9.23.6.2.Anchorage of Columns and Posts
(1) Except as provided in Sentences (2) and (3), exterior columns and posts shall be anchored to resist uplift and lateral
movement.
(2) Except as provided in Sentence (3), where columns or posts support balconies, decks, verandas and other exterior
platforms, and the distance from finished ground to the underside of the joists is not more than 600 mm,
(a) the columns or posts shall be anchored to the foundation to resist uplift and lateral movement, or
(b) the supported joists or beams shall be directly anchored to the ground to resist uplift.
(3) Anchorage is not required for platforms described in Sentence (2) that
(a) are not more than 1 storey in height,
(b) are not more than 55 m² in area,
(c) do not support a roof, and
(d) are not attached to another structure, unless it can be demonstrated that differential movement will not adversely
affect the performance of the structure to which the platform is attached.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.