PART 7 — PLUMBINGUpdated for the 2024 Ontario Building Code

7.5.9.2.Air Admittance Valves

(1) Air admittance valves shall only be used to vent (a) fixtures in buildings undergoing renovation, and (b) installations where connection to a vent may not be practical. (2) Air admittance valves shall be located (a) not less than 100 mm above the fixture drain being vented, (b) within the maximum developed length permitted for the vent, and (c) not less than 150 mm above insulation materials. (3) Air admittance valves shall (a) only vent fixtures located on the same storey, and (b) be connected to the horizontal fixture drain.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.