PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.9.2.3.Elevators, Slide Escapes and Windows as Means of Egress
(1) Elevators, slide escapes or windows shall not be considered as part of a required means of egress.
(2) Except for floor areas of mercantile occupancy, casement windows not less than 1 060 mm high, 560 mm wide,
with a sill height not more than 900 mm above the inside floor, are permitted to be considered part of a required means of
egress to provide access to fire escapes, when fire escapes are permitted.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.