9.9.8.5.Exiting Through a Lobby
(1) Not more than one exit from a floor area is permitted to lead through a lobby.
(2) The lobby referred to in Sentence (1) shall be not more than 4.5 m above grade, and the path of travel through the
lobby to the outdoors shall not exceed 15 m.
(3) The lobby referred to in Sentence (1) shall conform in all respects to the requirements for exits, except that rooms
other than service rooms, storage rooms and rooms of residential or industrial occupancy are permitted to open directly
onto such lobby.
(3.1) Except as provided in Sentence (6), an exit is permitted to lead through a lobby referred to in Sentence (1) provided
the lobby is not located within an interconnected floor space other than as described in Sentence 3.2.8.2.(6).
(4) Where the lobby referred to in Sentence (1) and adjacent occupancies that are permitted to open into the lobby are
sprinklered, the fire separation between such occupancies and the lobby need not have a fire-resistance rating. (See Note
A-3.4.4.2.(2)(e))
(5) Passenger elevators are permitted to open onto the lobby referred to in Sentence (1) provided the elevator doors are
designed to remain closed except while loading and unloading passengers.
(6) An exit that serves a hotel is permitted to lead through a lobby referred to in Sentence (1) provided the lobby is not
located within an interconnected floor space.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.