(1) Except as permitted in Sentence (2), a backwater valve that would prevent free circulation of air shall not be
installed in a building drain or in a building sewer.
(2) A backwater valve may be installed in a building drain provided that,
(a) it is a “normally open” design conforming to,
(i) CAN/CSA-B70, “Cast Iron Soil Pipe, Fittings, and Means of Joining”,
(ii) CAN/CSA-B181.1, “Acrylonitrile-Butadiene-Styrene (ABS) Drain, Waste, and Vent Pipe and Pipe Fittings”,
(iii) CAN/CSA-B181.2, “Polyvinylchloride (PVC) and Chlorinated Polyvinylchloride (CPVC) Drain, Waste, and
Vent Pipe and Pipe Fittings”, or
(iv) CAN/CSA-B182.1, “Plastic Drain and Sewer Pipe and Pipe Fittings”, and
(b) it does not serve more than one dwelling unit.
(3) Except as provided in Sentences (4) and (5), where a building drain or a branch may be subject to backflow,
(a) a backwater valve shall be installed on every fixture drain connected to it when the fixture is located below the level
of the adjoining street, or
(b) a backwater valve shall be installed to protect fixtures which are below the upstream sanitary manhole cover when
a residential building is served by a public sanitary sewer.
(4) Where more than one fixture is located on a storey and all are connected to the same branch, the backwater
valve may be installed on the branch.
(5) A subsoil drainage pipe that drains into a sanitary drainage system that is subject to surcharge shall be connected in
such a manner that sewage cannot back up into the subsoil drainage pipe.
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.