PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code

9.9.2.1.Types of Exits

(1) Except as otherwise provided in this Section, an exit from any floor area shall be one of the following used singly or in combination: (a) an exterior doorway, (b) an exterior passageway, (c) an exterior ramp, (d) an exterior stairway, (e) a fire escape, (f) a horizontal exit, (g) an interior passageway, (h) an interior ramp, or (i) an interior stairway. (2) Fire escapes shall only be used as exits on existing buildings and shall be designed and installed in conformance with Subsection 3.4.7. (2.1) Fire escapes shall not be installed on any new building. (3) Where a horizontal exit is used, it shall conform to Sentence 3.4.1.6.(1) and Article 3.4.6.10.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.