PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code

9.29.5.5.Length of Fasteners

(1) The length of fasteners for gypsum board shall conform to Table 9.29.5.5., except that lesser depths of penetration are permitted for assemblies required to have a fire-resistance rating provided it can be shown, on the basis of fire tests, that such depths are adequate for the required rating Table 9.29.5.5. Fastener Penetration into Wood Supports Forming Part of Sentence 9.29.5.5.(1) Minimum Penetration, mm Required Fire-Resistance Rating Walls Ceilings of Assembly Nails Screws Nails Screws Not required 20 15 20 15 45 min 20 20 30 30 1h 20 20 45 45 1.5 h 20 20 60 60

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.