9.21.4.6.Chimney Caps
(1) The top of a chimney shall have a waterproof cap of reinforced concrete, masonry or metal.
(2) The cap required in Sentence (1) shall slope from the lining and be provided with a drip not less than 25 mm from
the chimney wall.
(3) Cast-in-place concrete caps shall be separated from the chimney liner by a bond break and be sealed at that location.
(4) Jointed precast concrete or masonry chimney caps shall have flashing installed beneath the cap extending from the
liner to the drip edge.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.