9.10.16.1.Required Fire Blocks in Concealed Spaces
(1) Concealed spaces in interior walls, ceilings, floors and crawl spaces shall be separated by fire blocks from concealed
spaces in exterior walls and attic or roof spaces.
(2) Reserved.
(3) Fire blocks shall be provided at all interconnections between concealed vertical and horizontal spaces in interior
coved ceilings, drop ceilings and soffits where the exposed construction materials within the concealed spaces have a
surface flame-spread rating greater than 25.
(4) Fire blocks shall be provided at the top and bottom of each run of stairs where they pass through a floor containing
concealed space in which the exposed construction materials within the space have a surface flame-spread rating greater
than 25.
(5) Where not sprinklered, concealed spaces of combustible construction created by a ceiling, roof space or unoccupied
attic space shall be separated by fire blocks into compartments
(a) not more than 60 m in greatest dimension, and
(b) where such space contains exposed construction materials having a surface flame-spread rating greater than 25, not
more than 300 m2 in area.
(6) No dimension of the compartment described in Clause (5)(b) shall exceed 20 m.
(7) Concealed spaces in mansard or gambrel style roofs, exterior cornices, balconies and canopies of combustible
construction in which the exposed construction materials within the space have a surface flame-spread rating exceeding
25 shall have vertical fire blocks at intervals of not more than 20 m and at points where such concealed spaces extend
across the ends of required vertical fire separations.
← Previous9.10.15.5. Construction of Exposing Building Face of HousesNext →9.10.16.2. Required Fire Blocks in Wall Assemblies
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.