Full text of Section 6.7 (Piping Systems) — Division B, Part 6 (Heating, Ventilating and Air-Conditioning) of the 2024 Ontario Building Code, with every article reproduced below.
6.7.1.1.Piping Materials and Installation permalink →
(1) Piping shall be made from materials designed to withstand the effects of temperatures and pressures that may occur
in the system. (See Articles 3.1.5.19., 3.1.9.1., 9.10.9.6. and 9.10.9.7. for fire safety requirements.)
(2) Every pipe used in a heating or air-conditioning system shall be installed to allow for expansion and contraction due
to temperature changes.
(3) Supports and anchors for piping in a heating or air-conditioning system shall be designed and installed to ensure that
undue stress is not placed on the supporting structure.
(1) Clearances between combustible material and bare pipes carrying steam or hot water shall conform to Table 6.7.1.2.
Table 6.7.1.2.
Clearance Between Steam or Hot Water Pipes and Combustible Material
Forming Part of Article 6.4.2.1., Sentence 6.4.3.1.(2) and Article 6.7.1..2.
Steam or Water Temperature, °C Minimum Clearance, mm
Up to 95 No clearance
above 95 to 120 15
above 120 25
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
6.7.1.3.Surface Temperature permalink →
(1) The exposed surface temperature of a steam or hot water radiator shall not exceed 70°C unless precautions are taken
to prevent human contact. (See Note A-6.5.1.1.(3))
(1) Where a pipe carrying steam or hot water at a temperature above 120°C passes through a combustible floor, ceiling
or wall, the construction shall be protected by a sleeve of metal or other noncombustible material not less than 50 mm
larger in diameter than the pipe.
6.7.1.5.Piping in Shafts permalink →
(1) Where piping for heating or air-conditioning systems is enclosed in a shaft, the requirements of Article 3.6.3.1. for
shafts shall apply.
(1) Service pipes passing through a storage bin for solid fuel shall be protected or so located as to avoid damage to the
pipes.
(2) Except for fuel-thawing pipes, every pipe designed to operate at a temperature of 50°C or above shall be located
where fuel cannot be stored in contact with it.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.