9.23.9.9.Cantilevered Floor Joists
(1) Floor joists supporting roof loads shall not be cantilevered more than 400 mm beyond their supports where 38 mm
by 184 mm joists are used and not more than 600 mm beyond their supports where 38 mm by 235 mm or larger joists are
used.
(2) The cantilevered portions referred to in Sentence (1) shall not support floor loads from other storeys unless
calculations are provided to show that the design resistances of the cantilevered joists are not exceeded.
(3) Where cantilevered floor joists described in Sentences (1) and (2) are at right angles to the main floor joists, the tail
joists in the cantilevered portion shall extend inward away from the cantilever support a distance equal to not less than 6
times the length of the cantilever, and shall be end nailed to an interior doubled header joist in conformance with Table
9.23.3.4.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.