9.15.1.1.General (See Notes A-9.15.1.1., and A-9.4.4.6. and 9.15.1.1.)
(1) Except as provided in Articles 9.15.1.2. and 9.15.1.3., this Section applies to
(a) concrete or unit masonry foundation walls and concrete footings not subject to surcharge
(i) on stable soils with an allowable bearing pressure of 75 kPa or greater, and
(ii) for buildings of wood-frame or masonry construction,
(b) wood-frame foundation walls and wood or concrete footings not subject to surcharge
(i) on stable soils with an allowable bearing pressure of 75 kPa or greater, and
(ii) for buildings of wood-frame construction, and
(c) flat insulating concrete form foundation walls and concrete footings not subject to surcharge (See Note A-
9.15.1.1.(1)(c) and 9.20.1.1.(1)(b))
(i) on stable soils with an allowable bearing pressure of 75 kPa or greater, and
(ii) for buildings of light-frame or flat insulating concrete form construction that are not more than 2 storeys in
building height, with a maximum floor-to-floor height of 3 m.
(2) Foundations for applications other than as described in Sentence (1) shall be designed in accordance with
Section 9.4.
(3) Where a foundation is erected on filled ground, peat or sensitive clay, the footing sizes shall be designed in
conformance with Section 4.2.
(4) For the purpose of Sentence (3), sensitive clay means the grain size of the majority of the particles is smaller than
0.002 mm, including leda clay.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.