PART 7 — PLUMBINGUpdated for the 2024 Ontario Building Code

7.4.10.5.Conversion of Fixture Units to Litres and Gal/min

(1) Except as provided in Sentence 7.4.10.3.(2), where the hydraulic load is to be expressed in litres, fixture units shall be converted as follows: (a) when the number of fixture units is 260 or fewer, the load is 2 360 L, and (b) when the number of fixture units exceeds 260, the load is 9.1 L for each fixture unit. (2) Where the hydraulic load is to be expressed in gal/min, fixture units shall be converted in accordance with Table 7.4.10.5. Table 7.4.10.5.(1) Maximum Probable Drainage Rate, gal/min Forming Part of Sentence 7.4.10.5.(2) Fixture Units Fixture Units Fixture Units Fixture Units in Service Col. 1 Col. 1 × 10 Col. 1 × 100 100 53 174 900 90 51 164 835 80 49 153 750 70 47 140 680 60 44 128 600 50 41 115 520 40 38 102 435 30 33 88 350 20 27 72 262 10 21 53 174 Notes to Table 7.4.10.5.: (1) See Note A-Table 7.4.10.5.

This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.

Understand this provision in seconds

BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.

Try BUILDAiD Beta

Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.