PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.23.13.1.Requirements for Low to Moderate Wind and Seismic Forces
(See Note A-9.23.13.1.)
(1) This Article applies in locations where the seismic spectral acceleration, Sa(0.2), is not more than 0.70 and the 1-in-
50 hourly wind pressure is less than 0.80 kPa.
(2) Bracing to resist lateral loads shall be designed and constructed as follows:
(a) exterior walls shall be
(i) clad with panel-type cladding in accordance with Section 9.27.,
(ii) sheathed with plywood, OSB, waferboard, fibreboard, gypsum board or diagonal lumber sheathing complying
with Subsection 9.23.17. and fastened in accordance with Table 9.23.3.5.-A, or
(iii) finished on the interior with a panel-type material in accordance with the requirements of Section 9.29., or
(b) in accordance with
(i) Articles 9.23.13.4. to 9.23.13.7.,
(ii) Part 4, or
(iii) good engineering practice such as that provided in CWC 2014, “Engineering Guide for Wood Frame
Construction.”
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
← Previous9.23.12.3. Lintel Spans and SizesNext →9.23.13.2. Requirements for High Wind and Seismic Forces
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.