PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.10.8.1.Fire-Resistance Ratings for Floors and Roofs
(1) Except as otherwise provided in this Subsection, the fire-resistance ratings of floors and roofs shall conform to
Table 9.10.8.1. (See Subsection 9.10.2. for mixed occupancies and Subsection 9.10.21. for construction camps.)
Table 9.10.8.1.
Fire Resistance Ratings for Floors and Roofs
Forming Part of Sentence 9.10.8.1.(1)
Minimum Fire-Resistance Rating by Building Element, min
Maximum Building
Major Occupancy Floors Except Floors over
Height, Storeys Mezzanine Floors Roofs
Crawl Spaces
Residential (Group C) 3 45 45 —
2 45 — —
All other occupancies
3 45 45 45
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
← Previous9.10.7.1. Protection of Steel MembersNext →9.10.8.2. Fire-Resistance Ratings in Sprinklered Buildings
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.