9.33.6.14A.Exhaust Ducts and Outlets
(1) Where an exhaust duct passes through or is adjacent to unheated space, the duct shall be insulated to prevent
moisture or condensation in the duct.
(2) Exhaust outlets shall be designed to prevent back draft under wind conditions.
(3) Exhaust ducts directly connected to laundry drying equipment shall be independent of other exhaust ducts.
(4) Exhaust systems shall discharge directly to the outdoors.
← Previous9.33.6.14. Filters and Odour Removal EquipmentNext →9.33.7.1. Recessed Radiators and Convectors
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.