(1) Non-potable water systems shall be designed, fabricated and installed in accordance with this Subsection and good
engineering practice. (See Note A-7.7.1.1.(1))
(2) Except as provided in Sentence (3) and Subsection 7.7.2., non-potable water systems shall only be used to supply
water closets, urinals, trap seal primers, and directly connected underground irrigation systems that only dispense water
below the surface of the ground.
(3) Non-potable water systems shall not be used to supply fixtures in healthcare facilities.
(4) Where a non-potable water system is supplied by a potable water system, the potable water system shall be protected
in accordance with Article 7.6.2.1.
(5) Where the static pressure at any fixture in a non-potable water system may exceed 550 kPa, a pressure-reducing
valve shall be installed to limit the maximum static pressure at the fixture to 550 kPa.
(6) Where a clothes washer is supplied by a rainwater system and a potable water system, the potable water system
shall be protected by dual check valve backflow preventers conforming to CSA B64.6, “Dual check valve (DuC) backflow
preventers” for
(a) area isolation, and
(b) premise isolation.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.