9.8.8.4.Guards for Floors and Ramps in Garages
(1) Except for floors of garages referred to in Section 9.35., where garage floors or ramps are 600 mm or more above
the adjacent ground or floor level, every opening through a garage floor and the perimeter of floors and ramps that have
no exterior walls shall be provided with
(a) a continuous curb not less than 140 mm in height, and
(b) a guard not less than 1 070 mm above the floor level.
(2) Vehicle guardrails shall be designed and constructed to withstand the loading values stipulated in Sentence
4.1.5.15.(1). (See Note A-4.1.5.14. and 4.1.5.15.(1))
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.