9.10.19.6.Silencing of Smoke Alarms
(1) Except as permitted in Sentence (2), a manually operated device shall be incorporated within the circuitry of a smoke
alarm installed in a dwelling unit so that the signal emitted by the smoke alarm can be silenced for a period of not more
than 10 min, after which the smoke alarm will reset and sound again if the level of smoke in the vicinity is sufficient to re-
actuate it.
(2) Suites of residential occupancy equipped with smoke detectors installed to CAN/ULC-S524, “Standard for
Installation of Fire Alarm Systems,” which are part of the fire alarm system in lieu of smoke alarms as permitted in
Sentence 9.10.19.4.(3), need not incorporate the manually operated device required in Sentence (1).
← Previous9.10.19.5. Interconnection of Smoke AlarmsNext →9.10.19.7. Instructions for Maintenance and Care
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.