PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.23.9.4.Strapping, Bridging, Furring and Ceilings in Span Tables 9.23.4.2.-A and
9.23.4.2.-B (See Note A-9.23.4.2.(2))
(1) Except as permitted by Sentence (5), where strapping is specified in Span Table 9.23.4.2.-A, it shall be
(a) not less than 19 mm by 64 mm, nailed to the underside of floor joists,
(b) located not more than 2 100 mm from each support or other rows of strapping, and
(c) fastened at each end to a sill or header.
(2) Where bridging is specified in Span Table 9.23.4.2.-A, it shall consist of not less than 19 mm by 64 mm or 38 mm
by 38 mm cross bridging located not more than 2 100 mm from each support or other rows of bridging.
(3) Where bridging and strapping are specified in Span Table 9.23.4.2.-A,
(a) bridging shall
(i) comply with Sentence (2), or
(ii) consist of 38 mm solid blocking located not more than 2 100 mm from each support or other rows of bridging
and securely fastened between the joists, and
(b) except as provided in Sentence (5), strapping shall comply with Sentence (1) and be installed under the bridging.
(4) Bridging specified in Span Table 9.23.4.2.-B shall consist of
(a) bridging as described in Sentence (2), or
(b) 38 mm solid blocking located not more than 2 100 mm from each support or other rows of bridging and securely
fastened between the joists.
(5) Strapping described in Sentence (1) and Clause (3)(b) is not required where
(a) furring strips complying with Table 9.29.3.1. are fastened directly to the joists, or
(b) a panel-type ceiling finish complying with Subsection 9.29.5., 9.29.6., 9.29.7., 9.29.8., or 9.29.9. is attached directly
to the joists.
(6) Where a ceiling attached to wood furring is specified in Span Table 9.23.4.2.-B,
(a) the ceiling finish shall consist of gypsum board, plywood or OSB not less than 12.7 mm thick, and
(b) the furring shall be,
(i) 19 mm by 89 mm wood furring spaced at not more than 600 mm o.c., or
(ii) 19 mm by 64 mm wood furring spaced at not more than 400 mm o.c.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.