9.9.8.1.Measurement of Travel Distance
(1) Except as provided in Sentences (2) and (3), for the purposes of this Subsection, travel distance means the distance
from any point in the floor area to an exit measured along the path of exit travel.
(2) Where a room or suite is separated from the remainder of the floor area by a fire separation having a fire-resistance
rating of at least 45 min or, in a sprinklered building, by a fire separation which is not required to have a fire-resistance
rating, the travel distance may be measured from an egress door of the room or suite to the nearest exit.
(3) Where a public corridor is not less than 9 m wide and conforms to Subclauses 3.4.2.5.(1)(d)(i) to (d)(iv), the travel
distance may be determined in accordance with those Subclauses.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.