9.9.6.1.Obstructions by Doors
(1) Except as provided in Sentence (4), swinging doors in their swing shall conform to Sentences (2) and (3)
(a) at exit doors,
(b) at doors that open into or are located within a public corridor, and
(c) at doors that open into or are located within another facility that provides access to exit from a suite.
(2) When fully open, doors described in Sentence (1) shall not decrease the required exit width by more than
(a) 100 mm in exit corridors, and
(b) 50 mm for other exit facilities.
(3) The swing of doors described in Sentence (1) shall not reduce the width of the path of travel to less than
(a) the required exit width in exit corridors and passageways, and
(b) 750 mm on exit stairs or landings.
(4) Doors serving a single dwelling unit or a house with a secondary suite need not comply with Sentences (2) and (3).
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.