9.27.14.1.Application
(1) Except as provided in Sentence (2), this Subsection applies to exterior insulation finish systems (EIFS) that
(a) are covered in the scope of CAN/ULC-S716.1, “Standard for Exterior Insulation and Finish Systems (EIFS) –
Materials and Systems,” and
(b) have a geometrically defined drainage cavity with a minimum cavity depth of 6 mm and an open area equal to not
less than 13% of the area of a full-size EIFS panel.
(See Note A-9.27.14.1.(1))
(2) EIFS that are not covered by Sentence (1) shall comply with Part 5.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.