9.10.17.5.Walls in Public Corridors
(1) At least 90% of the total wall surface in any public corridor that is not sprinklered shall have a surface flame-spread
rating of not more than 75, or at least 90% of the upper half of such walls shall have a surface flame-spread rating of not
more than 25. (See Article 9.10.17.6.)
← Previous9.10.17.4. Exterior Exit PassagewaysNext →9.10.17.6. Calculation of Wall and Ceiling Areas
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.