6.3.2.17.Fans and Associated Air-Handling Equipment
(1) Fans for heating, ventilating and air-conditioning systems shall be located and installed so that their operation
(a) does not adversely affect the draft required for proper operation of fuel-fired appliances, and
(b) does not allow the air in the duct system to be contaminated by air or gases from the boiler room or furnace room.
(2) Fans and associated air-handling equipment, such as air washers, filters and heating and cooling units, when
installed on the roof or elsewhere outside the building, shall be of a type designed for outdoor use.
← Previous6.3.2.16. Evaporative Air Coolers, Misters, Atomizers, AirNext →6.3.2.18. Vibration Isolation Connectors
Understand this provision in seconds
BUILDAiD Assist explains any article of the building code in plain English — with exact citations, exceptions and related requirements.
Code text is reproduced for reference from the Ontario Building Code (O. Reg. 163/24, 2024 Building Code Compendium). This page is provided for general information and is not an official copy. Always verify requirements against the official Ontario Building Code and confirm with your local building department.