9.9.5.8.Service Rooms
(1) Service rooms containing equipment subject to possible explosion, such as boilers designed to operate at a pressure
in excess of 100 kPa, and certain types of refrigerating and transformer equipment, shall not be located under required
exits.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.