9.10.21.4.Walkways Connecting Buildings
(1) Walkways of combustible construction connecting buildings shall be separated from each connected building by a
fire separation having not less than a 45 min fire-resistance rating.
← Previous9.10.21.3. Floor Assemblies Between the First and Second StNext →9.10.21.5. Spatial Separations
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.