PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.24.3.7.Openings for Fire Dampers
(1) Openings for fire dampers in non-loadbearing fire separations required to have a fire-resistance rating shall be
framed with double studs on each side of the opening.
(2) The sill and header for openings described in Sentence (1) shall consist of a runner track with right angle bends
made on each end so as to extend 300 mm above the header or below the sill and fastened to the studs.
e1 (3) The openings described in Sentence (1) shall be lined with a layer of gypsum board not less than 12.7 mm thick
fastened to stud and runner webs.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.