PART 7 — PLUMBINGUpdated for the 2024 Ontario Building Code

7.5.8.1.Hydraulic Loads Draining to Wet Vents

(1) The hydraulic load that drains to a wet vent shall conform to Table 7.5.8.1. (2) When determining the nominal pipe size of a wet vent, the hydraulic load from the most downstream fixture or symmetrically connected fixtures shall not be included. Table 7.5.8.1. Maximum Permitted Hydraulic Loads Drained to a Wet Vent Forming Part of Sentences 7.5.7.3.(2) and 7.5.8.1.(1) Maximum Hydraulic Load, Fixture Units Nominal Pipe Size of Wet Vent, NPS Fixtures, Other Than Water Closets, That Not Serving Water Closets Serve Not More Than 2 Water Closets 1½ 2 n/a 2 4 3 3 12 8 4 36 14 5 n/a 18 6 n/a 23

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.