9.33.6.8.Clearances of Ducts and Plenums
(1) Reserved.
(2) Where the plenum clearance is 75 mm or less, the clearance between a supply duct and combustible material shall
(a) be equal to the required plenum clearance within 450 mm of the plenum, and
(b) be not less than 12 mm at a distance of 450 mm or more from the plenum, except that this clearance may be reduced
to zero beyond a bend or offset in the duct sufficiently large to shield the remainder of the supply duct from direct
radiation from the furnace heat exchanger.
(See Note A-3.6.5.6.(2))
(3) Where the plenum clearance is more than 75 mm but not more than 150 mm, the clearance between a supply duct
and combustible material shall be
(a) equal to the required plenum clearance within a horizontal distance of 1.8 m of the plenum, and
(b) not less than 12 mm at a horizontal distance of 1.8 m or more from the plenum, except that this distance may be
reduced to zero beyond a bend or offset in the duct sufficiently large to shield the remainder of the duct from direct
radiation from the furnace heat exchanger.
(See Note A-3.6.5.6.(3))
(4) Where the plenum clearance is more than 150 mm, the clearance between a supply duct and combustible material
shall be
(a) equal to the required plenum clearance within a horizontal distance of 1 m of the plenum,
(b) not less than 150 mm within a horizontal distance between 1 m and 1.8 m from the plenum, and
(c) not less than 25 mm at a horizontal distance of 1.8 m or more from the plenum, except that this distance may be
reduced to 8 mm beyond a bend or offset in the duct sufficiently large to shield the remainder of the supply duct
from direct radiation from the furnace heat exchanger.
(See Note A-3.6.5.6.(4))
(5) Where a register is installed in a floor directly over a pipeless furnace, a double-walled register box with not less
than 100 mm between walls, or a register box with the warm-air passage completely surrounded by the cold-air passage,
shall be permitted in lieu of the clearances listed in Sentences (2) to (4).
← Previous9.33.6.7. Installation of Ducts and PlenumsNext →9.33.6.9. Adjustable Dampers and Balance Stops
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.