7.6.2.1.Connection of Systems
(1) Connections to potable water systems shall be designed and installed so that non-potable water or substances that
may render the water non-potable cannot enter the system.
(2) Reserved.
(3) Backflow preventers shall be selected and installed in conformance with CSA B64.10, “Selection and installation of
backflow preventers.”
(3.1) No connection shall be made between a potable water system supplied with water from a drinking water system and
any other potable water system without the consent of the water purveyor.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.