PART 7 — PLUMBINGUpdated for the 2024 Ontario Building Code

7.5.1.1.Venting for Traps

(1) Except as provided in Sentences (3) and (4), traps shall be protected by a vent pipe. (2) Drainage systems may require additional protection as provided in Subsections 7.5.4. and 7.5.5. by the installation of (a) branch vents, (b) vent stacks, (c) stack vents, (d) vent headers, (e) fresh air inlets, (f) relief vents, (g) circuit vents, (h) yoke vents, (i) offset relief vents, (j) additional circuit vents, (k) wet vents, (l) individual vents, (m) dual vents, or (n) continuous vents. (3) A trap that serves a floor drain or hub drain need not be protected by a vent pipe separately where (a) the nominal pipe size of the trap is not less than NPS 3, (b) the length of the fixture drain is not less than 450 mm, (c) the fall on the fixture drain does not exceed its nominal pipe size. (4) A trap need not be protected by a vent pipe (a) where it serves (i) a subsoil drainage pipe, or (ii) a storm drainage system, or (b) where it forms part of an indirect drainage system. (See also Clause 7.4.2.3.(2)(b))

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.