PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.34.1.5.Wiring and Cables
(1) Except for dwelling units and except as required in Sentence (2), optical fibre cables and electrical wires and cables
installed in buildings permitted to be of combustible construction shall
(a) not convey flame or continue to burn for more than 1 min when tested in conformance with the Vertical Flame Test
in Clause 4.11.1. of CSA C22.2 No. 0.3, “Test Methods for Electrical Wires and Cables,” (FT1 Rating), or
(b) be located in
(i) totally enclosed noncombustible raceways, (See Note A-3.1.4.3.(1)(b)(i))
(ii) masonry walls,
(iii) concrete slabs, or
(iv) totally enclosed non metallic raceways conforming to Clause 3.1.5.23.(1)(b).
(2) Where a concealed space in a floor or ceiling assembly is used as a plenum, electrical wires and cables within the
plenum shall conform to Clause 3.6.4.3.(1)(a).
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.