9.10.3.2.Flame-Spread Rating
(1) Where a flame-spread rating is required in this Section for an element of a building, such rating shall be determined
in accordance with the test methods described in Part 3, or in accordance with MMAH Supplementary Standard SB-2,
“Fire Performance Ratings.”
(2) Unless the flame-spread rating is referred to in this Part as a “surface flame-spread rating”, it shall apply to any
surface of the element being considered that would be exposed by cutting through it as well as to the exposed surface of
the element.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.