PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.10.13.8.Maximum Size of Opening
(1) The size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 11 m²,
with no dimension greater than 3.7 m, if a fire compartment on either side of the fire separation is not sprinklered.
(2) The size of an opening in an interior fire separation, even where protected with a closure, shall not exceed 22 m²,
with no dimension greater than 6 m, when the fire compartments on both sides of the fire separation are sprinklered.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.