S.2/A440, which is referenced in Subsection 5.9.2., includes skylights and tubular
daylighting devices (TDD). Where skylights and TDDs pass through unconditioned space, their wells and shafts may
become the environmental separator and would therefore have to comply with the requirements of Part 5.
A-5.3.1.2.(1)Use of Thermal Insulation or Mechanical Systems for
Environmental Control.
The level of thermal resistance required to avoid condensation on the warm side of an assembly or within an assembly (at the
vapour barrier) and to permit the maintenance of indoor conditions appropriate for the occupancy depends on:
• the occupancy
• the exterior design air temperature
• the interior design air temperature and relative humidity
• the capacity of the heating system, and
• the means of delivering heat.
To control condensation on the interior surface of an exterior wall, for example, the interior surface must not fall below the
dew point of the interior air. If, for instance, the interior air is 20°C and 35% RH, the dew point will be 4°C. If the interior
air is 20°C and 55% RH, the dew point will be 11°C.
Exterior design temperatures are low in Ontario; for example, -20°C in Toronto, and -35°C in Geraldton. In these cases,
maintaining temperatures inboard of the vapour barrier above the dew point requires insulation. In these cases, maintaining
temperatures inboard of the vapour barrier above the dew point will require insulation or increased heat delivery to the
environmental separator. Direct delivery of heat over the entire surface of the environmental separator is generally
impractical. Indirect heat delivery may not be possible without raising the interior air temperatures above the comfort level.
In any case, increased heat delivery would often entail excessive energy costs.
In addition to controlling condensation, interior surface temperatures must be warm enough to avoid occupant discomfort due
to excessive heat loss by radiation. Depending on the occupancy of the subject spaces, this may require the installation of
insulation even where it is not needed to control condensation.
Appendix A • Volume 2 Page 133
A-5.3.1.3.(2)Position of Materials Providing Thermal Resistance.
For a material providing thermal resistance to be effective, it must not be short-circuited by convective airflow through or
around the material. The material must therefore be either
• the component of the air barrier system providing principal resistance to air leakage, or
• installed in full and continuous contact with a continuous low air permeance component.
A-5.4.1.Air Barrier Systems.
An air barrier system is required in most buildings to control air movement through the environmental separator to
minimize
• the condensation of airborne moisture within the environmental separator,
• discomfort from drafts,
• the infiltration of dust, soil gases, and other pollutants,
• interference in the performance of building services, such as HVAC and plumbing,
• the infiltration of exterior precipitation, and
• the loss of airborne heat energy.
The requirements for air barrier systems in Part 5 address all of these issues, except the loss of airborne heat energy, which is
an energy performance issue and, as such, is addressed in the NECB. Failure to manage the issues addressed in Part 5 can
lead to serious health or safety hazards.
The most significant issues are those with the potential to cause moisture-related material deterioration, such as rot and
corrosion, which can lead to the failure of component connections. Where the environmental separator is subject to high
moisture levels, mould can grow if spores and organic materials are present.
A-5.4.1.1.Locations Where an Air Barrier System Is Required.
Where the hygrothermal environments in adjacent interior spaces are sufficiently different, an air barrier system is required to
control the airflow between the spaces in order to maintain the different environments. Examples of such adjacent spaces
include skating arenas adjoining swimming pools, and industrial office spaces adjoining industrial production spaces.
An air barrier system is also required in building assemblies in contact with the ground to control the ingress of radon and
other soil gases, such as methane.
In addition to an air barrier system, other measures may be required in certain regions of Canada to reduce the radon
concentration to a level below the guideline specified by Health Canada. Further information on protection from radon
ingress can be found in:
• “Radon: A Guide for Canadian Homeowners” (CMHC/HC),
• “Guide for Radon Measurements in Public Buildings (Schools, Hospitals, Care Facilities, Detention Centres)” (HC),
and
• EPA 625/R-92/016, “Radon Prevention in the Design and Construction of Schools and Other Large Buildings.”
A-5.4.1.1.(3)Air Leakage Performance Classes for Air Barrier Assemblies.
The selection of a Performance Class for an air barrier assembly is intended to ensure that the air leakage performance level
of the assembly is sufficient to minimize condensation and reduce the uncontrolled movement of air across the environmental
separator.
The accumulation of condensation within a building assembly as a result of air leakage through the environmental separator
depends on the following:
• the air leakage rate of the air barrier assembly,
• the location of the accumulation of condensation within the building assembly, and
• the drying potential of the building assembly (i.e., its ability to release moisture through vapour diffusion and surface
evaporation, both inward and outward).
Page 134 Appendix A • Volume 2
Critical to the rates of both drying and the accumulation of condensation is the location where moisture may occur within the
building assembly. The location and amount of accumulation of condensation due to air leakage are influenced by the
materials used in the building assembly and the temperatures within the assembly. The location of insulation within the
building assembly is critical and can directly influence whether condensation occurs and how much moisture condensation
actually accumulates.
The drying potential of the building assembly is dependent on the water vapour permeance of the various layers in the
building assembly (e.g., exterior sheathing, sheathing membrane, unvented cladding, vapour barrier).
CAN/ULC-S742, “Standard for Air Barrier Assemblies – Specification,” contains requirements and test methods for air
barrier assemblies used in high- and low-rise buildings. The standard classifies the air leakage performance of air barrier
assemblies on the basis of air leakage rate, building height, and wind pressure loading. The approach in the standard is
consistent with limit states design principles to allow for the direct incorporation of test results into the overall structural
design of the building.
Unlike ASTM E2357, “Standard Test Method for Determining Air Leakage Rate of Air Barrier Assemblies”, CAN/ULC-
S742 measures air leakage under two temperature conditions:
(1) at ambient temperatures with no temperature differential across the test assembly, and
(2) with the exterior side of the test assembly at a temperature of −20°C and the interior side at a temperature of +20°C
(i.e., with a temperature differential of 40°C across the test assembly).
This difference makes the testing approach in CAN/ULC-S742 more appropriate for the climate in most regions of Canada.
CAN/ULC-S742 does not address the structural transfer of air pressure loads from air barrier assemblies to adjoining air
barrier assemblies or the primary structure. Nevertheless, this transfer of loads must be addressed by the designer.
The Performance Class of an air barrier assembly is selected on the basis of the following:
• the moisture loads on the building assembly due to the hygrothermal characteristics of the air,
• the ability of the materials and components of the building assembly to absorb and distribute moisture,
• the ability of the building assembly to dissipate moisture before it can lead to harm to the occupants or
damage to the materials and components of the building assembly, and
• the moisture tolerance of the materials from which the building assembly is constructed.
Air barrier assemblies with lower air leakage rates are typically necessary where the drying potential of the building
assembly is low and/or the moisture sensitivity of components of the building assembly is high.
Before selecting the appropriate Performance Class, the designer should consider formal study, analysis and/or
modeling to establish performance criteria for each air barrier assembly. Further guidance can be found in the NRC
publication entitled “Guideline on Design for Durability of Building Envelopes”. This recommendation is
particularly important for buildings with
• higher than normal operating hygrothermal characteristics, e.g., museums, swimming pools and
laboratories,
• building assemblies made from materials and components with lower than normal moisture tolerances, e.g.,
wood and other organic materials, or
• occupancies with a low tolerance for the potential health risks associated with condensation, e.g.,
hospitals, long-term care facilities and laboratories.
In such cases, Performance Classes with lower air leakage rates should be selected.
A-5.4.1.1.(4)Continuity of Air Barrier Systems.
An air barrier system can only function properly if all the materials, components and assemblies intended to provide the air
barrier functions are continuously connected and structurally capable of resisting applied loads. Historically, most failures of
Appendix A • Volume 2 Page 135
air barrier systems in buildings have been directly related to improper or insufficient connections between adjacent air barrier
materials, components and assemblies.
A-5.4.1.1.(7)Locations Where an Air Barrier System Is Not Required.
In Ontario, there are few buildings intended for human occupancy where the interior space is conditioned but an air barrier
system is not required. Any exemption from installing an air barrier system would depend on the level of interior
conditioning provided, the ventilation level, the protection provided for the building's occupants, and the tolerance of the
building's construction to the accumulation of condensation and potential precipitation ingress.
In some industrial buildings, limited conditioning (e.g., radiant heating) is provided, and ventilation levels are sufficient to
reduce the relative humidity to a level at which condensation will not accumulate to an unacceptable degree. Conversely,
some industrial buildings, due to the processes they contain, operate at very high temperatures and high ventilation levels. In
such cases, the building envelope may be maintained at temperatures required to avoid condensation. In both of these
examples, either the ventilation levels or protective means required in the work environment would protect the building's
occupants from unacceptable levels of pollutants.
A-5.4.1.2.(1)Low-Sloped Membrane Roof Assemblies.
For low-sloped membrane roof assemblies, CAN/ULC-S742, “Standard for Air Barrier Assemblies – Specification”,
provides pre-tested prescriptive solutions that have an air leakage rate not exceeding L/(s×m2). The air leakage rate of low-
sloped membrane roof assemblies not identified in CAN/ULC-S742 should be determined in accordance with ASTM D8052 /
D8052M, “Standard Test Method for Quantification of Air Leakage in Low-Sloped Membrane Roof Assemblies”.
A-5.4.1.2.(2)Air Barrier Assemblies Not Evaluated in Accordance with
CAN/ULC-S742.
Air barrier assemblies that have not been evaluated in accordance with CAN/ULC-S742, “Standard for Air Barrier
Assemblies – Specification”, must nevertheless provide the air leakage performance required for the selected
Performance Class. Field testing may be required to verify their performance.
Field assessment of the air leakage characteristics of both the primary air barrier assemblies and the connections between
adjacent air barrier assemblies can be a useful tool in establishing whether the acceptable minimum performance level is met.
Field testing of installed air barrier assemblies can be conducted in accordance with test standards such as
• ASTM E783, “Standard Test Method for Field Measurement of Air Leakage Through Installed Exterior Windows
and Doors”, and
• E1186, “Standard Practices for Air Leakage Site Detection in Building Envelopes and Air Barrier Systems”.
Even though some test standards are intended for specific types of air barrier assemblies (e.g., windows and doors), the test
methodology used to assess air leakage rates may be acceptable for use with other types of air barrier assemblies. However,
with this approach, it is important to establish rational acceptance criteria that reflect the test methodology and the types of air
barrier assemblies being tested.
Qualitative testing can be used to identify locations in air barrier assemblies where air leakage is occurring so that field
repairs can be made to improve the assembly's airtightness performance. ASTM E1186 provides guidance on a number
of approaches for identifying locations of air leakage, including the following:
• infrared scanning,
• smoke tracer observation,
• airflow measurement,
• sound detection,
• tracer gas detection, and
• liquid leak detection.
Each of these techniques has benefits and limitations, as described in the standard. The most suitable approach for a
particular situation is selected by the testing agency on the basis of their experience in relation to the type of construction
Page 136 Appendix A • Volume 2
being assessed and the weather conditions at the time of testing. Regardless of the approach selected, the testing of air
barrier assemblies must be properly coordinated with the construction process so that any air leaks identified can be
addressed without adversely affecting progress.
A-5.4.1.2.(4)Testing of Below-Grade Air Barrier Assemblies.
To ensure that they minimize the ingress of radon and other soil gases, below-grade air barrier assemblies in contact with
the ground can be tested in accordance with CAN/ULC-S742, “Standard for Air Barrier Assemblies – Specification,” using
the air leakage limit for Performance Class 1 or a more stringent limit. In such air barrier assemblies, as in all air barrier
assemblies, penetrations and junctions are the most likely locations for air leakage. These points of weakness must be
properly detailed and constructed to minimize the ingress of soil gases.
A-5.5.1.1.Required Resistance to Vapour Diffusion.
Resistance to vapour diffusion is required to reduce the likelihood of condensation within building assemblies, and the
consequent potential for material deterioration and fungal growth. Deterioration such as rot and corrosion can lead to the
failure of building components and connections, and interfere with the performance of building services. Some fungi can
have very serious effects on health.
In Ontario, relatively few buildings that are subject to temperature and vapour pressure differences would be constructed or
operated in such a manner that the control of vapour diffusion would not need to be addressed in their design. Assemblies
enclosing certain industrial spaces, as described in Appendix Note A-5.4.1.1.(7) for example, may be exempt.
For residential spaces and most other spaces that are conditioned for human occupancy, a means of vapour diffusion control
is generally agreed to be necessary. The questions in those cases pertain to the degree of control needed.
The word “minimize” is used in Sentence 5.5.1.1.(1) because not all moisture accumulation in an assembly need be of
concern. Incidental condensation is normal but should be sufficiently rare and in sufficiently limited quantities, and should
dry rapidly enough, to avoid material deterioration and the growth of mould or fungi. The following publications address the
effects of fungi on health:
• HC 2004, “Fungal Contamination in Public Buildings: Health Effects and Investigation Methods”
• “Guidelines on Assessment and Remediation of Fungi in Indoor Environments”, New York City Department of
Health and Mental Hygiene ) (NYCDH)
A-5.5.1.2.(1)Vapour Barrier Materials and Installation.
In the summer, many buildings are subject to conditions where the interior temperature is lower than the exterior temperature.
Vapour transfer during these periods is from the exterior to the interior. In general, in Canada, the duration of these periods
is sufficiently short, the driving forces are sufficiently low, and assemblies are constructed such that any accumulated
moisture will dissipate before deterioration will occur.
Buildings such as freezer plants, however, may operate for much of the year at temperatures that are below the ambient
exterior temperature. In these cases, the “warm” side of the assembly would be the exterior and a detailed analysis on an
annual basis is required.
Steady state heat transfer and vapour diffusion calculations may be used to determine acceptable permeance levels for the
vapour barrier and to identify appropriate positions for the vapour barrier within the building assembly.
A-5.6.1.1.Required Protection from Precipitation.
Windows, cast-in-place concrete walls, and metal and glass curtain wall systems are examples of components and assemblies
that, when properly designed and constructed, are expected to prevent the ingress of precipitation into a building. Assemblies
such as roofs and veneer walls consist of materials specifically intended to screen precipitation.
Components and assemblies separating interior conditioned space from the exterior are generally required to provide
protection from the ingress of precipitation. Components and assemblies separating interior unconditioned space from the
exterior may or may not be required to provide protection from the ingress of precipitation. Buildings such as stadia, parking
garages and some seasonally occupied buildings, for example, may not require complete protection from the ingress of
Appendix A • Volume 2 Page 137
precipitation. The degree of protection will depend to a large extent on the materials selected for the building elements that
will be exposed to precipitation.
The word “minimize” is used in Sentence 5.6.1.1.(1) because not all moisture ingress or accumulation in an assembly need be
of concern. The penetration of wind-driven rain past the cladding may not affect the long-term performance of the assembly,
provided the moisture dries out or is drained away before it initiates any deterioration of building materials. When the design
service life of a material or component is longer than the design service life of the overall assembly, taking into account the
expected exposure to moisture, initiating deterioration of the material should not be of concern. That is to say, provided the
material or component continues to provide the necessary level of performance for its intended service life and does not
adversely affect the service life of the assembly of which it is a part, the deterioration of the material or component is not an
issue.
A-5.6.1.2.(1)Ice Damming.
Water leakage through sloped roofs is often due to the formation of ice dams at the eaves, which can be limited by
controlling the transfer of heat to the roof through a combination of insulation and venting to dissipate heat. See
Clause 5.3.1.2.(1)(d).
A-5.6.1.2.(2)Vegetative Roofing Systems.
The integrity of some assemblies installed to provide the required protection from the ingress of precipitation in vegetative
roofing systems can be compromised due to an inadequate resistance to the penetration of plant roots and rhizomes.
Additional information on vegetative roofing systems and the performance of protective materials can be found in the
German Landscape Research, Development and Construction Society’s (FLL) “Guideline for the Planning, Execution and
Upkeep of Green-Roof Sites” and in the National Roofing Contractors Association’s Vegetative Roof Systems Manual.
A-5.6.2.1.Sealing and Drainage.
A number of different design solutions can provide an environmental separator with the minimum performance level
necessary to effectively control environmental and structural loads and their effects. An appropriate solution is
selected on the basis of the applied load characteristics, the performance achieved by the solution, and its durability
over the design service life. It is incumbent on the designer to balance the performance of a particular design solution
against the required performance level, the risk of failure, and the consequences of failure for the building and its
users.
Article 5.6.2.1. recognizes that acceptable solutions can use various strategies and single or multiple elements within the
design to control precipitation. However, as indicated by research and the documentation of failures, some of these
solutions are more effective than others.
One solution—a face-sealed assembly—relies on a continuous watertight surface on the outside of a building to
control all precipitation over the life of the building; there is no redundancy in this design. The watertight surface can
be difficult to both design and construct, and its long-term durability depends on proper preventive maintenance over
its service life. This solution has a well-documented history of unsatisfactory performance in most regions of Canada.
A solution with redundancy in its design provides more effective and reliable resistance to water penetration. For
example, in a rainscreen assembly, multiple water-resistive layers are combined with means to drain any water that
has penetrated the outer layer and means to redirect this water to the exterior before it can affect moisture-sensitive
materials within the assembly. Another solution—a mass wall assembly—accumulates and stores moisture, which is
re-released to the exterior when conditions allow. Depending on the solution selected, means to facilitate the drying of
materials may be incorporated in the assembly.
In selecting an acceptable solution for precipitation control, it is important to consider the structural and environmental loads
that are referenced in Subsection 5.1.4. The resistance provided by the design solution must exceed these loads and their
effects. The greater the intensity of the load, the higher the performance level required to provide the necessary resistance
and an acceptable level of risk. Design considerations that should be addressed include the following:
• intended building use(s),
• building exposure during service life (height, orientation and surrounding terrain),
Page 138 Appendix A • Volume 2
• building exposure during construction,
• current and future local climate characteristics affecting wetting and drying, including
– wind loads,
– precipitation loads (including wind-driven precipitation loads),
– relative humidity,
– temperature variations, and
– solar exposure,
• imposed load intensity, both in isolation and in combination (type, number, magnitude, frequency and duration),
• material types and moisture tolerances,
• resistance to the mechanisms of deterioration,
• effects of deformations, displacements and deflections of the building structure, and of materials,
components and assemblies,
• constructability of materials, components and assemblies,
• expected construction tolerances,
• level of maintenance required to maintain resistance to loads and deterioration,
• intended service life of materials, components and assemblies, and
• reliability of materials, components and assemblies.
All the materials in an environmental separator must be able to resist the mechanisms of deterioration that are expected to
occur over the design service life of the separator. For example, with respect to deterioration caused by moisture, a material
used in a design must not be exposed to moisture in sufficient quantity and/or for sufficient length of time to reduce its
ability to perform its required function(s) to a level below the required performance level. This concern is particularly
important for materials that are known to be susceptible to moisture deterioration.
An environmental separator must also be designed to be suitably resistant to failure caused by
• uncertainty or variation in load intensity,
• uncertainty in the effects of loads on materials, components and assemblies,
• uncertainty in the predicted service lives of materials, components and assemblies, and
• construction deficiencies that can reasonably be anticipated.
The building structure and the environmental separator are mutually dependent in managing precipitation. The choice of
materials for the building structure and the structural support/backing for the environmental separator can influence the
choice of materials, components and assemblies for the environmental separator. Materials, components and assemblies
with higher performance levels may be required for the environmental separator where the building structure and the
structural support/backing have lower material strengths, undergo higher in-service movements (e.g., shrinkage or
deflection), or have lower resistance to deterioration.
The design and construction of details at penetrations, at joints and junctions between assemblies, and at transitions between
planes are of critical importance to the long-term performance and durability of the environmental separator. Designers
should provide sufficient detail on drawings to illustrate how the design solution for precipitation control is to be integrated
into the building.
A-5.7.Protection from Interior Sources of Water.
Protection similar to that prescribed in Section 5.7. may be required where interior assemblies are in contact with water (such
as site-built showers, steam rooms, swimming pool areas) and where adjacent interior spaces need to be protected from the
transfer of water through these assemblies.
A-5.7.1.2.(2)Drainage.
Water should be directed away from the building and, ultimately, to a municipal drainage system, drainage ditch, swale, or
other acceptable water management means. This can be accomplished by setting the building grade higher than the
surrounding grades, by sloping the grade away from the building, by installing a surface water drainage system, or by a
combination of these approaches. The chosen approach should follow generally accepted guidelines, such as the Rational
Method of Stormwater Design by David B. Thompson, or other design methods acceptable to the authority having
jurisdiction.
Appendix A • Volume 2 Page 139
A-5.7.3.3.(1)(a)Imperfections.
Examples of imperfections include shrinkage cracks, air holes, honeycombing, form-tie cone holes, and form joint ridges.
A-5.7.3.4.(1)Dampproofing.
Dampproofing refers to the application of a material or materials to an environmental separation assembly to protect it and
the interior space against the transfer of moisture due to the mechanisms of water vapour transmission, capillary action and
pressure differences other than hydrostatic pressure.
A dampproofed assembly should be designed such that it can provide short-term resistance to the ingress of water due to
occasional hydrostatic pressure from ground water.
A-5.8.Required Protection from Noise.
Section 5.8. applies to the separation of dwelling units from other dwelling units and from spaces where noise may be
generated with regard to sound transmission irrespective of Clause 5.1.2.1.(1)(b), which deals with the separation of
dissimilar environments. It is understood that, at any time, there is the potential for sound levels to be quite different in
adjoining dwelling units.
A-5.8.1.2.Using ASTC in Lieu of STC.
A designer may choose to use an ASTC rating of equal or higher numerical value than the required STC to show compliance
where STC ratings are required.
An ASTC measurement or calculation will always yield a value equal to or lower than the STC for the same configuration, as
the ASTC includes flanking transmission.
A-5.8.1.4.Methods of Calculating ASTC.
The technical concepts, terminology, and calculation procedures relating to the detailed and simplified ASTC calculation
methods are discussed in detail, with numerous worked examples, in the NRC publication entitled “Guide to Calculating
Airborne Sound Transmission in Buildings”. This Guide includes references to readily available sources of pertinent data.
For many common constructions, the calculations required by Article 5.8.1.4. can be performed using software tools, such as
soundPATHS, which is available on NRC’s website.
The simplified calculation method may not always identify the prominent flanking paths. Furthermore, it corresponds more
closely with the results of the detailed calculation method where the separating assembly and the flanking constructions are
both constructed according to the same method, i.e. either both are lightweight construction (steel or wood framing) or both
are heavyweight construction (masonry or concrete).
A-5.8.1.4.(4)(b)Assemblies that Behave Like Homogeneous Panels.
Examples of assemblies that behave like homogeneous panels include cast-in-place concrete, precast concrete, precast
hollow-core concrete, concrete block masonry, and mass timber panels. For the purpose of calculating the ASTC rating for
construction using mass timber panel walls or floor assemblies in accordance with the detailed method described in Sentence
5.8.1.4.(4), a mass timber panel behaves as a homogeneous panel, notwithstanding that it has an average structural loss factor
greater than 0.03. Further information on the calculation of the ASTC rating for mass timber panel assemblies can be found
in the NRC publication entitled “Guide to Calculating Airborne Sound Transmission in Buildings”.
A-5.9.1.1.(1)Selection of Materials and Components and Compliance with
Referenced Standards.
Note that Sentence 5.9.1.1.(1) is drafted in such a way that the selection of materials and components is not limited to those
traditionally recognized as serving particular functions or those for which a standard is identified in Table 5.9.1.1. This
approach permits more flexibility than is provided by similar requirements in Part 9. As long as the selected material meets
the performance requirements stated elsewhere in Part 5, the material may be used to serve the required function.
Page 140 Appendix A • Volume 2
However, where the selected material or component, or its installation, falls within the scope of any of the standards listed in
Table 5.9.1.1., the material, component or installation must comply with that standard. For example, if some resistance to
heat transfer is required between two interior spaces and standard partition construction will provide the necessary resistance,
the installation of one of the “thermal insulation” materials identified in the standard list is not required. If, on the other
hand, one decides to install glass fibre insulation, the material must conform to CAN/ULC-S702.1, “Standard for Mineral
Fibre Thermal Insulation for Buildings, Part 1: Material Specification”.
A-Table 5.9.1.1. Selection and Installation of Sealants.
Analysis of many sealant joint failures indicates that the majority of failures can be attributed to improper joint preparation
and deficient installation of the sealant and various joint components. The following ASTM guidelines describe several
aspects that should be considered when applying sealants in unprotected environments to achieve a durable application:
• ASTM C 1193, “Standard Specification for Use of Joint Sealants”,
• ASTM C 1472, “Standard Guide for Calculating Movement and Other Effects When Establishing Sealant Joint
Width”.
The sealant manufacturer’s literature should always be consulted for recommended procedures and materials.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
A-5.9.2.1.(3)Airtightness and Watertightness of Wired Glass Windows.
Fixed wired glass assemblies are sometimes permitted as closures in vertical fire separations. The airtightness and
watertightness requirements are waived for these windows when used in such an application, in recognition of the fact that
the availability of assemblies that meet both the requirements of the window standards and the requirements for fire
resistance may be limited. However, control of air and water leakage should not be ignored: measures should be taken to
attempt to comply with applicable requirements.
A-5.9.2.2.Manufactured Windows, Doors and Skylights.
Design Values
CSA A440S1, “Canadian Supplement to AAMA/WDMA/CSA 101/I.S.2/A440-17, NAFS – North American Fenestration
Standard/Specification for Windows, Doors, and Skylights”, requires that the individual performance levels achieved by
the product for structural resistance, water penetration resistance and air leakage resistance be reported on the product’s
performance label.
Storm Doors and Windows
Where storm doors and storm windows are not incorporated in a rated window or door assembly, they should be designed
and constructed to comply with the applicable requirements of Part 5 regarding such properties as appropriate air leakage
and structural loads.
Forced Entry Test
Even though the performance label on rated windows, doors and skylights does not explicitly indicate that the product has
passed the forced entry resistance test, products are required to pass this test in order to be rated.
A-5.9.2.3.(1)Installation and Field Testing of Windows, Doors and Skylights.
Installation
The installation details of windows, doors, skylights and their components must be appropriately designed and implemented
for the building envelope assembly to perform acceptably overall. The proper design of the installation details provides the
information necessary to integrate the structure and air, vapour and moisture barrier functions of windows, doors and
skylights into the overall design of the building envelope assembly. Construction should be carried out in accordance with
these details to achieve an appropriate level of long-term performance. Further guidance on installation detailing can be
found in CAN/CSA-A440.4, “Window, Door, and Skylight Installation”.
Appendix A • Volume 2 Page 141
Field Testing
It is recommended that the performance of installed windows, doors and skylights be field tested early in the envelope
construction phase so that any discontinuities can be readily identified and corrected before construction of the building
envelope assembly is completed. Additional field testing during subsequent construction phases to monitor installation
consistency is also recommended. Field test procedures should be carried out in accordance with test standards such as
ASTM E783, “Standard Test Method for Field Measurement of Air Leakage Through Installed Exterior Windows and
Doors”, and ASTM E1105, “Standard Test Method for Field Determination of Water Penetration of Installed Exterior
Windows, Skylights, Doors, and Curtain Walls, by Uniform or Cyclic Static Air Pressure Difference”. Further guidance can
be found in Annex D of CAN/CSA-A440.4, “Window, Door, and Skylight Installation”, however, the performance
requirements developed in AAMA/WDMA/CSA 101/I.S.2/A440, “NAFS – North American Fenestration Standard/
Specification for Windows, Doors, and Skylights”, should be used rather than the industry performance data values listed in
CAN/CSA-A440.4.
A-5.9.2.4.(3)Heat Transfer Through Fire-Rated Glazed Assemblies.
Thermal bridging through fire-rated glazed assemblies should not be ignored; measures should be taken to minimize
condensation consistent with the intent of Sentence 5.9.2.4.(2).
5.9.4.1.(1) Exterior Insulation Finish Systems (EIFS).
A-5.9.3.Testing Standards for Other Fenestration Assemblies.
Subsection 5.10.4. references ASTM test methods. The following AAMA standards can also be used to evaluate the
performance characteristics of other fenestration assemblies:
• AAMA 501, “Test for Exterior Walls”,
• AAMA 501.1, “Water Penetration of Windows, Curtain Walls and Doors Using Dynamic Pressure”,
• AAMA 501.2, “Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain
Walls, and Sloped Glazing Systems”,
• AAMA 501.4, “Recommended Static Test Method for Evaluating Curtain Wall and Storefront Systems Subjected to
Seismic and Wind Induced Interstory Drifts”,
• AAMA 501.5, “Thermal Cycling of Exterior Walls”, and
• AAMA 501.6, “Recommended Dynamic Test Method for Determining The Seismic Drift Causing Glass Fallout
From A Wall System”.
A-5.9.3.1.(1)Terminology for Other Fenestration Assemblies.
Curtain Wall
A curtain wall is considered to be a continuous wall cladding assembly (which may include fenestration and opaque
portions) that is hung away from the edge of the primary floor structure. Curtain wall assemblies do not generally support
vertical loads other than their own weight. Anchorage is typically provided by anchors that connect back to the floor
structure. Curtain wall assemblies can be either “stick built,” meaning each main unit is assembled on-site, or a “unitized”
system, meaning factory-assembled main units are installed and connected together on-site.
Window Wall
A window wall is considered to be a wall cladding assembly (which may include fenestration and opaque portions) that
spans from the top of a primary floor structure to the underside of the next higher primary floor structure. Window wall
assemblies do not generally support vertical loads other than their own weight. Primary provision for anchorage occurs at
head and sill connections with the adjoining floor structure. Window wall assemblies may include separate or integral
floor edge covers.
Page 142 Appendix A • Volume 2
Storefront
A storefront is considered to be a non-residential assembly (which may include fenestration and opaque portions)
consisting of one or more elements that could include doors, windows and curtain wall framing. Storefronts do not
generally support vertical loads other than their own weight. Storefront profiles are typically narrow, rectilinear framing
members that hold a combination of pocket glazing and applied glazing stops to securely retain the infills. Vertical
framing members typically span the height of one floor or are retained within a structural punched opening.
Storefront assemblies are designed/selected to take into account the anticipated service and exposure conditions, which
may be different than for other portions of the building.
Glazed Architectural Structures
Glazed architectural structures are considered glazing assemblies that are supported in a non-traditional manner, such as
corner-clamped, point-supported, linear-supported and edge-clamped glazing. Structural support systems can include, but
are not limited to, tension cables, tension rods, steel and glass. Glazed architectural structures do not generally support
vertical loads other than their own weight. These assemblies are designed/selected to take into account the anticipated
service and exposure conditions, which may be different than those for other portions of the building.
Skylights that are not covered by AAMA/WDMA/CSA 101/I.S.2/A440, “NAFS – North American Fenestration
Standard/Specification for Windows, Doors, and Skylights,” are considered glazed architectural structures.
A-5.9.3.2.(1)Structural Loads and Environmental Loads.
The applicable laboratory test method for demonstrating adequate structural performance of other fenestration assemblies is
ASTM E330 / E330M, “Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and
Curtain Walls by Uniform Static Air Pressure Difference”.
A-5.9.3.3.(1)Resistance to Condensation.
Notwithstanding that other fenestration assemblies are not fully covered under the testing scope of CSA A440.2,
“Fenestration Energy Performance”, the test method described therein can be used to evaluate their resistance to
condensation, with technical modifications to accommodate differences in the size and configuration of the specimen. It is
also common practice to use one cold cycle of AAMA 501.5, “Thermal Cycling of Exterior Walls”, to assess the potential for
condensation. Both methods can be used for mock-ups in laboratory performance evaluations, however, only the test method
in CSA A440.2 should be used if a Temperature Index is required. In most cases, the project specification documents
establish the hygrothermal conditions (i.e., exterior temperature, interior temperature, interior relative humidity) for which the
potential for condensation should be minimized. Under these conditions, the aforementioned test methods can be used to aid
in the selection of the appropriate system performance to minimize the potential for interior surface condensation. In all
cases, care should be taken in the construction and configuration of the specimen, as these parameters may have an impact on
its thermal performance and resistance to condensation. These parameters may include, without limitation, interior wall
construction and finishes, heating systems, ventilation systems, etc., to simulate the actual in-service conditions as closely as
practicable.
A-5.9.3.4.(2)Air Leakage.
Air Leakage Rate and Test Pressure
A lower air leakage rate and/or higher differential test pressure can be selected for specific applications of other
fenestration assemblies where tight control of airflow is required to prevent interstitial condensation (e.g., in concealed
spaces), improve thermal comfort (e.g., in hospitals, seniors’ residences), or prevent the migration of airborne
contaminants (e.g., in food and drug research, manufacturing applications, biological laboratories). It is typical of other
fenestration assemblies to be used as the sole building envelope component; where this is the case, a correspondingly
higher degree of airtightness may be required.
In addition, higher test pressure differentials can be used to evaluate assemblies with low air leakage, such as non-
operable or fixed fenestration systems whose air leakage rates are not easily measurable at the lower standard pressure
differentials.
Appendix A • Volume 2 Page 143
Standard Test Methods
The applicable laboratory test method for determining the rate of air leakage is ASTM E 283, “Standard Test Method for
Determining Rate of Air Leakage Through Exterior Windows, Curtain Walls, and Doors Under Specified Pressure
Differences Across the Specimen”. If field testing for air leakage is to be conducted, the applicable test method is ASTM
E 783, “Standard Test Method for Field Measurement of Air Leakage Through Installed Exterior Windows and Doors”.
A-5.9.3.4.(3)Systems Excluded from Air Leakage Requirements.
The systems listed in Sentence 5.9.3.4.(3) perform different functions than other fenestration assemblies and are therefore
exempted from complying with the air leakage requirements.
A-5.9.3.5.(2)Standard Test Methods.
The applicable laboratory test method for determining the water penetration resistance of curtain walls and storefront
assemblies is ASTM E331, “Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and
Curtain Walls by Uniform Static Air Pressure Difference”. The applicable laboratory test method for window wall
assemblies is either ASTM E331 or ASTM E547, “Standard Test Method for Water Penetration of Exterior Windows,
Skylights, Doors, and Curtain Walls by Cyclic Static Air Pressure Difference”.
If field testing for water penetration is to be conducted, the applicable test method is ASTM E 1105, “Standard Test Method
for Field Determination of Water Penetration of Installed Exterior Windows, Skylights, Doors, and Curtain Walls, by
Uniform or Cyclic Static Air Pressure Difference”.
A-5.9.3.5.(3)Water Penetration.
Notwithstanding that other fenestration assemblies are not covered under the testing scope of CSA A440S1, “Canadian
Supplement to AAMA/WDMA/CSA 101/I.S.2/A440-17, “NAFS – North American Fenestration Standard/Specification for
Windows, Doors, and Skylights”, they must be tested at the driving rain wind pressure calculated in accordance with the
procedure described therein.
A-5.9.3.5.(4)Systems Excluded from Water Penetration Requirements.
The systems listed in Sentence 5.9.3.5.(4) perform different functions than other fenestration assemblies and are therefore
exempted from complying with the water penetration requirements.
A-5.9.4.1.(1)Exterior Insulation Finish Systems (EIFS).
The reference to CAN/ULC-S716.1, “Standard for Exterior Insulation and Finish Systems (EIFS) – Materials and Systems”,
in Clause 5.9.4.1.(1)(b) does not preclude the use of other component materials that may also meet the intent of the Code.
For example, using mineral-fibre insulation in lieu of other rigid insulation types, mechanical fastening methods for the
insulation component in lieu of adhesive, or a type of water-resistive barrier other than a liquid-applied water-resistive barrier
could be acceptable.
The following two companion standards facilitate the application of and conformance with CAN/ULC-S716.1:
• CAN/ULC-S716.2, “Standard for Exterior Insulation and Finish Systems (EIFS) – Installation of EIFS Components
and Water Resistive Barrier”, and
• CAN/ULC-S716.3, “Standard for Exterior Insulation and Finish System (EIFS) – Design Application”.
Additional information on EIFS design and installation can be found in the EIFS Council of Canada’s “EIFS Practice
Manual” and the manufacturer’s literature.
EIFS Selection
CAN/ULC-S716.1 provides minimum performance criteria for EIFS materials and systems that are tested under specific
laboratory test protocols identified in the standard. However, compliance with this standard does not ensure that a system
is appropriate for all projects. When selecting an EIFS product, designers should consider all relevant criteria—not only
those covered by the tests in CAN/ULC-S716.1—including, but not limited to,
Page 144 Appendix A • Volume 2
• building exposure
• local climate characteristics (wind, precipitation, temperature variations, solar exposure)
• intended building use
• intended resistance to damage and deterioration
• construction tolerances
• constructability
Design and Construction of EIFS Drainage Cavity
The drainage capacity and thermal performance of the EIFS assembly can be affected by the dimensions and
configuration of the EIFS drainage cavity.
EIFS are installed over other building materials such as sheathing and primary structural components, which have various
construction installation tolerances. Designers should take into consideration the cumulative effects of construction
tolerances and sequencing when specifying the drainage method and the cavity dimensions and configuration in order to
ensure adequate drainage.
Designers should also take into account the impact of air movement, which varies depending on cavity size and the extent
of venting, on the EIFS’ thermal performance when reviewing the overall thermal performance of the building envelope.
ASTM C 1363, “Standard Test Method for Thermal Performance of Building Materials and Envelope Assemblies by
Means of a Hot Box Apparatus”, presents one method for assessing the thermal performance of assemblies.
Understand any provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Try BUILDAiD Beta
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.