7.4.10.5.Conversion of Fixture Units to Litres and Gal/min
(1) Except as provided in Sentence 7.4.10.3.(2), where the hydraulic load is to be expressed in litres, fixture units shall
be converted as follows:
(a) when the number of fixture units is 260 or fewer, the load is 2 360 L, and
(b) when the number of fixture units exceeds 260, the load is 9.1 L for each fixture unit.
(2) Where the hydraulic load is to be expressed in gal/min, fixture units shall be converted in accordance with
Table 7.4.10.5.
Table 7.4.10.5.(1)
Maximum Probable Drainage Rate, gal/min
Forming Part of Sentence 7.4.10.5.(2)
Fixture Units Fixture Units Fixture Units
Fixture Units in Service
Col. 1 Col. 1 × 10 Col. 1 × 100
100 53 174 900
90 51 164 835
80 49 153 750
70 47 140 680
60 44 128 600
50 41 115 520
40 38 102 435
30 33 88 350
20 27 72 262
10 21 53 174
Notes to Table 7.4.10.5.:
(1) See Note A-Table 7.4.10.5.
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
← Previous7.4.10.4. Hydraulic Loads from Roofs or Paved SurfacesNext →7.4.10.6. Hydraulic Loads to Soil or Waste Pipes
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.