9.9.4.2.Fire Separation for Exits
(1) Except as provided in Sentence (5) and Article 9.9.8.5., every exit other than an exit doorway shall be separated
from each adjacent floor area or from another exit by a fire separation having a fire-resistance rating not less than that
required for the floor assembly above the floor area.
(2) Where there is no floor assembly above, the fire-resistance rating required in Sentence (1) shall not be less than that
required by Subsection 9.10.8. for the floor assembly below, but in no case shall the fire-resistance rating be less than
45 min.
(3) A fire separation common to 2 exits shall be smoke-tight and not be pierced by doorways, duct work, piping or any
other opening that may affect the continuity of the separation.
(4) A fire separation that separates an exit from the remainder of the building shall have no openings except those for
electrical wiring, noncombustible conduit and noncombustible piping that serve only the exit, and for standpipes, sprinkler
piping, exit doorways and wired glass and glass block permitted in Article 9.9.4.3.
(5) The requirements in Sentence (1) do not apply to an exterior exit passageway provided the passageway has at least
50% of its exterior sides open to the outdoors and is served by an exit stair at each end of the passageway.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.