9.13.2.5.Moisture Protection for Interior Finishes (See Note A-9.13.2.5.)
(1) The interior surface of foundation walls below ground level shall be protected by means that minimize the ingress of
moisture from the foundation wall into interior spaces, where
(a) a separate interior finish is applied to a concrete or unit masonry wall that is in contact with the soil, or
(b) wood members are placed in contact with such walls for the installation of insulation or finish.
(2) Except as provided in Sentence (3), where the protection of interior finishes required in Sentence (1) consists of
membranes or coatings,
(a) the membrane or coating shall extend from the basement floor surface up to the highest extent of the interior
insulation or finish, but not higher than the exterior finished ground level, and
(b) no membrane or coating with a permeance less than 170 ng/(Pa×s×m2) shall be applied to the interior surface of the
foundation wall above ground level between the insulation and the foundation wall.
(3) Where insulation functions as both moisture protection for interior finishes and as a vapour barrier in accordance
with Subsection 9.25.4., it shall be applied over the entire interior surface of the foundation wall.
← Previous9.13.2.4. Application of Dampproofing MaterialNext →9.13.2.6. Dampproofing of Floors-on-Ground
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.