PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.23.16.6.Edge Support
(1) Except as permitted in Sentence (2), where panel-type roof sheathing requires edge support, the support shall consist
of metal H clips or not less than 38 mm by 38 mm blocking securely nailed between framing members.
(2) The supports referred to in Sentence (1) are not required when tongued-and-grooved edged panel-type sheathing
board is used.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.