9.10.5.1.Permitted Openings in Wall and Ceiling Membranes
(1) Except as permitted in Sentences (2) and (3), a membrane forming part of an assembly required to have a fire-
resistance rating shall not be pierced by openings into the assembly unless the assembly has been tested and rated for
such openings.
(2) A wall or ceiling membrane forming part of an assembly required to have a fire-resistance rating is permitted to be
pierced by openings for electrical and similar service outlet boxes, provided such outlet boxes and the penetrations
conform to Article 9.10.9.8.
(2.1) Where boxes referred to in Sentence (2) are located on both sides of walls required to provide a fire-resistance
rating, they shall be offset where necessary to maintain the integrity of the fire separation.
(3) A membrane ceiling forming part of an assembly assigned a fire-resistance rating on the basis of Table 2 of MMAH
Supplementary Standard SB-3, “Fire and Sound Resistance Tables,” is permitted to be pierced by openings leading to
ducts within the ceiling space provided the ducts, the amount of openings and their protection conform to Sentence
9.10.13.14.(1) and the requirements in MMAH Supplementary Standard SB-2, “Fire Performance Ratings.”
← Previous9.10.4.4. Rooftop EnclosuresNext →9.10.6.1. Combustible Elements in Noncombustible Construct
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.