9.10.8.3.Fire-Resistance Ratings for Walls, Columns and Arches
(1) Except as otherwise provided in this Subsection, all loadbearing walls, columns and arches in the storey
immediately below a floor or roof assembly shall have a fire-resistance rating of not less than that required for the
supported floor or roof assembly.
(2) Light-frame walls, columns, arches and beams as well as loadbearing steel elements that support floors between
dwelling units in a house with a secondary suite including their common spaces shall be protected by not less than
15.9 mm thick Type-X gypsum board. (See Note A-9.10.8.3.(2))
← Previous9.10.8.2. Fire-Resistance Ratings in Sprinklered BuildingsNext →9.10.8.4. Support of Noncombustible Construction
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.