9.10.21.6.Flame-Spread Ratings
(1) Except in dwelling units and except as provided in Sentence (2), the surface flame-spread rating of wall and ceiling
surfaces in corridors and walkways, exclusive of doors, shall not exceed 25 over not less than 90% of the exposed surface
area and not more than 150 over the remaining surface area.
(2) Except within dwelling units, corridors that provide access to exit from sleeping rooms and that have a fire-
resistance rating of not less than 45 min shall have a flame-spread rating conforming to the appropriate requirements in
Subsection 9.10.17.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.