7.3.4.5.Support for Horizontal Piping
(1) Nominally horizontal piping that is inside a building shall be braced to prevent swaying and buckling and to control
the effects of thrust.
(2) Nominally horizontal piping shall be supported as stated in Table 2.3.4.5.
(3) Where PVC, CPVC or ABS plastic pipe is installed,
(a) the pipe shall be aligned without added strain on the piping,
(b) the pipe shall not be bent or pulled into position after being welded or joined, and
(c) hangers shall not compress, cut or abrade the pipe.
(4) Where PEX, PE-RT, PP-R, PE/AL/PE or PEX/AL/PEX plastic pipe or tube is installed, hangers shall not compress,
cut or abrade the pipe.
(5) Where hangers are used to support nominally horizontal piping, the hangers shall be
(a) supported by metal rods of not less than
(i) 6 mm diam to support piping of NPS 2 or less,
(ii) 8 mm diam to support piping of NPS 4 or less, and
(iii) 13 mm diam to support piping over NPS 4, or
(b) solid or perforated metal straps not less than
(i) 0.6 mm thick and 12 mm wide to support piping of NPS 2 or less, and
(ii) 0.8 mm thick and 18 mm wide to support piping of NPS 4 or less.
(6) Where a hanger is attached to concrete or masonry, it shall be fastened by metal or expansion-type plugs that are
inserted or built into the concrete or masonry.
Table 7.3.4.5.
Support for Nominally Horizontal Piping
Forming Part of Sentence 7.3.4.5.(2)
Maximum Horizontal Spacing
Piping Material Additional Support Conditions
of Supports, m
At the end of branches or fixture drains and
ABS or PVC plastic pipe 1.2
at changes in direction and elevation
ABS or PVC plastic trap arm or fixture drain pipe > 1 m
n/a As close as possible to the trap
long
Cast-iron pipe 3.0 At or adjacent to each hub or joint
Cast-iron pipe with mechanical joints that is ≤ 300 mm
1.0 None
long between adjacent fittings
Copper tube or copper and brass pipe, hard temper
• diameter > NPS 1 3.0
• diameter ≤ NPS 1 2.5 None
Copper tube, soft temper 2.5 None
CPVC pipe 1.0 None
Galvanized iron or steel pipe
• diameter ≥ NPS 6 3.75
• diameter < NPS 6 2.5 None
Lead pipe Throughout length of pipe None
PE/AL/PE composite pipe 1.0 None
PEX/AL/PEX composite pipe 1.0 None
PEX plastic pipe 0.8 None
PE-RT tube 0.8 None
At the end of branches and at changes
PP-R plastic pipe 1.0
in direction and elevation
Stainless steel pipe
• diameter ≥ NPS 1 3.0
• diameter < NPS 1 2.5 None
Stainless steel tube
• diameter ≥ NPS 1 3.0
• diameter < NPS 1 2.5 None
This provision includes a table — formatting is preserved from the source; refer to the official code for the authoritative layout.
← Previous7.3.4.4. Support for Vertical PipingNext →7.3.4.6. Support for Underground Horizontal Piping
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.