9.10.21.9.Hose Stations
(1) Every building in a camp for housing of workers providing sleeping accommodation for more than 30 persons shall
be provided with a hose station that is protected from freezing and equipped with a hose of sufficient length so that every
portion of the building is within the range of a hose stream.
(2) Hose stations required in Sentence (1) shall be located near an exit.
(3) Hoses referred to in Sentence (1) shall be not less than 19 mm inside diam and shall be connected to a central water
supply or to a storage tank having a capacity of not less than 4 500 L with a pumping system capable of supplying a flow
of not less than 5 L/s at a gauge pressure of 300 kPa.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.