PART 9 — HOUSING AND SMALL BUILDINGSUpdated for the 2024 Ontario Building Code
Try BUILDAiD Beta
9.10.10.3.Separation of Service Rooms
(1) Except as provided in Sentence (2) and Articles 9.10.10.5. and 9.10.10.6., service rooms shall be separated from the
remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h when the floor area
containing the service room is not sprinklered.
(2) Where a room contains a limited quantity of service equipment and the service equipment does not constitute a fire
hazard, the requirements in Sentence (1) shall not apply.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.