9.5.5.3.Doors to Bathrooms
(1) Where a barrier-free path of travel conforming to Section 3.8. is provided into a suite of residential occupancy and
where a bathroom within the suite is at the level of the suite entrance door, the doorway to such bathroom and to each
bedroom at the same level as such bathroom shall have, when the door is in the open position, a clear width of not less
than,
(a) 760 mm where the door is served by a corridor or space not less than 1 060 mm wide, and
(b) 810 mm where the door is served by a corridor or space less than 1 060 mm wide.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.